Digital Pressure Switch 
User Guide

USER GUIDE 

Summary of Contents for MFD

Page 1: ...Digital Pressure Switch User Guide USER GUIDE ...

Page 2: ...des 6 Analog Output Characteristics 7 Initial Settings 8 Setting Digital Outputs 9 Setting the Zero Point 10 Setting Max and Min Display Values 11 Setting Up the Key Lock Function 11 Using the Copy Function 12 Advanced Settings 12 Calibration and Fine Adjustment Mode 14 FAQ 14 Support 15 ...

Page 3: ...le center back port available panel adapter or threaded mounting holes Significant Features and Benefits Easy to read digital display Programmable display units psi bar MPa and kg cm2 Dual digital output indicators Two programmable display colors Multiple output options Two individually programmed sinking NPN or sourcing PNP digital outputs standard One 1 5V or 4 20mA analog output optional Techni...

Page 4: ...4 Engineering Specifications Accessories Panel Adapter and Cover DPS PA 5m Data Cable DPS C5M ...

Page 5: ...e hex shaped boss near the pressure port Do not attempt to install the pressure switch by turning the switch body Serious damage to the switch may result Wiring Diagrams Output 1 Indicator Output 2 Indicator UP Button SET Button DOWN Button Pressure Display Pressure Unit Display OK NO ...

Page 6: ...osed In normally open mode the switch contact is made when the output is active In normally closed mode the switch contact is broken when the output is active For information on setting the output contact mode NC or NO see the Initial Settings section Point Set Mode Point set mode enables the digital output when pressure increases above the setpoint P1 or P2 and disables the output when pressure f...

Page 7: ... H2 plus system hysteresis As pressure decreases the output is enabled when pressure drops below H1 or H2 and disabled when pressure drops below L1 or L2 For information on setting H1 H2 L1 and L2 see Setting Digital Outputs To ensure proper function the difference between H1 and L1 or H2 and L2 must be greater than the system hysteresis H see Advanced Settings Normally Open Contact Mode Normally ...

Page 8: ...d DOWN buttons to change a value and press SET to save Basic Settings Setting ID Value Measurement Mode 3s Digital Output 1 Operating Mode oPS HYS Win Point Set Hysteresis Window Comparator See Digital Output Modes for more information Digital Output 1 Contact Type no nc Normally Open Normally Closed Digital Output 2 Operating Mode oFF oPS HYS Win Off Point Set Hysteresis Window See Digital Output...

Page 9: ... MPa kgf cm2 bar psi Measurement Mode Setting Digital Outputs Press the blue SET button momentarily to access the pressure setting menu Press the SET button repeatedly to step through the available pressure setting variables When a variable is selected the display will alternate between the variable ID and its value Use the UP and DOWN buttons to change a value and press SET to save Digital Output...

Page 10: ...settings will only show P1 and P2 variables Setting the Zero Point The zero point of DPS series switches can be reset to counteract effects of changing atmospheric pressure This feature is not intended as an offset and the zero point should only be reset when system pressure is relieved To reset the zero point press and hold the UP and DOWN arrow keys simultaneously until the display reads zero pr...

Page 11: ...Setting ID Value Measurement Mode or 3s PE 100 0 99 9 Measurement Mode PE Upper display limit bo Lower display limit Setting Up the Key Lock Function The key lock function prevents unauthorized users from making changes to the switch settings To enable the key lock press and hold the SET and UP buttons together for at least three seconds Use the arrow keys to select on Press SET to save and exit T...

Page 12: ...ly five seconds for data to be transferred to the slave The master and slave displays may flash during data transfer 3 When successful data transfer is complete the master DPS display will alternate between CPy and Good The slave DPS display will alternate between 5Lu and Good If data transfer was not successful the slave DPS will display Er8 Attempt the transfer again ensuring that power is switc...

Page 13: ...led See Basic Settings for color options Power Save Mode oFF on Off On In power save mode the DPS display will turn off after 30 seconds without a button input Press any button to momentarily turn the display on Copy Function oFF on onl Off On On Automatically enables key lock on slave when restarted Factory Reset oFF on Off On Resets DPS to original factory settings Fine Adjustment Mode oFF on Of...

Page 14: ...d System hysteresis is a stored value used to prevent output chattering The system hysteresis value controls how digital outputs behave when in point set mode or window comparator mode For more information on digital output modes see the Digital Output Modes section of this document System hysteresis can be set between 1 and 8 decimal places in the advanced settings menu see Advanced Settings For ...

Page 15: ...i 100 29psi 100 3psi 5 00bar 5 02bar 5 02bar Q Why is the voltage analog output range 1 5V Isn t 0 10V more common DPS series switches are designed to operate with an input voltage of 12 to 24VDC If powered by a 12VDC supply a 10V analog output signal could be affected by variations in the supply voltage As such the analog output is limited to 5V Support For application support or information on M...