background image

DIP-34PA-03 

Addressable Photoelectric Smoke Detector 

 
 
 

INSTRUCTION MANUAL 

 

GENERAL 

DIP-34PA-03 Addressable  Photoelectric Smoke Detector (hereinafter referred to as the DIP-34PA-03  or the detector) is 

designed to be used in a fire alarm system in order to detect smoke inside enclosed premises by sensing light reflected 

by smoke particles. The detector meets the requirements of Appendix “

Р

” of Russian Rules 

СП

5.13130.2009. 

The DIP-34PA-03 operates under control of a Signal-10 Intrusion and Fire Alarm Control Unit in an alarm loop of Type 14, 

Fire Threshold Addressable. Up to ten detectors each having its own address from 1 to 10 can be brought into a single 

Signal-10 alarm loop of Type 14. Each detector responds with its state to the Signal-10. These states can be Fire Alarm, 

Trouble,  Dusty,  Norm,  and  Test.  Electromagnetic  compatibility  of  the  detector  meets  the  requirements  for  the  third 

resistance level. 

The  version  of  DIP-34PA-03  firmware  is  1.00.  Please  read  the  Signal-10  User’s  Manual  to  get  more  information  about 

DIP-34PA-03 operation. 

The detector’s operability can be tested by means of a laser tester (such as the tester produced by System Sensor). 

SPECIFICATIONS 

Sensitivity 

0.05 - 0.2 dB/m 

Response Time 

10 s max 

Ingress Protection Rating 

IP 41 

Input Voltage (via a Signal-10 alarm loop in threshold mode) 

9 ÷ 30 VDC 

Current Consumption (via an alarm loop of a Signal-10) 

0.4 mA max in quiescent mode 

Pre-operation Time 

60 s max 

The number of detectors per alarm loop 

Up to 10 

Operating Temperatures 

30 to +55°C 

Storage Temperatures 

50 to +50°C 

Humidity 

93% at 40°C, non-condensing 

Overall Dimensions (diameter x height) 

100 mm 

×

 47 mm max 

Weight 

0.2 kg max 

The detector doesn’t contain precious metals (Clause 1.2 of 

ГОСТ

 2.608-78) 

 

STANDARD DELIVERY 

For single-piece delivery: 

 

For group delivery: 

 

  DIP-34PA-03 Detector 

-  1 pc. 

  DIP-34PA-03 Detector 

-  10 pcs. 

  Instruction Manual 

-  1 pc. 

  Instruction Manual 

-  1 pc. 

  Address Sticker 

-  1 pc. 

  Address Sticker 

-  10 pcs. 

  Protective Cover 

-  1 pc. 

  Protective Cover 

-  10 pcs. 

  Unit Package 

-  1 pc. 

  Group Package 

-  1 pc. 

WIRING 

 

Figure 1 shows the standard wiring diagram to connect DIP-34PA-03 

detectors  into  an  alarm  loop  of  the  Type  14  of  a  Signal-10  control 

unit.  The  first  terminal  of  a  detector  base  can  be  used  to  connect  a 

shield of the connecting wire. 

 

 
 
 
 
 
 
 
 
 
 
 

Figure 1. Wiring Diagram

 

Summary of Contents for DIP-34PA-03

Page 1: ... The detector s operability can be tested by means of a laser tester such as the tester produced by System Sensor SPECIFICATIONS Sensitivity 0 05 0 2 dB m Response Time 10 s max Ingress Protection Rating IP 41 Input Voltage via a Signal 10 alarm loop in threshold mode 9 30 VDC Current Consumption via an alarm loop of a Signal 10 0 4 mA max in quiescent mode Pre operation Time 60 s max The number o...

Page 2: ...d the detector into a suspended ceiling variant B The size of the mounting hole is shown in Figure 3 at the right 1 DIP 34PA 03 Detector 2 Light Emitter 3 Alignment Guide 4 Mark and Bar OPEN HERE 5 Base Plate 6 MK 2 Suspended Ceiling Mounting Kit ordered separately Figure 3 Drilling Pattern Figure 3 shows the drilling pattern to install the detector for the variant A and the diameter of the mounti...

Page 3: ...d release when it lights up In 5 seconds the light emitter shall flash the number of times which is equal to the current address and then the detector lights up for a half of second DIP 34PA 03 ROUTINE TESTING Before testing DIP 34PA 03 please disconnect executive outputs of all system devices and modules that can release an extinguishing agent or activate light and sound alarms Notify the fire de...

Page 4: ...il info bolid ru Technical Support support bolid ru http bolid ru CONFORMITY CERTIFICATES The detector is approved by Conformity Certificate No C RU ЧС13 В 00149 Conformity Declaration ТС RU Д RU МЕ61 В 00312 certifies that the detector meets the requirements of Technical Regulations of Custom Union TR CU 020 2011 Production of the detector is certified in line with Russian Standard ГОСТ ISO 9001 ...

Reviews: