background image

Configurable Gateway with 0 to 10V analog inputs and 0 to 10V analog outputs

IP67 Base
2.4 GHz

IP20 Base
900 MHz

For additional information, upda-
ted documentation, and acces-
sories, refer to Banner Engineer-
ing's website, 

www.bannerengin-

eering.com/surecross

.

The SureCross

®

 wireless system is a radio frequency network with integrated I/O that can operate

in most environments and eliminate the need for wiring runs. Wireless networks are formed around a
Gateway, which acts as the wireless network master device, and one or more Nodes.

• Wireless industrial I/O device with four 0 to 10V analog inputs and four 0 to 10V analog outputs
• 10 to 30V dc power input
• DIP switches for user configuration
• Modbus serial interface
• Site Survey analyzes the network’s signal strength and reliability and displays the results on the

Gateway's LCD

• Frequency Hopping Spread Spectrum (FHSS) technology and Time Division Multiple Access

(TDMA) control architecture ensure reliable data delivery within the unlicensed Industrial, Scien-
tific, and Medical (ISM) band

• Transceivers provide bidirectional communication between the Gateway and Node, including

fully acknowledged data transmission

• Lost RF links are detected and relevant outputs set to user-defined conditions
• The DX80...C models are certified for use in Class I, Division 2, Group A, B, C, D; Zone 2 (Cate-

gory 3G) Hazardous Locations when properly installed in accordance with the National Electrical
Code, the Canadian Electrical Code, or applicable local codes/regulations (see Specifications)

Models

Frequency

Environmental Rating

I/O

DX80G9M6S0P0V4V4

900 MHz ISM Band

IP67, NEMA 6

Inputs: Four 0 to 10V analog
Outputs: Four 0 to 10V analog

DX80G2M6S0P0V4V4

2.4 GHz ISM Band

DX80G9M6S0P0V4V4C

900 MHz ISM Band

IP20, NEMA 1
Class I, Division 2, Group A, B, C, D Haz-
ardous Locations (see Specifications)

DX80G2M6S0P0V4V4C

2.4 GHz ISM Band

Internal antenna models are also available, but are not UL Listed. For more information, contact your local Banner Engineering Corp.
representative.

WARNING: Not To Be Used for Personnel Protection
Never use this device as a sensing device for personnel protection. Doing so could lead to serious
injury or death.
 This device does not include the self-checking redundant circuitry necessary to allow its
use in personnel safety applications. A sensor failure or malfunction can cause either an energized or de-
energized sensor output condition.

The SureCross

®

 DX80 Wireless Network

Gateway

Node

Node

FlexPower Node
and Battery Supply Module

The SureCross

®

 DX80 wireless I/O network provides reliable moni-

toring without wiring or conduit installation. The SureCross wireless
network operates independently or in conjunction with a host system,
PLC, and/or PC software.
Each wireless network system consists of one Gateway and one or
more Nodes. Devices ship with factory-defined discrete, analog, or a
mix of discrete and analog inputs and outputs.
The SureCross

®

 DX80 network is a deterministic system—the net-

work identifies when the radio signal is lost and drives relevant out-

SureCross DX80 Gateway

 

 

P/N 136325 Rev. F

5/24/2013

0 136325

8

Summary of Contents for SureCross DX80G9M6S0P0V4V4C

Page 1: ...ian Electrical Code or applicable local codes regulations see Specifications Models Frequency Environmental Rating I O DX80G9M6S0P0V4V4 900 MHz ISM Band IP67 NEMA 6 Inputs Four 0 to 10V analog Outputs...

Page 2: ...n gineering com wireless Setting Up Your Wireless Network To set up and install your wireless network follow these steps 1 Configure the DIP switches of all devices 2 Connect the sensors to the SureCr...

Page 3: ...m of 16 devices Extended address mode uses a security code to bind Nodes to a specific Gateway Bound Nodes can only send and receive informa tion from the Gateway to which they are bound In extended a...

Page 4: ...dc common GND dc common GND dc common GND Rx RS485 D0 A B 3 6 to 5 5V dc Terminal Blocks Connecting dc power to the communication pins will cause permanent damage Do not exceed analog input ratings fo...

Page 5: ...should be at least two meters apart or the communications may fail LED 1 LED 2 Gateway Status solid green Power ON flashing red flashing red Device Error flashing yellow Modbus Communication Active f...

Page 6: ...247 ETSI EN In accordance with EN 300 328 V1 7 1 2006 05 IC 7044A DX8024 Spread Spectrum Technology FHSS Frequency Hopping Spread Spectrum Link Timeout Gateway Configurable Node Defined by Gateway Rad...

Page 7: ...waterproofing instructions Op erating the devices at the maximum operating conditions for exten ded periods can shorten the life of the device Certifications DX8x C External Wiring Terminal Models CS...

Page 8: ...to change Banner reserves the right to modify product specifications or to update docu mentation at any time For the most recent version of any documentation refer to www bannerengineering com 2006 20...