DURA

pulse

 GS4 AC Drive Quick-Start Guide – 1st Ed, Rev.C  07/02/2021

DURA

pulse

 GS4 AC Drive Quick-Start Guide

GS4_QSP_1edRevC 07/02/2021

GS4 AC Drives Installation Instructions

Sensorless Vector Control Variable Frequency Drive

•  Please read this instruction sheet thoroughly before installation and keep this instruction sheet.
•  To ensure the safety of operators and equipment, only qualified personnel familiar with AC drives should 

install, wire, program, and operate the GS4 drive.  Always read this instruction sheet thoroughly before using 

the GS4 drive, especially the WARNING, DANGER and CAUTION notes.  If you have any questions, please contact 

AutomationDirect.

PLEASE READ PRIOR TO INSTALLATION FOR SAFETY

DANGER

•  The ground terminal of the GS4 drive must be grounded correctly.  The grounding method 

must comply with the laws of the country where the GS4 drive is to be installed.

•  After power has been turned off, the capacitors in the GS4 drive may retain a charge for 

several minutes.  To prevent personal injury, visually verify that the “CHARGE” LED has 

turned off.  Then measure to confirm that the DC bus voltage level between terminals (+1) 

and (-) is less than 25VDC before touching any terminals.  (Will take at least 5 minutes for 

most GS4 models; 10 minutes for GS4 models ≥40hp.)

•  The CMOS ICs on the internal circuit boards of the GS4 drive are sensitive to static electricity.  

Please DO NOT touch the circuit boards with your bare hands before taking anti-static 

measures.  Never disassemble the internal components or circuits.

•  If wiring changes must be made, turn off power to the GS4 drive before making those 

changes.  Allow the internal DC bus capacitors in the GS4 drive sufficient time to discharge 

prior to making changes in power or control wiring.  Failure to do so may result in short 

circuit and fire.  To ensure personal safety, allow DC bus voltage to discharge to a safe level 

before making wiring changes to the GS4 drive.

•  DO NOT install the GS4 drive in locations subject to high temperature, direct sunlight, or 

flammable materials.

WARNING

•  Never apply power to the output terminals U/T1, V/T2, W/T3 of the GS4 drive.  If a fault 

occurs during operation of the GS4 drive, refer to the fault code descriptions and corrective 

actions to reset the fault before attempting to operate the GS4 drive.

•  DO NOT use Hi-pot test for internal components.  The semi-conductors in the GS4 drive are 

easily damaged by high voltage.

CAUTION

•  Long motor lead lengths may result in reflective wave due to impedance mismatch between 

the motor cable and the motor.  Reflective wave may damage the insulation of the motor.  

To avoid the possibility of reflective wave damage, use an inverter-rated motor with an 

insulation rating of 1600 volts.  A load reactor installed between the GS4 drive and motor 

will help to mitigate reflective wave.

•  Nominal supply voltage to the GS4 drive should be less than or equal to 240 volts AC for 

GS4-2xxx models, and less than or equal to 480 volts AC for GS4-4 models.

•  Nominal supply current capacity should be less than or equal to 5kA RMS for GS4 models of 

40hp or less, and less than or equal to 10kA RMS for GS4 models of 40hp and larger.

•  The GS4 drive must be installed in a clean, well-ventilated and dry location, free from 

corrosive gases or liquids.

•  The GS4 drive must be stored within an ambient temperature range from –25°C to +75°C, 

and relative humidity range of 0% to 90% without condensation.

•  Do not apply AC power to the GS4 drive with the front cover removed.  Following a fault of 

the GS4 drive, wait 5 seconds before pressing the RESET key.

•  To improve power factor, install a line reactor ahead of the GS4 drive.  Do not install power 

correction capacitors in the main AC supply circuit to the GS4 drive to prevent drive faults 

due to over-current.

Minimum Wiring

•  AC input power to L1, L2, L3 (for single-phase input, use two of the terminals) (For applicability of 1-phase input 

power, please refer to Chapter 1 of the DURApulse GS4 AC Drives User Manual at 

AutomationDirect.com

.)

•  Ground from the power supply
•  Drive power to the motor (U, V, W on T1, T2, T3) (For use with 3-phase motors only!)
•  Ground to the motor
•  STO1 and STO2 (both must be wired through appropriate N.C. safety-rated contacts to SCM1 and SCM2)

With this minimal wiring, the drive can be operated via the keypad to test the motor and drive installation.  

See the “Parameter Quick-Start Set Up” (

page 3

) section to configure the drive for keypad operation.

Recommended Safety Wiring

We strongly recommend that customers use the STO safety feature.
The Safe Torque Off (STO) function turns off the power supplied to the motor through the hardware, so 

that the motor cannot produce torque.  This method of removing power from the motor is considered an 

emergency stop, also known as “coast to stop.”
To use this feature, disconnect the appropriate factory-installed jumpers and wire a safety relay, safety PLC, 

or E-Stop pushbutton as shown.  See “GS4 with Sinking Digital Inputs” (

page 1

) for wiring using the GS4 

internal power supply, or Appendix E of the GS4 user manual for wiring using an external power supply.

Wiring Diagrams

RFI Jumper Removal

If the power distribution system supplying the GS4 AC drive is a floating (IT) or an asymmetric 

ground system, the RFI jumper must be removed. 

Removing the RFI jumper uncouples the internal RFI capacitor (filter capacitor) between the GS4 

drive frame and circuitry to avoid damaging those circuits and (according to IEC 61800-3) to reduce 

ground leakage current.

  GS4 Frame A through C

  GS4 Frame D0 through G

Mains Wiring (Power Circuit)

For main (power) wiring terminal specifications, Please refer to “Specifications for Wiring Terminals – 

Main-Circuit Terminals” (

page 6

).

  GS4 Frame A through C

Brake resistor

(optional)

DC choke

(optional)

R(L1)

S(L2)

T(L3)

(L1)
(L2)
(L3)

U(T1)
V(T2)

W(T3)

+2

B1

B2

+1

-

Jumper

AC Motor

3 Ø 

IM 

Mains Wiring Diagram

for frames A thru C

3-phase power is provided

For connection of Dynamic Braking Units and separate control power (large-frame drives only).

  GS4 Frames D and Larger

 

Control-Circuit Wiring

  GS4 with Sourcing Digital Inputs

SOURCING

 Mode (field devices are sinking)

FWD/STOP* **
REV/STOP* **
Multi-step 1*
Multi-step 2*
Multi-step 3*
Multi-step 4*

N/A*

N/A*
N/A*
N/A*

+

DCM
+24V

FWD 

DIC

REV
DI1 
DI2
DI3
DI4
DI5
DI6
DI7
DI8

Factory Settings

Internal

Power

Supply

NOTE

*  Do NOT apply mains voltage directly to above terminals.

**  If P4.09 = 1, FWD/REV direction is controlled by analog input only.

+

FWD/STOP* **
REV/STOP* **
Multi-step 1*

DCM
+24V

FWD 

DIC

REV

Wiring if using

an external

power supply

+24V

The rest of the control wiring is the same as for SINKING mode.

Internal P.S. = 200mA max

  GS4 with Sinking Digital Inputs

Control terminals

Shielded leads & Cable

SINKING

 Mode (field devices are sourcing)

Communication

extension card

Option 

Slot 1

5kΩ

3

2

1

Option 

Slot 3

8 1 8 1

Pin 1~2, 7, 8:  open or no connection

Pin 3, 6:GND

Pin 4:SG-

Pin 5:SG+

FWD/STOP* **
REV/STOP* **

Multi-step 1*
Multi-step 2*
Multi-step 3*
Multi-step 4*

N/A*

Multi-Function Output Terminals

I/O & RELAY

extension card 

N/A*
N/A*
N/A*

+

AO1

SGND

SG+

SG-

DO1 

DO2

DOC

FO

DCM

DCM

R1O

R2O

R2C

R2

+24V

FWD 

DIC

REV
DI1 
DI2
DI3
DI4
DI5
DI6
DI7
DI8

AO2

R1

R1C

+10V 

-10V 

AI1* 
AI2*
AI3
ACM

ACM

Factory Settings

RJ

45-1

RJ

45-2

Analog Signal Common

Analog Output 2 Terminal

0~10VDC / 4~20mA

Analog Output 1 Terminal

0~10VDC / -10~+10V

0~10V / 0~20mA / 4~20mA

0~10V / -10 to +10V

+10V / 20mA

-10V / 20mA

Analog Signal Common

Modbus RS-485

BACnet

Internal

Power

Supply

NOTE

*  Do NOT apply mains voltage directly to above terminals.

**  If P4.09 = 1, FWD/REV direction is controlled by analog input only.

SW3*

SW4*

* Ensure that the physical switches for AI1 and AI2 

(located above the control terminal blocks) are 

set for the correct voltage/current configuration.

NOTE

SW1*

SW2*

SCM1

STO1

+24V

STO2

ECM

Safety Relay,

Safety PLC,

or

E-Stop PB

(2 NC contacts required)

SCM2

NOHC
NOHC

Red

STO

Terminals

*

* Remove factory-installed short-circuit

 jumper from +24V–STO1–STO2 when

using STO function with in24VDC.

NOTE

See User Manual Appendix E

for STO details.

* Ensure that the physical 

switches for AO1 and AO2 

(located above the control 

terminal blocks) are set for 

the correct voltage/current 

configuration.

NOTE

0~10V / 0~20mA / 4~20mA

Resistive Load:

250VAC / 3A (N.O.)

250VAC / 3A (N.C.)

Inductive Load:

250VAC / 1.2A (N.O.)

250VAC / 1.2A (N.C.)

Estimate at COS (0.4)

Resistive Load:

30VDC / 5A (N.O.)

30VDC / 3A (N.C.)

+

FWD/STOP* **
REV/STOP* **

Multi-step 1*

DCM

+24V

FWD 

DIC

REV

Wiring if using

an external

power supply

Internal P.S. = 200mA max

Digital Output terminals

5~48 VDC / 50mA 

Digital Output terminals

5~48 VDC / 50mA 

Multi-Function Output

Frequency terminals

5~30VDC / 30mA 100kHz

Digital Output common

Specifications for Wiring Terminals – Control Circuit

GS4-xxxx All Models; All Frame Sizes

Terminal

Wire Gauge

Torque

A

24–16 AWG 

[0.20–1.31 mm

2

]

5kg·cm 

[4.3 lb·in]

B

26–16 AWG 

[0.13–1.31 mm

2

]

8kg·cm 

[6.9 lb·in]

C

24–16 AWG 

[0.20–1.31 mm

2

]

2kg·cm 

[1.7 lb·in]

FWD DI1 DI3 DI5 DI7 SGND

DCM REV DI2 DI4 DI6 DI8 SG+ SG-

0~10V

-10~10V

SW1

SW2

RJ45-1 RJ45-2

SW3

SW4

SW5

0~10V

0/4~20mA

AO2

AO1

0~10V

0/4~20mA

AI1

0/4~20mA

0~10V

AI2

Open

120Ω

485

Control circuit board is removable from the GS4 (for ease of wiring)

R2

R1O

R1C

R1

R2O

R2C

A

B

C

AO1

D01

AI3

AI1

+10V

D02

D02

STO1

+24V

STO2

AO2

DOC

ACM

AI2

-10V

FO

SCM1

ECM

SCM2

+24V DIC

IM

Motor

U(T1)

V(T2)

W(T3)

-/DC-

+1/DC+

R(L1)
S(L2)
T(L3)

R(L1)

S(L2)
T(L3)

Fuse/No Fuse Breaker

NFB

Wiring diagram for frame D and larger

3-phase power is provided

DC+/DC- are for optional

Dynamic Braking Unit wiring

(do not connect a braking resistor

directly to these terminals)

Summary of Contents for DURApulse GS4

Page 1: ...ardware so that the motor cannot produce torque This method of removing power from the motor is considered an emergency stop also known as coast to stop To use this feature disconnect the appropriate...

Page 2: ...er to P3 00 P3 01 P4 00 and P4 01 for defining LOCAL and REMOTE sources of operation and frequency Descriptions of LED Functions Steady ON Drive is running Blinking Drive is stopping or in base block...

Page 3: ...e five menus described in the following table Then set the applicable parameters for that application as shown Please refer to the user manual if you need more detailed information about the parameter...

Page 4: ...VDC 390 0 780 0 11 P6 29 Line Start Lockout 0 Enable start up lockout 1 Disable start up lockout 0 12 P6 31 Cooling Fan Control 0 Always ON 1 Fan OFF 1 minute after Stop 2 Run fan ON Stop fan OFF 3 He...

Page 5: ...Rate for Cooling Power Dissipation Model Number Flow Rate cfm Flow Rate m3 hr Power Dissipation Watt External Internal Total External Internal Total Loss External Heat sink Internal Total GS4 21P0 33...

Page 6: ...cification Fig 2 The figure shows the specification of insulated heat shrink tubing that complies with UL 600C YDPU2 Figure 1 Figure 2 GS4 22P0 12 AWG 3 3 mm2 GS4 23P0 10 AWG 5 3 mm2 GS4 25P0 8 AWG 8...

Page 7: ...t exceeds 45 C UL installations of other models must use 600V 75 C or 90 C wire Please use copper wire only Fig 1 The usage of ring terminals for R L11 R L12 S L21 S L22 T L31 and T L32 should comply...

Page 8: ...11 22 550 0 21 65 525 0 20 67 492 0 19 37 107 2 4 22 16 0 0 63 11 0 0 43 18 0 0 71 D1 Flange mounting GS4 Frame D with conduit box Units mm in W W1 1 2 3 H H1 H2 S1 S1 SEE DETAIL A DETAIL A MOUNTING H...

Page 9: ...ge during Accel ovA 8 Overvoltage during Decel ovd 9 Overvoltage during normal speed ovn 10 Overvoltage during Stop ovS 11 Low voltage during Accel LvA 12 Low voltage during Decel Lvd 13 Low voltage d...