The LO-21K (PN: 10LO21K) is a micro-processed lock out module designed to operate with the 

Keane Monroe 

3100 Swing Door System ONLY!

 The LO-21K is used with BEA’s Bodyguard or DK-12 overhead presence 

sensor.  The LO-21K interprets door open or door closed position based upon motor voltage input. The motor 
voltage information is sent from the LO-21K to the Bodyguard or DK-12 via data lines. The LO-21K provides 
optional safety beam input to override the inhibit signal during closing.  For example, when the safety beam path is 
blocked or interrupted during closing, the inhibit data will be cancelled, thus initiating a safety signal to the door 
control safety input. 
 

‰

 

ANSI / BHMA 156.10-2005 requires the use of a sensor or photobeam on the swing side of the door 
when using a header mounted safety sensor, such as the Bodyguard or DK12.  For more information 
reference the ANSI 156.10 standard. 

 
 
 
 

 

 

 
 

 

 

 

 

 
 
 
 
 
 
 
 

 

 
 

 

  

 
 

 

 
 

 
 
 

 

 

 

Shut off all power going to the header before attempting any wiring procedures. 

 

Maintain a clean & safe environment when working in public areas. 

 

Constantly be aware of pedestrian traffic around the door area. 

 

Always stop pedestrian traffic through the doorway when performing tests that may result in unexpected 
reactions by the door. 

 

Always check placement of all wiring before powering up to insure that moving door parts will not catch any 
wires and cause damage to equipment. 

 

Ensure compliance with all applicable safety standards (i.e. ANSI A156.10) upon completion of installation. 

 
 
 

DESCRIPTION 

SPECIFICATION 

Power Supply 

12-24 Volts AC / 15-24 Volts DC 

Operating Frequency 

4 MHz (Microprocessor) 

Power Consumption 

10 mA at rest, 50 mA Max. 

Output 

2 x SPST Relays 

Max. Voltage - Relay Contact 

60V DC, 120V AC 

Max. Current - Relay Contacts (both) 

2A DC, 0.5A AC 

USERS GUIDE

 

LO-21K

 

LOCKOUT RELAY 

Dipswitches

Green LED – Safety  

Red LED – Lock out time 

The LO-21K module is designed specifically for the KM3100 K-Control only, and must not 
be used on other brands/models of operators! Damage to module may result if this 
occurs. 

 

!

CAUTION

OBSOLETE

Summary of Contents for LO-21K

Page 1: ...reference the ANSI 156 10 standard Shut off all power going to the header before attempting any wiring procedures Maintain a clean safe environment when working in public areas Constantly be aware of pedestrian traffic around the door area Always stop pedestrian traffic through the doorway when performing tests that may result in unexpected reactions by the door Always check placement of all wirin...

Page 2: ...and the BODYGUARD DK 12 will switch to a door open pattern Once the door starts to close the LO 21K will sense the reversing change of polarity of the motor and will inhibit the BODYGUARD DK 12 for the preset lock out time delay During this time the red LED at the sensor will be off In addition to providing communication to the BODYGUARD DK 12 the LO 21K provides a safety connection between the sa...

Page 3: ...sing speed of the door is changed the time delay on the LO 21K must also be adjusted to accommodate the time difference for the duration of the closing cycle Time Delay sec dip 1 1 sec dip 2 2 sec dip 3 4 sec dip 4 8 sec dip 5 16 sec Time Delay sec dip 1 1 sec dip 2 2 sec dip 3 4 sec dip 4 8 sec dip 5 16 sec 1 ON OFF OFF OFF OFF 17 ON OFF OFF OFF ON 2 OFF ON OFF OFF OFF 18 OFF ON OFF OFF ON 3 ON O...

Page 4: ...res at the Bodyguard DK 12 3 Check continuity on the data wires red wire and red white striped wire Green LED does not come on when safety beams are blocked 1 Faulty safety beam receiver 2 Faulty connection on purple and gray wire from LO 21K 1 Test beams and LO 21K with multi meter 2 Perform continuity test on purple and gray wires Improper voltage reading on data lines at LO 21K 1 Incorrect wiri...