Interface Module XC Modbus 

Protocol Converter / User Manual

 

Page 1 from 10 

E120103819092 

Baer Energie- & Messtechnik GmbH 

 Siemensstr. 3 

 D-90766 Fürth 

 Phone +49 911 970590 

 Fax +49 911 9705950 

 

 

General 

The 

Interface Module XC

 

Modbus

 is designed for use with the EMH LZQJ-XC and DMTZ-XC 

meters.

 

The module is equipped with a RS485 (2 wires) interface. The module can be plugged 

easily  into  the  module  compartment  of  the  meter.  It  can  be  mounted  or  exchanged  during 
operation  (without  breaking  approval  seal).  An  integrated  Modbus  interface  provides  a  simple 
means  of  connecting  multi-energy  meters.  This  makes  multi-energy  applications  an  affordable 
proposition  for  domestic  use.    Due  to  the  communication,  the  modules  are  suitable  for  a  lot  of 
control centres.

 

 

 

Compatible meters 

 

LZQJ-XC (special meter for industrial applications): 
- Standard meter for direct connection  
- Transformer connection version Cl. B (Cl. 1) 
- Precision meter Cl. C (Cl. 0.5S) 
- Precision meter Cl. 0,2S 

 

DMTZ-XC (industry meter)  

Functions 

 

RS-485 (2 wires) interface for bi-directional 
communications  

 

Protocol converter for meter data (max. 125 values) 
into Modbus-Format (non transparent data readout) 

 

Transmission protocol: Modbus RTU (8N1) 

 

Internal communication interface for the transfer 
service data (TS) between the meter and the 
interface module 

 

Internal power supply from meter 

 

Exchangeable during the meter operation  

Safety Notes 

 

 

The owner of the interface modules is responsible that all persons engaged on 
work with the modules: 
•  Are competent and qualified in accordance with national regulations (see ISSA 

"Guideline for Assessing the Competence of Electrically Skilled Persons").  

•  Have read and understood the relevant sections of the user manual.  
•  Strictly observe the safety regulations (according to the following section) and 

the instructions in the individual chapters.  

The owner of the modules is also responsible for:  
•  The protection of persons.  
•  The prevention of material damage.  
•  The training of personnel. 

The following safety regulations must be observed at all times:  
•  Devices which have fallen down should not be installed, even if no damage is apparent, and should 

be returned for testing to an authorised service centre (internal damage possible).  

• 

Modules must never be cleaned with running water or high pressure devices. Water can cause 
short-circuits or damage el. components.

 

Summary of Contents for Interface Module XC Modbus

Page 1: ...or meter data max 125 values into Modbus Format non transparent data readout Transmission protocol Modbus RTU 8N1 Internal communication interface for the transfer service data TS between the meter and the interface module Internal power supply from meter Exchangeable during the meter operation Safety Notes The owner of the interface modules is responsible that all persons engaged on work with the...

Page 2: ...erface module 2 Remove the terminal cover 5 3 Open the transparent module cover 1 4 Insert the interface module 3 carefully at the place provided in the meter 2 5 Push the module in to the internal contacts 6 Connect the cable 7 Close the transparent module cover 1 8 Close the terminal cover 5 Removing of the interface module 9 Remove the terminal cover 5 10 Open the transparent module cover 1 11 ...

Page 3: ...mmunications loop A SLAVE device never initiates a communications sequence All communications activity on the loop occurs in the form of PACKETS A packet is a serial string of 8 bit byte The maximum number of bytes contained within one packet is 255 All packets transmitted by a MASTER are REQUESTS All packets transmitted by a SLAVE are RESPONSES At most one SLAVE can respond to a single request fr...

Page 4: ...undancy Check Example ID Address 123Dec 7BHex start register 14Dec 00 0EHex of registers 2 one 32 bit value Request ID Addr Function Start register of registers CRC16 7B 03 00 0E 00 02 AE 52 Response ID Addr Function Register 1 Register 2 CRC16 7B 03 04 00 00 00 3B 60 27 Value 59Dec 00 00 00 3BHex Accepting the meter data The Modbus module reads the service data list TS from the meter periodically...

Page 5: ...erface Module XC Modbus uses the same baud rate like the communication interface at the meter For setting use please the EMH COMBI TOOL Software menu Meter Interfaces Electrical supplement aditional interface For correct working set please a fixed bad rate e g 9600 baud If you use the baud rate changeover according to mode C the communication is possible with 300 baud only For the addressing set t...

Page 6: ...ID Address For setting the meter data list use menu Lists Reading lists Service Table TS Note 1 The Modbus module uses for ID Address the first data value in the service data list TS register addresses 0 and 1 In this example we use the identification number 1 OBIS 0 0 1 for ID Address menu Meter Meter ID OBIS Register 0 0 1 e g value 123 00000123 Note 2 Only the first 125 values from the service ...

Page 7: ...ress Start register 22 Value 5001 C 86 0 38307030 Address Start register 24 Value 38307030 C 86 6 B05800F0 Address Start register 26 Value 58000 Modbus registers Register address Value Comments 0 0 OBIS Register 0 0 1 123 0 123 Modbus ID Address 1 007FHex 0123Dec 2 0 OBIS Register 1 25 0 kW 0 0 3 0 4 0 OBIS Register 3 25 0 kvar 0 0 5 0 6 0 OBIS Register 9 25 0 kVA 0 0 7 0 8 0 OBIS Register 31 25 0...

Page 8: ...imensions Ca 50mm x 105mm x 27mm W x H x D Nominal voltage Internal power supply from LZQJ XC or DMTZ XC meter Battery None Installation Exchangeable during the meter operation LED displays 3 LEDs green Power Tx power transmit data yellow Rx receive data red Error internal communication error Interface RS485 2 wires according to ANSI TIA EIA 485 A 98 Baud rate 300 to 19200 baud fixed baud rate Dat...

Page 9: ...tocol Converter User Manual Page 9 from 10 E120103819092 Baer Energie Messtechnik GmbH Siemensstr 3 D 90766 Fürth Phone 49 911 970590 Fax 49 911 9705950 Dimensions Note if necessary the 120Ω termination can be activated position ON ...

Page 10: ...tr 3 D 90766 Fürth Phone 49 911 970590 Fax 49 911 9705950 Subject to change without notice Version 2 01 Terminal assignment Terminal block Terminal Description A RS485 A Modbus B RS485 B Modbus Baer Energie Messtechnik GmbH Siemensstr 3 D 90766 Fürth Germany Phone 49 0 911 970590 Fax 49 0 911 9705950 Internet www baer gmbh com ...

Reviews: