background image

Part Number Key

AutomationDirect.com (ADC)

3505 Hutchinson Road, Cumming, GA   30040

Phone: (800) 633-0405 or (770) 889-2858

VADT SERIES

INSTALLATION 

INSTRUCTIONS

Quick Start Guide

1.  Ensure correct sensor model was chosen for 

monitored voltage of application.

2.  Mount the sensor to a DIN rail using an 

integrated mounting clip on the backside of the  

transducer.

3.  Connect input voltage to be monitored to 

terminals 5 & 6 using 30-12AWG copper wires 

rated 75/90°C, 5-7 in-lbs torque. Output and 

power wiring using 22AWG up to 12AWG copper 

wires rated 75/90°C, 6 in-lbs torque..

4.  

Connect 24VAC or DC power supply fused to 5 

amps to terminal 3 & 4.  

Do not connect power and signal together.

 

 

 

VADT - 050 - 42 - 24

SENSOR TYPE

VADT AC/DC Voltage

OUTPUT 

POWER SUPPLY

 

MONITORED VOLTAGE RANGE

015 - 15V

050 - 50V

150 - 150

500 - 500

24 - 24 VAC/DC

42 - 4-20mA

®

VADT - Inst - Rev 1     0820 

P-N 292180027 

Specifications

Power Supply

24 VAC/DC (+/-8.3%) External Power

(Note: Output and power supply negatives are 

not isolated.) 

Power Consumption

< 2VA

Voltage Measurement

15, 50, 150, and 500 VAC or DC

Frequency Range

0 - 5KHz

Output

4 - 20 mA

Output Limit

31mA

Response Time

500 ms (90% step change)

Accuracy

<1% Full Scale

Output Impedance

< 400

Ω

Isolation Voltage

UL tested to 2200VAC

Case

UL 94V-0 Flammability rated thermoplastic

Environmental

-Temp -4 to 122°F (-20 to 50°C)

-Humidity 0-95% RH, Non-condensing

-Pollution degree 2

-Altitude 2000 meters

Certifications

cULus listed E222847

CE

Warning! Risk of electric shock or 

personal injury

Safe operation can only be guaranteed if the 
device is used for the purpose for which it was 
designed and within the limits of the technical 
specifications. When this symbol is used, it 
means you should consult all documentation to 
understand the nature of potential hazards and 
the action required to avoid them.

Warning! Risk of hazardous voltage

When operating the device, certain parts may 
carry hazardous live voltage (e.g., primary 
conductor, secondary terminals). The device 
should not be put into service if the installation is 
not complete.

For products intended for the EU market, the 

following is applicable to the CE compliance of 

the product:

The VADT Series comply with EN 61010-1 CAT III 600V max 
measurement category. Use 24 V input power and fuse at 5 
amps. Power source overvoltage category I as defined per EN 
61010-1. 

Part No. VADT015-42-24

Reviews: