75.0148 V1 July 2000
These power supplies are UL-Listed control units for use with electromagnetic locking devices and systems. They may be
ordered with optional battery backup systems to power devices in the case of power loss.
GENERAL DESCRIPTION:
12 VOLT
24 VOLT
POWER SUPPLY
10PS12 10PS24
POWER SUPPLY WITH
BATTERY BACKUP
10PS12PB 10PS24PB
DESCRIPTION
12 VDC RATED POWER SUPPLY
24 VDC RATED POWER SUPPLY
ENCLOSURE
DIMENSIONS
12” W x 14” L x 4”D
12” W x 14” L x 4”D
INPUT POWER
120 VAC
120 VAC
OUTPUT POWER
12 VDC
24 VDC
RATING
2 Amps
2 Amps
MAXIMUM # OF
MAGLOCKS
UP TO 3 MAGLOCKS
UP TO 6 MAGLOCKS
OUTPUTS
Fire alarm release
Auto/ Manual reset after fire alarm release
Auxiliary power for keypads/ external controls
Fire alarm release
Auto/ Manual reset after fire alarm release
Auxiliary power for keypads/ external controls
POWER SUPPLY BOARD DESCRIPTION:
TERMINAL
DESCRIPTION
1 N/C
2 N/O
3 COMMON
Auxiliary form ‘C’ dry contact. Fire alarm supervised.
4 & 5
Field selection for automatic or manual system reset. For system to automatically reset
when the fire alarm contact is reset, put jumper wire across these terminals. If manual
reset is required, a normally open (momentary switch) is used across these terminals.
Momentary activation of switch will reset the system.
6 & 7
To be tied to (normally closed) fire alarm contacts. The fire alarm contacts will open and
release all magnetic locks immediately. If fire alarm system supervision is not required,
a jumper across the terminals is required to derive 24 VDC from output terminals.
8 & 9
Auxiliary 12 VDC output (0.1 Amp max, not fused) for other system components,
requiring 12 VDC power.
TB1
10 & 11
(
For 10PS24/PB only
) Auxiliary 24 VDC output (0.25 Amp max, not fused) for other
system components, requiring 24 VDC power.
TB2
1 & 2
Optional battery backup unit terminals. Jump these two wires if battery backup is not
supplied.
If after troubleshooting a problem, a satisfactory solution cannot be achieved, please call B.E.A., Inc.
for further assistance during Eastern Standard Time at
1-800-523-2462 from 7am - 5pm or 1-800-407-4545 from 5pm - midnight & weekends.
DO NOT
leave any problem unresolved. If you must wait for the following workday to call B.E.A., leave the door inoperable until
satisfactory repairs can be made.
NEVER
sacrifice the safe operation of the automatic door or gate for an incomplete solution.
12 and 24VDC POWER SUPPLY
INSTRUCTION MANUAL