INSTRUCTIONS
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed including the following:
1.
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
2. Disconnect power before performing work on electrical equipment.
3. Do not use outdoors.
4. Do not let power cords touch hot surfaces and do not mount near gas or electric heaters.
5. Use caution when servicing batteries. Battery acid can cause burns to skin and eyes. If acid is spilled on skin or
eyes, flush with fresh water and contact a physician immediately.
6. Equipment should be mounted in locations and at heights where unauthorized personnel will not readily
subject it to tampering.
7. The use of accessory equipment not recommended by Beluce Canada Inc., may cause an unsafe condition,
and will void the unit’s warranty.
8. Do not use this equipment for other than its intended purpose.
9. Servicing of this equipment should be performed by qualified service personnel.
10.
SAVE THESE INSTRUCTIONS!
INSTALLATION
WALL MOUNT - SINGLE FACE:
1. Extend unswitched 24 hour AC supply of rated voltage to junction box or appropriate wiring (supplied by others).
Leave at least eight (8) inches of slack wire. The circuit should not be energized at this time.
2. Remove both lenses by pulling the lenses away from the housing. Do not lift the unit by the lenses. (Figure 1)
3. Remove unit back plate by releasing two tabs at the bottom with a narrow screwdriver blade, and pull away. (Figure 2)
4. The Deco product mounts in any orientation on walls or ceilings.
For wall or ceiling mount, place screws through appropriate keyhole slots and tighten. Be sure to orient the back
plate, so the test switch faces the bottom, or desired direction, if ceiling mounted.
For mounting to a junction box, complete wiring connections as per step 5 and secure to box by removing
appropriate knockouts in back plate.
For conduit entry, secure back plate to wall or ceiling with suitable anchors. Knock out the conduit entry hole in the
top of the unit housing, and install conduit with bushing.
5. Attach unswitched AC circuit wires to unit AC input wire with wirenuts. INSULATE UNUSED LEAD. For 120VAC
input, follow diagram C. For 347VAC input, follow diagram D.
6. When ready to energize AC circuit, connect red battery lead to battery positive terminal. Verify battery negative
terminal is connected to battery blue wire.
7. AC must be off when mating unit housing to back plate. Align AC connector over circuit board and press onto back
plate until the retaining tabs snap through the housing. Reinstall both lenses by slight squeezing of the top and
bottom mounting tabs.
TESTING
To test, depress test switch. The emergency lamps will illuminate. When switch is released, lamps will go off. Allow unit to
charge for 48 hours before full load testing.
IMPORTANT NOTICE
This equipment is furnished with a low voltage disconnect circuit to prevent damage by over discharging the battery.
However, if the AC supply to the unit is to be disconnected for prolonged periods of time the battery MUST BE
DISCONNECTED. If unit fails to perform as described, disconnect AC and battery immediately, and contact either the
factory or trained service personnel for assistance.
MAINTENANCE
1. Relamping: To relamp, pull lenses from housing. Relamp only with type T5 6V, 5.4W, wedge-base lamp.
2. The lamps listed herein when used according to the instructions with this unit are in accordance with the requirements
of CSA Standard C22.2, No. 141 – Unit Equipment for Emergency Lighting.
DECO
926000101
Beluce Canada Inc., 3900 14th Avenue, Markham, ON L3R 4R3 Tel: (905) 948-9500 Fax: (905) 948-8673