DIP-34PA-03
Addressable Photoelectric Smoke Detector
INSTRUCTION MANUAL
GENERAL
DIP-34PA-03 Addressable Photoelectric Smoke Detector (hereinafter referred to as the DIP-34PA-03 or the detector) is
designed to be used in a fire alarm system in order to detect smoke inside enclosed premises by sensing light reflected
by smoke particles. The detector meets the requirements of Appendix “
Р
” of Russian Rules
СП
5.13130.2009.
The DIP-34PA-03 operates under control of a Signal-10 Intrusion and Fire Alarm Control Unit in an alarm loop of Type 14,
Fire Threshold Addressable. Up to ten detectors each having its own address from 1 to 10 can be brought into a single
Signal-10 alarm loop of Type 14. Each detector responds with its state to the Signal-10. These states can be Fire Alarm,
Trouble, Dusty, Norm, and Test. Electromagnetic compatibility of the detector meets the requirements for the third
resistance level.
The version of DIP-34PA-03 firmware is 1.00. Please read the Signal-10 User’s Manual to get more information about
DIP-34PA-03 operation.
The detector’s operability can be tested by means of a laser tester (such as the tester produced by System Sensor).
SPECIFICATIONS
Sensitivity
0.05 - 0.2 dB/m
Response Time
10 s max
Ingress Protection Rating
IP 41
Input Voltage (via a Signal-10 alarm loop in threshold mode)
9 ÷ 30 VDC
Current Consumption (via an alarm loop of a Signal-10)
0.4 mA max in quiescent mode
Pre-operation Time
60 s max
The number of detectors per alarm loop
Up to 10
Operating Temperatures
−
30 to +55°C
Storage Temperatures
−
50 to +50°C
Humidity
93% at 40°C, non-condensing
Overall Dimensions (diameter x height)
100 mm
×
47 mm max
Weight
0.2 kg max
The detector doesn’t contain precious metals (Clause 1.2 of
ГОСТ
2.608-78)
STANDARD DELIVERY
For single-piece delivery:
For group delivery:
DIP-34PA-03 Detector
- 1 pc.
DIP-34PA-03 Detector
- 10 pcs.
Instruction Manual
- 1 pc.
Instruction Manual
- 1 pc.
Address Sticker
- 1 pc.
Address Sticker
- 10 pcs.
Protective Cover
- 1 pc.
Protective Cover
- 10 pcs.
Unit Package
- 1 pc.
Group Package
- 1 pc.
WIRING
Figure 1 shows the standard wiring diagram to connect DIP-34PA-03
detectors into an alarm loop of the Type 14 of a Signal-10 control
unit. The first terminal of a detector base can be used to connect a
shield of the connecting wire.
Figure 1. Wiring Diagram