AB-6439 

  Azbil Corporation’s controller Infilex series:  Infilex is named for “Infinity” and “Flexible”.

 

 

Specifications/Instructions

 

Infilex

 ZM 

Zone Manager 

Model WY5122 

 
General 

Infilex ZM (Infilex: named for “Infinity” and “Flexible”) Model 
WY5122, integrated into savic-net FX

 BMS (building 

management system), manages remote units (also called 
sub-controllers), such as Infilex VC, Infilex FC, and Infilex 
SC.   

Up to 50 remote units can be connected.  Infilex ZM can 
control these units separately as well as per group. 

Infilex ZM communicates with the savic-net

 FX center unit 

through the transmission trunk line NC-bus and with the 
remote units through the transmission trunk line SC-bus. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Features 

 Compact 

design: 

Small size body ensures space saving. 

 Installation: 

A quick-fit screwless (clamp) terminal block is used for 
the communication terminal block of the I/O module, 
ensuring the labor saving of the wiring work. 
Additionally, either DIN rail mounting or screw mounting 
can be selected. 

 

Management of remote units: 
Infilex ZM manages up to 50 connected remote units 
(Infilex VC, Infilex FC, Infilex SC, etc.), allowing ON/OFF, 
failure monitoring, measuring, and setting individually 
from the BMS center unit.  Infilex ZM can perform such 
managements of remote units by group and is applicable 
to any group configuration consisting of up to 50 units of 
Infilex VC and Infilex FC.  Additionally, Infilex ZM 
provides flexible management.  For example, group 
ON/OFF can be commanded even when individual 
measuring is commanded. 

 

Risk diversification and high-speed supervision: 
Infilex ZM has 50 programs of time schedules, analog 
alarm monitoring, and runtime/cycle-count integrating in 
order to manage the connected Infilex VC, Infilex FC, 
Infilex SC, etc.  This achieves diversification of risks and 
high-speed supervision of BMS. 

 

  One Infilex ZM controls up to 4 sets of VAV (VAV: 

variable air volume, controlled by Infilex VC) and AHU 
(controlled by Infilex GC).  Load reset control of supply 
air temperature, fan speed control, interlocking operation 
are available.  Additionally, the mixing loss control of the 
interior VAV and perimeter FCU (fan coil unit) can be 
performed. 

 Support 

functions: 

Infilex ZM supports to adjust VAV by setting the 
max./min. air volume levels of all VAV units included in a 
specified set.  Infilex ZM also supports to adjust 
AHU/FCU flow rate and to flush the piping by fully 
opening and closing all the valves that the Infilex ZM 
controls. 

 

CE Marking certified product: 
Infilex ZM Model WY5122W0000 (NC-bus model (Line 
A)) conforms to all the applicable standards of CE 
Marking (Class A). 

 

 

 

 

Summary of Contents for Infilex ZM WY5122

Page 1: ... unit Infilex ZM can perform such managements of remote units by group and is applicable to any group configuration consisting of up to 50 units of Infilex VC and Infilex FC Additionally Infilex ZM provides flexible management For example group ON OFF can be commanded even when individual measuring is commanded Risk diversification and high speed supervision Infilex ZM has 50 programs of time sche...

Page 2: ...ll applicable safety standards This product must be operated under the operating conditions power temperature humidity vibration shock installation position atmospheric condition etc specified in this manual to prevent equipment damages All wiring must comply with local codes of indoor wiring and electric installation rules Use crimp terminal lugs with insulation for electric wires connected to th...

Page 3: ...l WY5110 PMX III Model WY2001 Infilex ZM Model WY5122 Infilex FC Model WY5205 Infilex VC Model WY5206 BMIF Building Multi Air Conditioning Interface DIF DGP Data Gathering Panel Interface DIF II DGP Interface II DSS Data Storage Server MIS Management Integration Server NC bus New Controller bus PMX III PARAMATRIX III SC bus Sub Controller bus SCS System Core Server SMS System Management Server Neo...

Page 4: ...eration Red LED ON Minor failure or system restart Operation Minor failure ERR2 Red LED OFF Normal operation NC bus Transmit TX Receive RX Communication SC bus Transmit TX Receive RX LED Flashing ON OFF POWER ON OFF NC bus TX Normal Abnormal NC bus RX Normal Abnormal SC bus TX Normal Abnormal SC bus RX Normal Abnormal ERR1 Abnormal Normal LED indication Description of LED indication ERR2 Abnormal ...

Page 5: ...ng bands so as not to hide LED Data Setter connector mark switch battery holder or tag JIS Japanese Industrial Standards JCS Japanese Electric Wire and Cable Makers Association CE Marking Conformity This product must be installed in a panel cabinet Besides the product in the panel cabinet must be out of reach of unauthorized people who are not well trained for electric facilities This product comp...

Page 6: ...AB 6439 6 Dimensions Figure 3 Dimensions mm 140 60 90 8mm Stripping Length BATT S S NC bus NC bus CN1 O 3 2 1 POWER I SC bus ERR1 ERR2 S1 H MMI RX Tx RX Tx 6 5 7 8 9 10 SC bus E 4 12 11 ...

Page 7: ...At this time hold the male connector with the mark facing left and insert it as the mark points to the mark on the Infilex ZM main unit 2 Connection of Data Setter Model QY7211A Convert the D SUB connector to the mini DIN connector with the conversion cable Part No 83104995 001 At this time hold the male connector with the mark facing left and insert it as the mark points to the mark on the Infile...

Page 8: ...hows the maintenance clearance Figure 6 Mounting dimensions DIN rail mounting mm Direct screw mounting When Infilex ZM is mounted with screws the screw tab Part No 83165861 001 is required Mount and fix Infilex ZM on the wall with two M4 8 screws Lengthwise mounting Incorrect mounting Crosswise 2 face up Notes 1 Hatched are shows the maintenance space 2 Do not mount Infilex ZM in crosswise face up...

Page 9: ...he cables connected to Infilex ZM so as not to hide the parts shown in Fig 8 Make sure there is no slack in the wires from the cable ducts to Infilex ZM Figure 8 Connected wires in position System indication label for the controller number The indication tag has the system indication label on its back Turn it over and fill in the controller number on the label Figure 9 System indication label Prot...

Page 10: ...n use in ON state If the product has never or hardly been operated in OFF state for a year replace the lithium battery before the product operation Battery replacement Replace the battery with the Infilex ZM in ON state Figure 11 Battery replacement 1 Pull out the battery holder using a slotted screwdriver 2 Disconnect the connector and detach the lithium battery from the battery holder 3 Place a ...

Page 11: ...e correctly connected Several tens of seconds are required for the product normal operation after the power is turned on During this time the red LED ERR1 major failure on the front lights up indicating major failure temporarily but this does not indicate an error Do not connect wires to vacant terminals Leave at least 35 mm clearance between the top bottom surfaces of the product and other device...

Page 12: ...AB 6439 Specifications are subject to change without notice Building Systems Company http www azbil com Rev 8 0 Sep 2015 AB 6439 H W03 J AI 6439 Rev 4 2 Printed in Japan 12 ...

Reviews: