579-1034AC   Rev G

TrueAlert ES Addressable Indoor A/O Notification Appliances Installation Instructions

*05791034ACG*

Cautions, warnings, and regulatory information

IMPORTANT: 

When the notification appliance emits light or sound, it indicates the possibility of an emergency situation that requires

immediate attention of all occupants.

SAFETY:

 Always install, maintain, and test notification appliances within their specifications. Failure to follow all safety precautions and instructions

may result in loss of life and property due to non-functioning notification appliances. Some notification appliances use high voltage. To avoid electrical

hazards and avoid damage to appliances, make sure that the electrical power for the Notification Appliance Circuit is disconnected at the control

panel before installing, repairing, or internally adjusting any notification appliances. Even with electrical power removed, some notification appliances

(such as visible strobes) store a high voltage charge. The high voltage can cause injury resulting in death from electrical shock. DO NOT TOUCH

EXPOSED CIRCUITRY.

LOCATION REFERENCE:

 Location and quantity of appliances required must conform to the applicable local standards and guidelines (the National

Fire Alarm and Signaling Code (NFPA 72); ULC Standard CAN/ULC-S524, Installation of Fire Alarm Systems; the appropriate model building codes,

etc.) and specific requirements of the Local Authority Having Jurisdiction (AHJ). These notification appliances are not intended for installation within

hazardous locations as defined by the National Electrical Code (NEC) or NFPA.

Introduction

Table 1: UL listed TrueAlert ES indoor product identification reference

Type

Colors

Models

Operation

Wall Mount Horn Audible

Only (AO)

Red
White

Components:

A49AO-APPLW

Backplate:

A49MP-AVVOWR
A49MP-AVVOWW

Covers:

A49AOC-WRFIRE
A49AOC-WRS
A49AOC-WWFIRE
A49AOC-WWS

These appliances provide an audible

(AO) warning of an alarm condition when

activated from the control panel of a

compatible UL/ULC Listed, Autocall Fire

Alarm System.

Note: 

For information about TrueAlert ES appliance testing, see 

TrueAlert ES Addressable Appliances testing and applications guide (579-1049).

Mounting instructions

Table 2: Kit contents

Kit contents

Appliance x 1

Cover x 1 Backplate x1 with 8-32 1 inch mounting screws x 2, and 6-32 1 inch mounting screws x 2.

Not included

Electrical box 1-1/2 inch (38.1 mm) minimum depth required: single gang, double gang, or 4 inch (101.6 mm) square.

1.

Select the mounting location and install the electrical box using screws suitable for the mounting surface. See Figure 1 for mounting and

location information.

2.

Bring the building wiring through the rectangular opening in the backplate.

3.

Connect the building wires to the backplate. See 

Wiring Instructions

 on page 2.

4.

Secure the backplate to the electrical box using the provided hardware. Install with the writing Install this side up at the top. Use a torque

wrench to tighten the screws to 12-15 inch-pounds. Do not over-tighten the screws.

5.

Attach the cover to the appliance.

6.

Set the appliance settings. See 

Setting the address DIP Switch

 on page 3.

7.

Attach the assembled appliance onto the backplate.

NFPA 72 requires that

the device is not

less than 80 in. (203.2 cm)

and not greater than

96 in. (243.8 cm) above

the finished floor.

Single gang, double gang, or 

4 in. (101.6 mm) square electrical box

 Backplate

Appliance cover

Building wire

Screws: Use 8-32 screws for a 4 in. (101.6 mm) square electrical box

              Use 6-32 screws for a single or a double gang electrical box

Appliance

100%

Fig 1: Mounting Instructions

Summary of Contents for A49AO-APPLW

Page 1: ...e Colors Models Operation Wall Mount Horn Audible Only AO Red White Components A49AO APPLW Backplate A49MP AVVOWR A49MP AVVOWW Covers A49AOC WRFIRE A49AOC WRS A49AOC WWFIRE A49AOC WWS These appliances provide an audible AO warning of an alarm condition when activated from the control panel of a compatible UL ULC Listed Autocall Fire Alarm System Note For information about TrueAlert ES appliance te...

Page 2: ...A O A O A O A O A O A O A O From a compatible SLC controller see notes Class B wiring see notes To the next appliance or compatible SLC controller see notes 100 Fig 2 Wiring Instructions Wiring notes The maximum number of appliances on a circuit or on an IDNAC SLC is 127 The maximum wire resistance between appliances is 26 ohms See the field wiring diagrams for the driving compatible fire alarm co...

Page 3: ...dress 7 Not used 001 101 011 111 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 DIP SWITCHES 5 THROUGH 7 000 100 010 110 Fig 3 Setting the DIP Switch Address Setting the horn configuration switch Certain options for the horn ca...

Page 4: ...le controller See Note 3 17 Min 23 31 Max 87 6 89 8 91 9 83 1 86 86 Low volume setting using addressable controller See Note 3 17 Min 23 31 Max 80 6 83 4 86 2 76 9 79 2 82 3 Anechoic Room at 10 feet in accordance with ULC S525 see note 4 High volume setting 17 Min 23 31 Max 89 9 92 5 94 4 89 6 92 4 93 9 Low volume setting 17 Min 23 31 Max 84 1 86 7 89 1 83 6 86 6 88 6 Note 1 The coded category cov...

Reviews: