background image

Specifications are subject to change without notice (16.10.08)

1

Monitoring Relays
3-Phase Active power
Types DWB02, PWB02

• TRMS active power relays for three phase 

balanced applications

• Measuring if active power is within set limits
• Measuring voltage on own power supply
• Measuring ranges:  5A, 10A, MI current transformers
• Power ON delay 1 to 30 s knob selectable
• Separately adjustable upper/lower level on relative

scale

• Programmable latching or inhibit at set level 
• Automatic and manual start and stop of the system
• Output: 8 A SPDT relay N.D. or N.E. selectable
• For mounting on DIN-rail in accordance with DIN/EN

50 022 (DWB02) or plug-in module (PWB02)

• 45 mm Euronorm housing (DWB02) or 36 mm plug-in

module (PWB02)

• LED indication for relay, alarm and power supply ON

Product Description

DWB02 and PWB02 are
precise TRMS active power
monitoring relays for 3-
phase balanced systems.
They can be used for moni-
toring the actual load of
asynchronous motors and
other symmetrical loads, as
well as the power consump-
tion by of system.
Start/stop input allows to
use a manual switch to start
and stop the system, with-
out the need of an auxiliary

device.
The advantage of using the
latch function is that the
alarm status can be kept
even after the end of the
alarm condition. Inhibit func-
tion can be used to avoid
relay operation when not
desired (maintenance, tran-
sitions).
The LED's indicate the state
of the alarm and the output
relay.

Input Specifications

Input

Voltage (Own power supply):
3 - phase 

DWB02:

L1, L2, L3

PWB02:

5, 6, 7

M23: 

208 to 240 VAC ± 15%

DWB02CM48: 

380 to 480 VAC ± 15%

PWB02CM48: 

380 to 415 VAC ± 15%

DWB02CM69:

600 to 690 VAC ± 15%

1- phase 

DWB02CM23:

L1, L2

PWB02CM23:

5, 6
208 to 240 VAC ± 15%

Current:

DWB02:

5A, 10A: I1, I2
MI...:U1, U2

PWB02:

5A, 10A: 11, 10
MI...: 9, 8

Measuring ranges

Upper level

Lower level

Active power

10 to 110 %

10 to 110 %

AACrms

Max. curr.
(30s)

Direct input:

0.5 to 5A

30A

1 to 10A

50A

Standard CT (examples)

TADK2 50 A/5 A

5 to 50 A

60 A

CTD1 150 A/5 A

15 to 150 A

180 A

CTD4 400 A/5 A

40 to 400 A

480 A

TAD12 1000 A/5 A

100 to 1000 A

1200 A

TACO200 6000 A/5 A

600 to 6000 A

7200 A

MI CT ranges

MI 100

10 to 100 A

250 AAC

MI 500

50 to 500 A

750 AAC

Note:

The input voltage cannot
raise over 300 VAC with
respect to ground (PWB02
only)

Contact input

DWB02

Terminals Z1, U2

PWB02

Terminals 2, 9

Disabled

> 10 k

Enabled

< 500 

Pulse width

> 500 ms

Hysteresis

~ 2% of set value - fixed

DWB02

PWB02

Ordering key

Housing
Function
Type
Item number
Output
Power Supply
Range

DWB 02 C M48 10A

Type Selection

Mounting

Output

Supply: Supply:

Supply: 

Supply: 

208 to 240 VAC

380 to 415 VAC

380 to 480 VAC

600 to 690 VAC

DIN-rail

SPDT

DWB 02 C M23 10A

DWB 02 C M48 10A

DWB02 C M69 10A

Plug-in

SPDT

PWB 02 C M23 10A

PWB 02 C M48 10A

Summary of Contents for DWB02

Page 1: ...e alarm condition Inhibit func tion can be used to avoid relay operation when not desired maintenance tran sitions The LED s indicate the state of the alarm and the output relay Input Specifications Input Voltage Own power supply 3 phase DWB02 L1 L2 L3 PWB02 5 6 7 M23 208 to 240 VAC 15 DWB02CM48 380 to 480 VAC 15 PWB02CM48 380 to 415 VAC 15 DWB02CM69 600 to 690 VAC 15 1 phase DWB02CM23 L1 L2 PWB02...

Page 2: ...arts to measure power If it is within the set points the relay is ener gized and the yellow LED is ON As soon as the power drops below the lower set point or raises above the upper setpoint the output relay releases after the set time has expired To restart the measurement connect Z1 and U1 2 and 9 or inter rupt the power supply for at least 1 s Example 2 Non latching mode relay NE DWB02 and PWB02...

Page 3: ...able Working mode ON Contact input for start stop functions OFF Contact input for latch inhibit functions Input current range terminals I1 I2 or 10 11 ON 10A OFF 5A MI Relay status ON Relay de energized in normal condition OFF Relay energized in normal condition Contact input working mode CLOSED OPEN LATCH NOT ACTIVE ACTIVE INHIBIT ACTIVE NOT ACTIVE START STOP START STOP Mode of Operation cont res...

Page 4: ...ower ON Power ON Power ON Lower level Relay ON Power supply Inhibit contact Closed inhibit active Upper level Hysteresis Hysteresis Active power Lower level Relay ON Wiring Diagrams DWB02 Direct connection PWB02 Direct connection Latch Inhibit Contact Latch Inhibit Contact T T Start and stop function NE relay Power ON Power supply Start Stop contact Closed Start Open Stop Upper level Hysteresis Hy...

Page 5: ...ibit Contact L2 L3 L1 m 15 16 18 L1 L2 L3 U1 U2 Z1 I2 I1 I1 N P P 6 7 5 m 1 4 3 L1 L2 L3 9 8 2 10 11 I1 N P P PWB02 Direct connection Manual start and stop NE relay DWB02 Direct connection Manual start and stop NE relay Start stop Contact Start stop Contact Wiring Diagrams cont With the start stop function enabled it s necessary to use the following wiring diagrams which are two examples among man...

Page 6: ...6 Specifications are subject to change without notice 16 10 08 DWB02 PWB02 45 80 83 5 99 5 63 28 5 36 80 94 28 5 63 90 Dimensions DIN rail Plug in ...

Reviews: