background image

1:  OVERVIEW

The Bacharach MVR-300 UK version detects refrigerant leaks in 

occupied spaces.

4:  SAFETY INSTRUCTIONS

CODE COMPLIANCE:  

Comply with all local and national 

laws, rules, wiring codes, and regulations associated with 

this equipment. 

TECHNICIAN USE ONLY: 

This unit must be installed by a 

suitably qualified technician who will install this unit in 

accordance with these instructions and the standards in his 

particular industry/country. Operators of the unit should be 

aware of the regulations and standards in their indus

-

try/country for the operation of this unit. These notes are 

only intended as a guide and the manufacturer bears no 

responsibility for the installation or operation of this unit.

Failure to install and operate the unit in accordance with 

these instructions and with industry guidelines may cause 

serious injury including death and the manufacturer will not 

be held responsible in this regard.

SAFE MOUNTING:

 This detector must be connected by a 

marked, suitably located and easily reached switch or 

circuit-breaker as means of disconnection.

CAUTION:  

DO NOT MOUNT the MVR-300 in an 

area that may contain flammable liquids or 

vapors. Operation of electrical equipment in 

such an area constitutes a safety hazard.

World Headquarters

621 Hunt Valley Circle

New Kensington, PA 15068  USA

Phone: 724-334-5000 • Fax: 724-334-5001

Toll Free: 1-800-736-4666

114A Georges Street Lower 

Dun Laoghaire • Co Dublin • Ireland 

Phone: +353 1 284 6388

Fax: +353 1 284 6389 

CAUTION:

  Mounting in ceiling voids in a hotel 

room would not strictly comply with EN378.

IMPORTANT: 

 Mount at a height between 100 

and 150 mm (4 and 6 inches) off the floor.  

Avoid drafts and heat sources (like radiators), 

and avoid sources of steam.

P/N: 6203-9002       Revision 2 

August 2018

INSTALLATION GUIDE

MVR-300 Proper vs. Improper Placement Locations

6:  INSTALLATION

REFRIGERANT

GAS DETECTOR

Website: www.mybacharach.com  ●  E-mail: help@mybacharach.com

CAUTION:

  Ensure all wiring 

connections are made 

before

 

applying power.

ENVIRONMENTAL CONSIDERATIONS:

  Carefully 

consider the full range of environmental conditions 

to which the instruments will be exposed.

TARGET GAS CONSIDERATIONS: 

 The physical data of 

the gas or vapor to be detected must be observed.

APPLICATION CONSIDERATIONS: 

 The specifics of the 

application (for example, possible leaks, air move

-

ment/draft, etc.) must be observed.

ACCESSIBILITY CONSIDERATIONS:  

The degree of 

accessibility required for maintenance purposes 

must be granted.

ELECTRONIC CONSIDERATIONS: 

The system contains 

sensitive electronic components that can be easily 

damaged. Do not touch or disturb any of these 

components.

2:  MOUNTING CONSIDERATIONS

Mount the MVR-300 according to the above considerations, 

product dimensions, and maximum wiring lengths.

3:  INSTALLATION SPECIFICATIONS

Outputs: 

Relay outputs (2)

 

 

2 SPDT, 1 A at 30 VDC,

 

 

1 A at 125 and 250 VAC, resistive load

Modbus:

 

Connection:  RS-485 terminal block

 

 

Baud rate:  9600 or 19200 (selectable)

 

 

Default baud:  9600

 

 

Start bits:  1; 

Data bits:  8

 

 

Parity:  None (default), odd, even (selectable)

 

 

Stop bits:  1 (default) or 2 (selectable)

 

 

Retry time:  500 ms (min) between retries

 

 

End of msg:  Silent 3.5 characters

Power: 

 

100 to 240 VAC, 50/60 Hz, 4 W

Wiring Power:

  3-core cable, 14 to 20 AWG (0.5 to 2.0 mm

2

Wiring Relays:

  3-core cable, 18 to 20 AWG (0.5 to 1.0 mm

2

)

Wiring Modbus:

  2-core twisted, shielded pair 18 to 24 AWG

 

 

(0.2 to 1 mm

2

) with 120 Ω characteristic

 

 

impedance;  Use Belden 8761 or similar; 

 

 

Maximum diameter of cable + heat shrink

  must 

be 

≤5 mm (0.2 in)

NOTE:

  The MVR-300 UK is designed for use in 

2-gang and 3-gang UK back boxes with a minimum 

depth of 47 mm (1.9”).

The refrigerant detector can be calibrated and maintained 

non-intrusively using a magnetic wand.

The detector is for indoor applications. It is housed in an ABS 

enclosure that fits into most 2-gang UK electrical back boxes 

(not included).   Thinner 

metal

 mounting tabs are provided for 

flush mounting in UK back boxes with higher mounting tabs.

Copyright ©

 2018 Bacharach, Inc.  All Rights Reserved

5:  CONFIGURATION

When inserting the wire into the terminal, 

release the spring clamp by pushing back 

the release latch.

Push to release

1 2 3 4

ON

5 6 7 8

Gas alarms and status messages are indicated visually by a 

3-colored LED and audibly by a buzzer.  In case of an alarm 

and/or fault, relays switch (for example, shut-off valves or alarm 

devices).

NOTE:

  Before installing the MVR-300, refer to the 

calibration gas concentration label and record the 

value for use in step 16 of the calibration procedure.

NOTE:

  The manufacturer of this product requires that 

a bump test or calibration be performed following 

installation to verify instrument functionality.

CAUTION: 

 RS-485 signal cable must be 

insulated to the highest voltage level in the 

system. Protect the RS-485 signal cable by using 

the supplied installation kit.

1. Prepare signal cable and put boot over the signal cable.

2. Add appropriately sized ferules (not included) if required.

3. Apply 10 cm piece of shrink wrap as close to the wire ends/

    ferules as possible while leaving some free wire to allow

    connection to the detector.

4. Heat the shrink wrap.

5. Connect signal wires/ferules to the detector.

6. Slide rubber boot along the wire and shrink wrap assembly

    and connect it to the detector.

Po

w

er

Modbus

(See St

ep

s 1-6)

1 Restart

 

Off 

  Normal operation (Default)

 

On 

  Restart MVR-300

2,3  Alarm ON Delay

 

Off, Off  No delay (Default)

 

Off, On   5 minute delay

 

On, Off  10 minute delay

 

On, On   15 minute delay

Failsafe

 

Off 

  Normal relay operation (Default)

 

On 

  Failsafe relay operation

Relay 2 Fault Indication

 

Off 

  High alarm or fault (Default)

 

On 

  High alarm only

Alarm Latching

 

Off 

  Alarms automatically reset (Default)

 

On 

  Alarms latch and require manual reset

Buzzer Disable

 

Off 

  Buzzer enabled (Default)

 

On 

  Buzzer disabled

Enable Reset to Factory Defaults

 

Off 

  Normal operation (Default)

 

On 

  Reset enabled (see manual for details)

For more detailed information, scan here or 

visit www.mybacharach.com to access the 

MVR-300 User Manual (P/N 6203-9000).

Magnetic Wand

3-color status LED

Magnetic switch 1 (

)

Magnetic switch 2 (

••

)

Sensor Module

Plastic Mounting Tabs

Example of a customized

faceplate (not included)

Sample UK back box

(not included)

MVR-300 is a trademark of Bacharach, Inc.  All rights reserved.

Reviews: