Installation and Technical Information
BEGA
Accessories
Please refer to the appropriate
accessory installation sheet for
further instruction when applicable.
In the interest of product improvement, BEGA reserves the right to make technical changes without notice.
Replacement Parts
BEGA
1000 Bega Way, Carpinteria, CA 93013 (805)684-0533 Fax (805)566-9474 www.bega-us.com © Copyright BEGA-US 2017
Bollards for indirect light directed downwards
77 589
Tools Required:
3mm hex key
4mm hex key
1/4” masonry/concrete drill bit
Drill
Protection Class:
IP65
Weight:
14.8 lbs.
Dimensions
A:
10-1/4 “
B:
31-1/4 “
C:
5-1/2 “
Relamping/Maintenance
Loosen (2) set screws and remove top casting with
lens. Clean luminaire and lens using only solvent-free
cleansers. Replace top casting and attached lens and
tighten (2) set screws evenly, making sure the gasket
is seated properly.
Lamp:
19.2W LED
77 589
8/21/2017
Page 1 of 2
Description
Lens
Lens gasket
LED Driver (120-277V)
LED Module (4000K)
LED Module (3000K)
Part No
112530.2
830814
76089
LED-0638/940
LED-0638/930
Anchorage
79 817
Notice to Installer for 77 589:
1. See page 2 for specific product safety warnings
2. Fixture may be damaged if connected to conduit systems that contain water - Article
300-5G of the National Electric Code requires that “Conduits or raceways through which
moisture may contact energized live parts shall be sealed or plugged at either or both
ends.”
3. It is recommended that when installing in planting areas the base of the bollard
be slightly elevated to avoid prolonged submerging during heavy rains.
4. Wet location listing does not imply suitability for exposure to standing water for
long periods of time.
5. 79 817 anchorage kit (included) must be installed in concrete pad/foundation.
6. LED and LED driver integral, provided inside luminaire housing.
79 817 anchorage installation:
1. Provide means to bring supply wiring to the bollard in accordance with local code. The
template has a 2-3/8” conduit hole for conduit entry.
2. Assemble anchorage kit. Unscrew the (3) hex bolts from the female couplers. Remove
each hex bolt and washer. Align each anchor bolt with the hole in the template. Attach
each anchor bolt to the template by replacing the washer and hex bolt and tightening.
3. Determine the fi nished grade for the application. Use leveling hardware to adjust
template to desired fi nished height after pouring.
4. Install anchorage kit using either method:
A. Attach template to forming or cross bracing using the (2) nail holes
provided in the template. Level template properly. Pour concrete.
B. Insert anchorage assembly into poured concrete. Concrete must be
vibrated to ensure proper anchorage setting. Level template properly.
77 589 - installation:
1. Make supply wiring and luminaire wiring connections in the luminaire base:
MAIN VOLTAGE SUPPLY WIRE TO BLACK LUMINAIRE WIRE
NEUTRAL (COMMON) SUPPLY WIRE TO WHITE LUMINAIRE WIRE
GREEN GROUND WIRE TO GREEN LUMINAIRE WIRE
Dimming (if applicable):
DIMMING CONTROL WIRE (+) TO POSITIVE DRIVER DIM CONTROL WIRE
DIMMING CONTROL WIRE (-) TO NEGATIVE DRIVER DIM CONTROL WIRE
2. Mount bollard over mounting plate and tighten 4mm set screw at base to secure.
(5/16" - 18 x 10")