background image

Installation and Technical Information

BEGA

Due to the dynamic nature of lighting products and the associated technologies, luminaire data on this sheet is subject to change at the discretion of BEGA North America. For the most current technical data, please refer to bega-us.com

BEGA   

1000 Bega Way, Carpinteria, CA 93013

   

(805)684-0533

   

© copyright BEGA 2021

Figure 1:

Figure 2a:

Figure 3:

Overview:

LED Watts:

2.8W

System Watts: 5.0W
Controllability:

0-10V dimmable

Weight:

2.2 lbs.

Protection Class: IP65

Tools Required:

•  T10 torx head screwdriver

•  T20 torx head screwdriver

•  Flat head screwdriver

Figure 4:

Figure 2b:

Recessed wall luminaire - location

33 296

Dimensions
A:

5-7/8”

B:

5-7/8”

C:

5-1/4”

Maintenance:

Clean regularly with solvent-free cleaner 

removing dirt and debris. Do not use high 

pressure cleaners.

Replacement Parts

See label inside of fixture for LED replacement 

part number.
Consult factory for all other replacement 

components.

Accessories

Please refer to the appropriate accessory installation 

sheet for further instruction when applicable.

 Updated: 07/15/21

33 296

1 of 2

A

C

B

B

C

Notice to Installer:

1. 

See page 2 for specific product safety warnings.

2. BEGA luminaires may be damaged if connected to conduit systems containing water - Article 

300-5G of National Electric Code requires that “Conduits or raceways through which moisture 

may contact energized live parts shall be sealed or plugged at either or both ends”

3. Luminaire is Non-IC rated. Insulation must be at least 3” from luminaire.

4. Suitable for installation in hollow wall construction or poured concrete construction.

5. Installation housing provided with (6) 1/2” NPT threaded conduit holes.

6. 

Installation housing must be installed so that the front face is flush with the finished wall.

7. Suitable for wall applications only. (No ceiling or in-grade applications).

8.  

Warning: A silicone-based sealant MUST be used between the faceplate of the installed 

fixture and the exposed surface of the back box. Failure to do so could result in water 

entry into back box and fixture failure.

 

 

BB24215 installation in hollow (stud) wall or masonry construction:

1. Install (2) slotted mounting brackets provided as shown in Figure 1, using the (4) self-tapping 

T20 torx head screws provided with the included kit (Kit #93).

2. 

Adjust the brackets so that the front face of the installation housing will be flush with the finished 

wall surface after installation, Figures 2a / 2b.

3. Secure the mounting brackets to wood or metal horizontal blocking using hardware (by others) 

as shown in Figure 2a OR to masonry unit using hardware (by others) as shown in Figure 2b. 

4. Remove plastic insert. 

5. Connect conduit to installation housing and pull wires for electrical connections to be made later. 

6. 

Replace plastic insert and finish wall. 

 

BB24215 installation in poured concrete construction:

1. Remove plastic insert.

2. Install (4) threaded M4 rods into the installation housing and hand tighten until fully secure, 

Figure 3.

3. Connect conduit to installation housing and pull wires for electrical connections to be made later. 

4. 

Replace plastic insert, rods will fit through holes in plastic insert. 

5. Attach the installation housing to concrete forms by using (8) wing nuts provided. Ensure that 

the front face of the installation housing will be flush with the finished surface. 

6. Pour concrete. Do not pump or drop concrete directly on top of the installation housing. Doing 

so could deform or damage the installation housing. 

7. After concrete has cured, remove wing nuts from threaded rods before removing the forms.  

33296 luminaire installation:

1. Remove plastic insert and debris from installation housing

2. Make wiring connection: 

  

MAIN VOLTAGE SUPPLY WIRE TO BLACK DRIVER WIRE 

  

NEUTRAL (COMMON) SUPPLY WIRE TO WHITE DRIVER WIRE 

  

GREEN GROUND WIRE TO GREEN DRIVER WIRE 

 Dimming (if applicable): 

  

DIMMING CONTROL WIRE (+) TO POSITIVE DRIVER DIM CONTROL WIRE 

  

DIMMING CONTROL WIRE (-) TO NEGATIVE DRIVER DIM CONTROL WIRE

3.  Insert luminaire into installation housing and secure into place by evenly tightening the (2) T10 

torx head screws on the front of the luminaire to engage the clamping system. Before tightening 

completely, apply a silicone-based sealant as outlined below:  

Apply a silicone-based sealant between the faceplate of the installed fixture and the 

exposed surface of the back box to prevent water from entering the back box. At a 

minimum, use silicone on the top and side edges of the fixture.

Masonry bracket

Stud bracket

Reviews: