background image

Installation Instructions

ERVBBLHA

ENERGY RECOVERY VENTILATOR

SIZES 1150 AND 1200

TABLE OF CONTENTS

PAGE

SAFETY CONSIDERATIONS

1

. . . . . . . . . . . . . . . . . . . . . . . . .

INTRODUCTION

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

INSTALLATION CONSIDERATIONS

1

. . . . . . . . . . . . . . . . . . .

COMPONENT DESCRIPTIONS

2

. . . . . . . . . . . . . . . . . . . . . . .

UNIT INSTALLATION

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

WALL CONTROL

3

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

ELECTRICAL CONNECTIONS

5

. . . . . . . . . . . . . . . . . . . . . . . .

ACCESSORIES

5

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

BALANCING ERV

5

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

VENTILATION EVALUATION

6

. . . . . . . . . . . . . . . . . . . . . . . .

CONTROL BOARD OPERATION

6

. . . . . . . . . . . . . . . . . . . . . .

CARE AND MAINTENANCE

7

. . . . . . . . . . . . . . . . . . . . . . . . .

TROUBLESHOOTING

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

WIRING DIAGRAM

10

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A07619

Fig. 1 -- ERVBBHA Energy Recovery Ventilator

NOTE

: Read the entire instruction manual before starting the

installation.

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance,

or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury or property

damage. Consult a qualified installer, service agency or your

distributor or branch for information or assistance. The qualified
installer or agency must use factory--authorized kits or accessories

when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Have a fire extinguisher available. Read these

instructions thoroughly and follow all warnings and cautions

included in literature and attached to the unit. Consult local
building codes and the current edition of the National Electrical

Code (NEC) NFPA 70.
In Canada, refer to the current editions of the Canadian Electrical

Code CSA C22.1.

Recognize safety information. When you see this symbol

on

the unit and in instructions or manuals, be alert to the potential for

personal injury. Understand the signal words

DANGER

,

WARNING

, and

CAUTION

. These words are used with the

safety--alert symbol.

DANGER

identifies the most serious hazards,

which

will

result in severe personal injury or death.

WARNING

signifies hazards, which

could

result in personal injury or death.

CAUTION

is used to identify unsafe practices, which

may

result

in minor personal injury or product and property damage.

NOTE

is used to highlight suggestions which

will

result in enhanced

installation, reliability, or operation.

INTRODUCTION

The ERVBBHA Energy Recovery Ventilator is used to exchange

indoor stale air with outside fresh air. The unit is equipped with a
special energy recovery core which transfers both sensible and

latent heat between the fresh incoming air. The cross--flow design

core allows entering and leaving air streams to transfer heat energy
without mixing. (See Fig. 2.)
The ERVBBHA is available in 2 sizes with airflow ranges of
60--148 CFM (28 -- 71 L/s), and 60--183 CFM (28 -- 89 L/s). The

design of this unit is horizontal. Special attention should be given

to duct application, balancing the ERV, and locating unit for easy
access and routine maintenance.

INSTALLATION CONSIDERATIONS

Inspect Equipment

Move carton to final installation location. Remove ERVBBHA
from carton taking care not to damage unit. Remove all packaging

and inspect unit for damage. Remove parts bag from inside unit.

File claim with shipping company if shipment is damaged or
incomplete. Check to make sure ERV unit matches Fig.1.

Select Location

The ERV

should be located in a conditioned space

and in close

proximity to a fused power source. It should be easily accessible

for routine maintenance.
If ERV is installed independent of a forced--air system, unit should
be located near the center of the air distribution system. If ERV is

installed in conjunction with a forced--air system, unit should be
located next to (or close to) the indoor equipment.

Summary of Contents for ERVBBLHA Series

Page 1: ...CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which will result...

Page 2: ... air pickup registers throughout the home Fresh air registers are normally located in bedrooms dining rooms living rooms and basements It is recommended that registers be placed 6 to 12 152 to 305 mm from the ceiling on an interior wall and airflow directed toward the ceiling If registers are floor installed airflow should be directed toward the wall A92269 Fig 4 Chain Spring Installation CARBON M...

Page 3: ...g between ERV and exterior wall Fresh air intake and stale air exhaust must be separated by at least 6 ft 1 8 m Fresh air intake must be positioned at least 10 ft 3 m from nearest dryer vent furnace exhaust driveway gas meter or oil fill pipe Fresh air intake must be positioned as far as possible from garbage containers and potential chemical fumes When possible it is advised to locate the intake ...

Page 4: ...35 45 4 F 20 C 30 45 22 F 30 C 25 35 NOTE The ERV may be controlled using the Evolution system control The ERV may be connected using either a NIM or a 4 Zone Damper Module See the appropriate instructions if using the NIM of a 4 Zone Damper Module for connection instructions OneTouch Control The OneTouch control may be used as the primary wall control for the ERV This control will step through th...

Page 5: ...d optimum performance when applying an ERV Unit balancing prevents a positive and or negative pressure within the home Balancing the ERV is done by using balancing dampers in the fresh air intake and stale air exhaust ducts Airflow is determined by temporarily connecting a magnehelic gauge to the pressure taps on ERV See Fig 10 Balancing chart is located on unit door A98400 Fig 10 Magnehelic Gauge...

Page 6: ...h configuration setup shown in Fig 12 under Jumper Table Jumpers are factory set and do not require any changes unless control board is replaced If control board is replaced or unusual start up operation is encountered check jumpers to make sure they are located properly NOTE Power disconnect for 30 seconds is required to reset the CPU when changing jumpers Outdoor Ambient Below 23_ F 5_ C The ERV...

Page 7: ...n outdoor temperature is between 60 F and 75 F 16 C and 24 C and it is dry UNIT COMPONENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation DO NOT use water to clean core or damage will result In addition before servicing or removing the core inspect the edges to see if they appear soft or slightly expanded This can be normal and due to moisture in t...

Page 8: ...ory connected to electronic control board on HIGH and LOW speed taps of blowers Installer can easily change low speed tap to medium speed tap so electronic control will select between high and medium speed Connections can be changed at motor location see Table 9 and 10 To change low speed to medium speed proceed as follows 1 Unplug unit from 115 VAC 2 Remove filters and core from ERV 3 Slide blowe...

Page 9: ...l may be defective S Remove the wall control and test it right beside the unit using another shorter wire If the wall control works there change the wire If it does not change the wall control S The wires may be in reverse position S Ensure that the color coded wires have been connected to their appropriate places S The wires may be broken S Inspect every wire and replace any that are damaged S Th...

Page 10: ...er Le non respect de ces instructions peut causer un décès ou un choc électrique ADVERTENCIA PELIGRO DE CHOQUE ELÉCTRICO Desconecte el suministro de energía antes de reparar de mantener o de cablear in situ Vuelva a colocar todos los paneles antes de hacer lo funcionar No seguir estas instrucciones puede causar la muerte o choque eléctrico NOTES 1 CONTROLS AVAILABLE SEE THE INSTRUCTION MANUAL 2 IF...

Page 11: ... 11 860 72 22 11 270 74 23 10 750 76 24 10 250 78 26 9 750 80 27 9 300 82 28 8 840 84 29 8 432 86 30 8 042 88 31 7 668 90 32 7 310 92 33 6 993 94 34 6 661 96 36 6 368 98 37 6 085 100 38 5 811 102 39 5 571 104 40 5 313 106 41 5 088 108 42 4 869 110 43 4 660 112 44 4 450 114 46 4 268 116 47 4 019 118 48 3 918 120 49 3 750 Table 9 Factory Set Blower Connection HIGH or LOW Speed Control Module Main El...

Page 12: ... change at any time specifications or designs without notice and without incurring obligations E2009 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in U S A Edition Date 03 09 Replaces IIERVLHA 01 Catalog No IIERVLHA 02 ERV ...

Reviews: