background image

2615 Wentz Avenue, Saskatoon, SK S7K 5J1    Ph: (306) 651-1815    Fax: (306) 651-2293 

email: sales@axiomind.com    website: www.axiomind.com

 

 

 
 

Installation, operation, and maintenance instructions 

for the Puropal-Pro-25 and Puropal-Pro-50 H

2

demineralizers 

 
 

Function 

 
The Puropal-Pro filters lime and aggressive dissolved substances such as sulfates, nitrates and 
chlorides out of the local domestic water. The device operates on the basis of a mixed bed ion 
exchange resin and provides completely demineralized water that meets fill water specifications of 
glycol and boiler manufacturers. It is also possible to demineralize an existing “water only” system 
by circulating the system water through the Puropal-Pro demineralizing cart. This method does not 
release any chemical additives into the water. The device operates without an external power supply. 
Not for drinking water. 
 
The filling apparatus is equipped with precise meters for monitoring pure water production in terms 
of quality and quantity. 
 
If the mixed bed ion exchange resin capacity is exhausted, then it can be easily replaced and disposed 
of with the household waste. 

 
Protective measures 

 
Only trained personnel should use the filling apparatus. 
 
Operating specifications must be adhered to according to this manual. 
 
Local guidelines are to be followed for the connection between the local domestic water supply and 
the closed loop hydronic system.  
 
The system is not suitable for unmonitored, permanent connection under pressure. The valves in the 
input and output are to be kept closed and only to be opened for the duration of the system filling. 
 
Even demineralized water contains dissolved gasses, including oxygen and carbon dioxide that can 
cause the beginning of the corrosion process. The gases are purged by heating the water, therefore we 
recommend carrying out a heating test run for the system as soon as possible after fill-up. 

 

Summary of Contents for Puropal-Pro-25

Page 1: ...or drinking water The filling apparatus is equipped with precise meters for monitoring pure water production in terms of quality and quantity If the mixed bed ion exchange resin capacity is exhausted...

Page 2: ...ection under pressure is not permitted Under normal domestic water pressure the flow rate through the Puropal Jr Pro is approximately 6 6 gpm 25 l min Figure 1 Connections Open the drain valve on the...

Page 3: ...meter shows the total amount of water including mixed water It is recommended to log the last meter reading when changing the resin because the meter cannot be reset Mixing valve If demineralization...

Page 4: ...below Example With a hardness of 11 7 gpg 200 ppm Puropal Pro 25 provides 725 gal 2750 L of completely demineralized water and Puropal Pro 50 provides 1780 gal 6750 L Capacity of the Puropal Pro 25 5...

Page 5: ...connected to the untreated water tap 3 2 Connect hose to drain valve 4 and insert it into the supplied water permeable collection sack Tightly connect the sack to the top of the hose with a cable bin...

Page 6: ...l leak into the system Figure 5 Filling the Puropal Pro with new resin Check that the spray hose is pressed tightly into the head and is sealed otherwise resin will leak into the system Make sure that...

Page 7: ...to read or contains illegible characters Change batteries See Fig 6 below The display shows ERR Measuring device malfunction Reset by switching on and off quickly 2 3 times until the display is norma...

Page 8: ...de of the cartridge is blocked Loosen screw rinse out fine sieve and reattach See Fig 7 below Figure 7 Location of fine sieve at outlet Drain sieve for residual water Damage Preventative solution The...