Solid State Relay

Number of poles

Switching Mode

Rated Operational Voltage

Control voltage

Rated Operational current

Connection type for control

Connection type for power

Connection configuration

Option

Specifications are subject to change without notice (14.04.2010)

1

Zero Crossing or Instant-On (Random) Switching

Product Width 17.5mm, 22.5mm

Rated Operational voltage: Up to 600Vrms

Rated Operational Current: Up to 30Arms

Up to 1800A²s for I²t and 1200Vp for blocking voltage

Control voltages: 3-32 VDC, 20-275 VAC (24-190 VDC)

IP20 protection

Design according to IEC60947-4-2, IEC60947-4-3,

IEC62314, UL508, CSA 22-2 No. 14-05

Integrated voltage transient protection with varistor

RoHS compliant

Product Description

Ordering Key

This new range of solid state

contactors presents a unique

opportunity to maximize effi-

ciency in panel space and is an

evolution of solid state switch-

es for which Carlo Gavazzi is

very well known.

The latest technologies in elec-

tronic and power semicondcu-

tor design allows a slim design

incorporating product ratings

at a surrounding temperature

of 40°C. The smallest width is

17.5mm and is rated at

20 AAC. Power and control

teminals allow for safe looping

of cables. Voltage transient

protection is standard across

the output with a varistor.

Specifications are stated at

25°C unless otherwise noted.

Solid State Relays

Zero Switching

Types RGC Solid State Contactor 'E' (Contactor) Connection

Rated Output

Blocking

Connection

Control Voltage

Rated Operational Current

Voltage

Voltage

Control/ Power

20 AAC

30 AAC

230 VAC, ZC

800Vp

Screw/Screw

3 - 32 VDC

RGC1A23D20KKE

RGC1A23D30KKE

20 - 275 VAC, 24-190 VDC

RGC1A23A20KKE

RGC1A23A30KKE

600 VAC, ZC

1200Vp

Screw/Screw

4 - 32 VDC

RGC1A60D20KKE

RGC1A60D30KKE

20 - 275VAC, 24-190 VDC

RGC1A60A20KKE

RGC1A60A30KKE

600 VAC, IO

1200Vp

Screw/Screw

4 - 32 VDC

RGC1B60D20KKE

RGC1B60D30KKE

Selection Guide

(ZC: Zero Cross Switching, IO = Instant-On Switching)

RGC 1 A 60 A 30 K K E _

Ordering Key

1Phase SSR

Rated Voltage

Control Voltage

Rated

Connection

Connection

Connection

with heatsink

Current

Control

Output

configuration

RGC1A: ZC

23: 230V +10% - 15%, 800Vp

D: 3 or 4-32VDC

20: 20AAC

K: Screw

K: Screw

E: Contactor

RGC1B: IO

60: 600V +10% -15%, 1200Vp

A: 20 - 275VAC, 24-190 VDC

30: 30AAC

Summary of Contents for RGC1A

Page 1: ...m design incorporating product ratings at a surrounding temperature of 40 C The smallest width is 17 5mm and is rated at 20 AAC Power and control teminals allow for safe looping of cables Voltage transient protection is standard across the output with a varistor Specifications are stated at 25 C unless otherwise noted Solid State Relays Zero Switching Types RGC Solid State Contactor E Contactor Co...

Page 2: ...e category III fixed installations General Specifications Isolation Input to Output 4000Vrms Input Output to Case 4000Vrms AC input current Vs Input Voltage DC input current Vs Input Voltage RGS D 1 RGS A Control voltage range RGC 23 3 32 VDC 20 275 VAC 24 10 190 VDC RGC 60 4 32 VDC 20 280 VAC 24 10 190 VDC Pick up voltage RGC 23 3 0 VDC 20 VAC DC RGC 60 3 8 VDC Drop out voltage RGC 23 1 2 VDC 5 V...

Page 3: ...C 30 Rated operational current AC 51 rating Ta 40 C 20 AAC 30 AAC AC 53a rating Ta 40 C 5 AAC 10 AAC Number of starts x 6 Tx 6s F 50 at 40 C 2 30 30 Min operational current 150 mAAC 250 mAAC Rep overload current UL508 TAMB 40 C tON 1s tOFF 9s 50cycles 60 AAC 84 AAC Maximum transient surge current ITSM 325 Ap 600 Ap Maximum off state leakage current 3 mA 3 mA I t 10ms Typical 525 A s 1800 A s Criti...

Page 4: ...t 4kV Performance Criteria 2 Electrical Fast Transient Burst Immunity IEC EN 61000 4 4 Output 2kV Performance Criteria 1 Input 1kV Performance Criteria 1 Electrical Surge Immunity IEC EN 61000 4 5 Output line to line 1kV Performance Criteria 1 Output line to earth 2kV Performance Criteria 1 Input line to line 1kV Performance Criteria 2 Input line to earth 2kV Performance Criteria 2 Radio Interfere...

Page 5: ...housing UL 94 V0 1 L1 Supply connection 2 T1 Load connection A1 positive control signal A2 control ground Environmental Specifications Dimensions Terminal Layout Housing width tolerance 0 5mm 0mm as per DIN43880 All dimensions in mm 5 3 2 17 8 19 5 106 98 90 135 6 35 4 50 6 Connection Diagram Filter Connection diagram In AC controlled types only RG A a varistor is placed across A1 A2 terminals In ...

Page 6: ...WG 1 x 14 12AWG Flexible without end sleeve 2 x 2 5 6 mm2 1 x 2 5 6 mm2 2 x 14 10 AWG 1 x 14 10 AWG Aperture for termination lug 12 3mm CONTROL CONNECTIONS A1 A2 Torque specifications 0 5 Nm 4 4 in lb M3 Pozidriv 1 Use 60 75 C copper Cu conductors Stripping Length X 6mm Rigid Solid Stranded 2 x 0 5 2 5mm2 1 x 0 5 2 5mm2 2 x 18 12 AWG 1 x 18 12 AWG Flexible with end sleeve 2 x 0 5 2 5mm2 1 x 0 5 2 ...

Page 7: ...between enclosure and supply shall not open The door or cover of the enclosure shall not be blown open There shall be no damage to conductors or terminals and the condcutors shall not sepa rate from terminals There shall be no breakage or cracking of insulating bases to the extent that the integrity of the mounting of live parts is impaired Discharge of parts or any risk of fire shall not occur Th...

Reviews: