1.

General

1.1 

Use

The  flow  meter  is  used  as  a  flow  meter  for  calculators  for 
heating  or  cooling  consumption  measurement  in  systems  with 
water.  
The  flow  meter  consists  of  a  metal  measuring  part  and  an 
associated  electronic  unit.  These  two  components  are  affixed 
with each other by cable.  

1.2 

General Notes 

The  flow  meter  left  the  factory  in  a  faultless  condition  where 
safety  is  concerned.  The  manufacturer  will  provide  additional 
technical support on request. Calibration relevant security seal 
on the flow meter must not be damaged or removed. Otherwise 
the  guarantee  and  calibration  validity  of  the  flow  meter  will 
lapse. 

Keep the packaging so that you can transport the flow meter
in its original packaging following expiry of the calibration
validity.

Lay all cables at a minimum distance of 500 mm to high
voltage and high frequency cables.

A relative humidity of < 93 % at 25 °C is permissible (without
condensation). 

Avoid cavitation in the whole system due to overpressure
i.e. at least 1 bar at qp and approx. 3 bar at qs (applies for
approx. 80 °C).

2.

Safety Information

The  flow  meter  may  only  be  used  in  building  service 
engineering  systems  and  only  for  the  applications 
described. 
The  local  regulations  (installation  etc.)  must  be 
adhered to. 
Adhere  to  the  operating  conditions  according  to  the 
dial  plate  during  use.  Non-adherence  can  cause 
hazards and the guarantee will lapse. 
The flow meter is only suitable for circulating water in 
heating systems. 

The flow meter is not suitable for drinking water.

Adhere  to  the  AGFW  requirements  regarding 
circulating water (FW510).

Do not lift the flow meter by the electronic unit.

Be  aware  of  sharp  points  on  the  thread,  flange  and 
measuring tube.
Only  personnel,  trained  in  the  installation  and 
operation  of  meters  in  heating  and  cooling  systems, 
may install and remove the flow meter.
Only install or remove the flow meter when the pipes 
are pressure-less.
After installing the flow meter, check the leak-tightness 
of the system.
Guarantee  and  calibration  validity  will  lapse  if  the 
calibration relevant security seals are broken.

Only  clean  the  flow  meter  from  outside  with  a  soft, 
lightly  wetted  cloth.  Do  not  use  any  spirit  or  cleaning 
solvent. 
As  far  as  disposal  is  concerned,  the  flow  meter  is  a 
waste  electronic  appliance  in  the  sense  of  European 
Directive  2002/96/EC  (WEEE)  and  it  must  not  be 
disposed of as domestic waste. The relevant national, 
legal  regulations  must  be  observed  as  the  appliance 
must be disposed of via the channels provided for this 
purpose. The local and currently valid legislation must 
be observed.
The meter contains lithium batteries. Do not dispose of 
the  meter  and  the  batteries  with  domestic  waste. 
Observe the local stipulations and laws on disposal. 
You  can  return  the  lithium  batteries  to  the 
manufacturer  for  appropriate  disposal  following  use. 
When  shipping  please  observes  legal  regulations,  in 
particular, those governing the labelling and packaging 
of hazardous goods.
Do not open the batteries. Do not bring batteries into 
contact  with  water  or  expose  to  temperatures  above 
80 °C.
The flow meter does not have any lightning protection. 
Ensure  lightning  protection  via  the  in-house 
installation.

3.

Installation

Proceed as follows to install the flow meter: 

Observe the dimensions of the flow meter and check
whether there is sufficient space available.

Rinse the system thoroughly before installing the flow meter.

Fit the flow meter vertically or horizontally between two slide
valves so that the arrow on the housing and the flow
direction match. Also observe the installation situations and
the following examples of installation (see figure 2 and
figure 3).

Seal the fittings to protect against manipulation.

Loosen the elastic band or the cable tie, provided for the
transport, from the volume measurement unit. In operation,
the control cable should not depend directly on the volume
measurement unit.

If you install the flow meter for cold metering, follow the
appropriate notes.

Recommendation:

 If you are installing more flow meters in one 

unit, make sure that all the flow meters operate under the same 
mounting conditions. 

Installation Notes 

Note:

  When  installing  the  flow  meter  the  locally 

applicable  installation  regulation  for  flow  meters  must 
be observed. 

Inlet or outlet sections are not necessary. If you install the flow 
meter in the common return of two circuits, determine a place of 
installation  with  a  minimum  distance  of  10 × DN  from  the  T-
piece.  This  distance  ensures  a  good  thorough  mixing  of  the 
different water temperatures.  