The BE1-50/51B Time Overcurrent Relay provides economical
overload and fault protection for generators, transformers, lines
and motors.

ADVANTAGES

• Self powered from 50/60Hz systems, available for 5 or 1 amp

CT secondaries.

• Ten field selectable curves.
• Independent instantaneous overcurrent function.
• Drawout construction, testable in the case.
• Qualified to the requirements of:

- IEEE C37.90-1989, C37.90.1-1989, C37.90.2-1989, UL508

• 200 series adds:

- Patented integrating reset characteristic, even when current
  goes to zero.
  Replicates electromechanical reset for all applications.
- Five additional field selectable curves, for a total of 15.

• Five year warranty.

ADDITIONAL INFORMATION

INSTRUCTION MANUAL

Request Publication 9252000991

TIMING CURVES

Request Publication 9252000998 or 9252000894 for Basler-equivalent IAC curves
Request Publication 9252000999 for Basler-equivalent CO and BS142 curves

STANDARDS, DIMENSIONS and ACCESSORIES

Request Publication SDA

FEATURES and

APPLICATION

Page 2

FUNCTIONAL

DESCRIPTION

Pages 2-5

SPECIFICATIONS

Pages 6 and 7

ORDERING

INFORMATION

Page 8

UHD-14

5-08

P. O. BOX 269 HIGHLAND, ILLINOIS, U.S.A. 62249   PHONE 618-654-2341   FAX 618-654-2351

BE1-50/51B

SELF POWERED

TIME OVERCURRENT

RELAY

Direct replacement "plug and play"

relays are available.

See Product Bulletin UHK.

Summary of Contents for BE1-50/51B

Page 1: ...echanical reset for all applications Five additional field selectable curves for a total of 15 Five year warranty ADDITIONALINFORMATION INSTRUCTION MANUAL RequestPublication9252000991 TIMING CURVES Re...

Page 2: ...for use in applications requiring time delayed coordination for phase or ground overcurrent condi tions The relay can be used to provide coordinated protection foroverheadandundergrounddistributionci...

Page 3: ...mps 0 2 to 19 8 Amps 2 from 0 1 to 2 from 0 2 to 19 8 Amps in 02 Amp Steps in 0 2 Amp Steps 3 18 Amps Operating power from the power supply is applied to the microprocessor supervisor circuit When the...

Page 4: ...to allow shorting the output terminals to verify external control circuit wiring TARGETS Two target indicators are provided as a standard feature of the BE1 50 51B These magnetically latched current o...

Page 5: ...B BS142 Very Inverse L Long Inverse I Inverse C BS142 Extremely Inverse D Definite Time V Very Inverse F Fixed Time E Extremely Inverse Figure 2 Time Current Characteristics IAC curves in 200 series m...

Page 6: ...des delays of 0 0 to 9 9 seconds corresponding to the dial setting BURDEN Burden is non linear and resistive 5 Amp Unit 4 8 Ohms 0 5A 0 2 Ohms 5A 1 Amp Unit 120 Ohms 0 1A 5 Ohms 1A TARGETS Magneticall...

Page 7: ...BE1 50 51B 7 SPECIFICATIONS continued AGENCY cURusrecognitionperULStandard508 FileE97035 and CSA Standard C22 2 No 14 CASE SIZE A1 or S1 NET WEIGHT 8 6 pounds...

Page 8: ...R NEW INSTALLATION PACKAGES For 5 Amp System CT Secondaries Semi Flush Mounting A1 Size Case BE1 50 51B 105 Drawout Construction Testable in Case BE1 50 51B 205 Projection Mounting S1 Size Case BE1 50...

Reviews: