75.0148 V1 July 2000 

 

These power supplies are UL-Listed control units for use with electromagnetic locking devices and systems.  They may be 
ordered with optional battery backup systems to power devices in the case of power loss.

 

 
 

GENERAL DESCRIPTION:

 

 

12 VOLT 

24 VOLT 

POWER SUPPLY 

10PS12 10PS24 

POWER SUPPLY WITH 
BATTERY BACKUP 

10PS12PB 10PS24PB 

DESCRIPTION 

12 VDC RATED POWER SUPPLY 

24 VDC RATED POWER SUPPLY 

ENCLOSURE 
DIMENSIONS 

12” W x 14” L x 4”D 

12” W x 14” L x 4”D 

INPUT POWER 

120 VAC 

120 VAC 

OUTPUT POWER 

12 VDC 

24 VDC 

RATING 

2 Amps 

2 Amps 

MAXIMUM # OF 
MAGLOCKS 

UP TO 3 MAGLOCKS 

UP TO 6 MAGLOCKS 

OUTPUTS 

Fire alarm release 
Auto/ Manual reset after fire alarm release 
Auxiliary power for keypads/ external controls 

Fire alarm release 
Auto/ Manual reset after fire alarm release 
Auxiliary power for keypads/ external controls 

 

 

 

 

POWER SUPPLY BOARD DESCRIPTION: 

 

TERMINAL 

DESCRIPTION 

1 N/C 
2 N/O 
3 COMMON 

Auxiliary form ‘C’ dry contact.  Fire alarm supervised. 

4 & 5 

Field selection for automatic or manual system reset.  For system to automatically reset 
when the fire alarm contact is reset, put jumper wire across these terminals.  If manual 
reset is required, a normally open (momentary switch) is used across these terminals.  
Momentary activation of switch will reset the system. 

6 & 7 

To be tied to (normally closed) fire alarm contacts.  The fire alarm contacts will open and 
release all magnetic locks immediately.  If fire alarm system supervision is not required, 
a jumper across the terminals is required to derive 24 VDC from output terminals. 

8 & 9 

Auxiliary 12 VDC output (0.1 Amp max, not fused) for other system components, 
requiring 12 VDC power. 

 
TB1 

10 & 11 

(

For 10PS24/PB only

) Auxiliary 24 VDC output (0.25 Amp max, not fused) for other 

system components, requiring 24 VDC power. 

TB2 

1 & 2 

Optional battery backup unit terminals.  Jump these two wires if battery backup is not 
supplied. 

 

 

If after troubleshooting a problem, a satisfactory solution cannot be achieved, please call B.E.A., Inc. 

for further assistance during Eastern Standard Time at 

1-800-523-2462 from 7am - 5pm or 1-800-407-4545 from 5pm - midnight & weekends. 

 

DO NOT

 leave any problem unresolved. If you must wait for the following workday to call B.E.A., leave the door inoperable until 

satisfactory repairs can be made. 

NEVER

 sacrifice the safe operation of the automatic door or gate for an incomplete solution.

 

12 and 24VDC POWER SUPPLY 

INSTRUCTION MANUAL

 