background image

Mounting

Hang the device to the DIN-Rail being sure that 
the spring closes. Use a screwdriver to remove 
the product

Connections

DPB01

PPB01

Adjustment

Yellow

Relay output status

Red

Alarm status

Green

Device ON

Undervoltage

Overvoltage

Delay

Check if the input range is correct. Turn the power ON. The green LED is ON. Adjust the delay, upper ( ) and lower ( ) level knobs to the desired value. 
Provided that all the 3 phases are present in the proper sequence, as long as they are all within upper and lower set points, relay and yellow LED are 
ON. When one or more phase exceeds the upper level or drops below the lower level for more than the set delay time relay and yellow LED turn OFF, 
red LED (flashing 2 Hz during the delay time) turns ON. If the phase sequence is wrong or one phase is lost the output relay releases immediately (only 
200 ms delay occurs). This failure is indicated by the red LED which flashes 5 Hz as long as the alarm condition is occurring.

Installation instructions

TRMS 3-phase voltage monitoring relay
D/P PB01CM23/N

D/P PB01CM44

D/P PB01CM48/N

Code 8022250/071022 INSTRUCTION SHEET 
XPB01/XPB01N V8
www.gavazziautomation.com

Scan to read me in your language!

Scannen Sie, um mich in Ihrer Sprache zu 

lesen!

Scanne pour me lire dans ta langue !

¡Escanea para leerme en tu idioma!

Scansiona per leggermi nella tua lingua!

Scan for at læse mig på dit sprog!

扫码后选择相关语言进行阅读!

SW1 

ON:  6 s
OFF: 1 s

SW2

ON: 3P+N
OFF: 3P

CM23, CM48

CM44

Settings

SW1: 

Power ON delay

SW2: 

Mains type

SW3-SW4-SW5: 

Nominal voltage

SW6: 

Not used

(M23, M48)
SW3

ON

ON

OFF

OFF

SW4

ON

OFF

ON

OFF

M23 Ph-Ph 208 V 220 V 230 V 240 V
M23 Ph-N 120 V 127 V 133 V 140 V
M48 Ph-Ph 380 V 400 V 415 V 480 V
M48 Ph-N 220 V 230 V 240 V 277 V

(M44)
SW3

ON

ON

ON

ON

OFF

OFF

OFF

OFF

SW4

ON

ON

OFF

OFF

ON

ON

OFF

OFF

SW5

ON

OFF

ON

OFF

ON

OFF

ON

OFF

M44 Ph-Ph 208 V 220 V 230 V 240 V 380 V 400 V 415 V 480 V
M44 Ph-N 120 V 127 V 133 V 140 V 220 V 230 V 240 V 277 V

To access the DIP switches open the plastic cover using a screwdriver as shown on the left. 
Select the input voltage range by setting DIP switches 3 and 4 for M23 and M48 versions, DIP switches 3, 4 and 5 for M44 only. Select the desired 
function by setting DIP switches 1 and 2. Use DIP switch 1 to set a power ON delay. The actual mains reading will start after this set delay, thus alarms 
are inhibited during the delay. DIP Switch 2 sets the mains as either 3Ph (Delta) or 3Ph + N (Star). 

Do not open the DIP switches cover if the power supply is ON

DPB01

PPB01

Terminals

Tightening torque 

(DPB01)

L1, L2, L3, N 5, 6, 7, 11

Power supply

15, 16, 18

1, 3, 4

Relay output

DPB01

: each terminal can accept up to 2 x 2.5 mm

2

 wires

Connect the 3-phase power supply and the neutral (if present) taking care of the sequence (N ver-
sions don’t detect incorrect phase sequence). Connect the relay output according to the ratings.

Keep power OFF while connecting!

Packaging

The packing material should be kept for redeliv-
ery in case of replacement or repair.

CE-marking and approvals