Use a Spirit level to check
that the bracket is horizontal

Holes to secure bracket
to the wall

HEAT RECOVERED

WATER OUT

HEAT RECOVERED

WATER IN

 1. REMOVE FIXING SCREWS

2 HINGE COVER 
AND LIFT AWAY

FIG 1

DH33 DH55 

WATER FLOW
AS SHOWN
15mm STUBS

WATER FLOW
AS SHOWN
15mm STUBS

100M MAX

1mm SQ CABLE

Remote Air Stat

(Not supplied)

Remote  Humidistat

(Not supplied)

Remote On/Off
Switch 

(Not supplied)

REMOTE THERMOSTAT

REMOTE HUMIDISTAT

REMOTE ON/OFF

FIG 2 WIRING DIAGRAM

HEALTH & SAFETY WARNING

As th e Heat Pump contains electrical and rotational equipment, it is recommended th at ONLY competent persons carry out any work on th is type of machine 

(see guarantee). Isolate electrically before entering machine or removing panels.

This appliance is not intended for use by persons (including children) with  reduced physical,sensory or mental capabilities, or lack of experience and 

knowledge, unless th ey have been given supervision or instruction concerning use of th e appliance by a person responsible for th eir safety.

Children should be supervised to ensure th at th ey do not play with  th e appliance

INSTALLATION - WALL MOUNTING ALL MODELS

1. Remove machine from packaging and locate fi xing bracket.

2. Place bracket on wall in required position. Drill one hole in th e wall Ø 6.0mm 
(no. 10) by 60mm deep. Use th e wall plug provided to fi x th e bracket to th e 
wall. Using th e bracket as a template mark positions for oth er holes. Using 
a spirit level check th at th e bracket is level. Drill holes Ø 6.0mm (no. 10) by 
60mm deep. Insert wall plugs and screw bracket in place. Note. The wall plugs 
provided with  th e dehumidifi er are suitable for fi xing to a load bearing wall
3. Check all screws are tight.
4. The dehumidifi ers are heavy and may require two or th ree people to lift  th e 
dehumidifi er on to locating lugs on wall bracket.
5. Remove front cover as shown FIG 1.

6. Locate pipe from drip tray and run it away to waste. A short length  of 10mm 
pipe is provided which should be led into a fi xed waste pipe. Two pipe outlet 
holes are provided, one to rear of unit, one below th e unit.
7. Electrical supply to th e unit must be sized according to data on serial number 
label paying special attention to I.E.E. regulations latest edition regarding th e 
special conditions governing electrical supply to machines in potentially damp 
areas. The machine should be installed in accordance with  EMC2004/108/EC.
8. The electrical supply should be connected to th e terminal block mounted on 
th e side of th e bracket supporting th e compressor. Brown/red to 'live', blue/
black to neutral and earth  to th e stud provided.
9. Fan mode switch can be set to cycle fan when humidistat senses demand 
but should be set to continuous to promote good air circulation and reduce 
condensation. Note th at on models fi tted with  LPHW th e fan(s) will start 
automatically whenever th ere is an air heating demand. On 'X' models fan(s) 
will stop during defrost cycle.
10. The humidity of th e environment is controlled by a humidity sensor. The dial 
for th is is located on th e bottom of th e dehumidifi er, on th e left  hand side for a 
DH30/33 or th e right hand side for a DH50/55. Turning th e dial anti-clockwise 
gives maximum dehumidifi cation.

'RH' MODEL WITH HEAT RECLAIM TO WATER

11. Connect water circuit piping to 15mm stubs projecting from side of machine 
as per diagram below:
12. It is recommended th at isolating valves are fi tted to enable isolation of th e 
machine in th e event of service.
Complete water circuit as per diagrams overleaf.
(a) Circulating pump must be sized to take into account th e design fl ow
rate of th e machine plus th e water system resistance.
For Pressure drops see data section.

MODELS WITH LPHW FITTED

13. Connect water circuit piping to 15mm stubs projecting from side of 
machine as per diagram below:
14. It is recommended th at isolating valves are fi tted to enable isolation of 
th e machine in th e event of service.
Complete water circuit as per diagrams overleaf.
(a) Circulating pump must be sized to take into account th e design fl ow rate 
of th e machine plus th e water system resistance.
For Pressure drops see data section.

12V REMOTE HUMIDISTAT, THERMOSTAT, & 
REMOTE ON/OFF CONNECTIONS

(THESE OPTIONS NEEDS TO BE SPECIFIED WHEN 

ORDERING DEHUMIDIFIER)

15. Remove cover from dehumidifi er as shown in Fig 1.
REMOTE HUMIDISTAT
Remove link wire from mains in terminal block marked ‘Remote Humidistat 
and connect remote humidistat as shown below, ensure dial on internal 
humidistat is set fully anti-clockwise (ie maximum dehumidifcation).
REMOTE ON/OFF
When connecting th e Remote On/Off  Switch remove th e link from th e mains 
in terminal block marked Remote On/Off . Connect th e switch as shown 
below.

SD139450 ISSUE 17