Installation and Operating Instructions

Part Number 50QE900-220WS

CONTENTS

SAFETY CONSIDERATIONS

. . . . . . . . . . . . . . . . . . . . . . 1

GENERAL

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

INSTALLATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  1-6

Select Thermostat Location

. . . . . . . . . . . . . . . . . . . . . . 1

Install Thermostat

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Set Clock

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Heat Pump Configuration

 . . . . . . . . . . . . . . . . . . . . . . . . 3

Configure Advanced Setup

. . . . . . . . . . . . . . . . . . . . . . . 3

Program Thermostat Schedules

. . . . . . . . . . . . . . . . . . 4

Calibrate Sensor

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Check Thermostat Operation

. . . . . . . . . . . . . . . . . . . . . 6

Final Checklist

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

OPERATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Auto-Changeover

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Two-Stage Operation

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Clock Backup

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Fan Operation

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Emergency Heat

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Electric Heat

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Holiday Mode

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Keypad Lock

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

TROUBLESHOOTING

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

SAFETY CONSIDERATIONS

Read and follow manufacturer instructions carefully. Fol-

low all local electrical codes during installation. All wiring

must conform to local and national electrical codes. Improper

wiring or installation may damage thermostat.

Recognize safety information. This is the safety alert sym-

bol 

 . When the safety alert symbol is present on equipment

or in the instruction manual, be alert to the potential for person-

al injury.

Understand the signal words DANGER, WARNING, and

CAUTION. These words are used with the safety alert symbol.

DANGER identifies the most serious hazards which will result

in severe personal injury or death. WARNING signifies a haz-

ard which could result in personal injury or death. CAUTION

is used to identify unsafe practices which would result in minor

personal injury or property damage.

GENERAL

The 7-day, commercial, programmable thermostats is a

wall-mounted, low-voltage thermostat which maintains room

temperature by controlling the operation of an HVAC (heating,

cooling and ventilation) system. Separate heating and cooling

set points and auto-changeover capability allow occupied and

unoccupied programming for energy savings.

This thermostat allows up to 4 time/temperature settings to

be programmed per 24-hour period. Each thermostat stores

programs for 7 independent days. Batteries are not required.

During power interruption the internal NEVERLOST™ mem-

ory stores programmed schedules for an unlimited time while

the clock continues to run for at least 48 hours.

The thermostat can be configured to accept several different

equipment configurations, and is provided for heat pump

operation.

INSTALLATION

Select Thermostat Location — 

The thermostat should

be mounted:
• approximately 5 ft from the floor

• close to or in a frequently used room, preferably on an

inside partitioning wall

• on a section of wall without pipes or ductwork

• where temperature operating limits are within 41 to

104 F (5 to 40 C)

• where humidity operating range is within 0 to 95% rela-

tive humidity, non-condensing

The thermostat should 

NOT 

be mounted:

• close to a window, on an outside wall, or next to a door

leading to the outside

• where exposed to direct light and heat from a lamp, the

sun, a fireplace, or any other temperature-radiating

object which may cause a false reading

• close to or in direct airflow from supply registers or

return-air grilles

• in areas with poor air circulation (such as behind a door

or in an alcove)

IMPORTANT: Read entire instructions before starting

the installation.

AQUAZONE™

50QE900 Water Source Heat Pump

Commercial Programmable Thermostat

Summary of Contents for AQUAZONE 50QE900

Page 1: ...r property damage GENERAL The 7 day commercial programmable thermostats is a wall mounted low voltage thermostat which maintains room temperature by controlling the operation of an HVAC heating cooling and ventilation system Separate heating and cooling set points and auto changeover capability allow occupied and unoccupied programming for energy savings This thermostat allows up to 4 time tempera...

Page 2: ...re length and routing to allow proper closure of the thermostat Strip each wire at the end no more than 1 4 in to prevent adjacent wires from shorting together Match and connect wires to terminals on the thermostat See Fig 2 5 and Table 1 9 Push excess wiring into wall Seal hole in wall to prevent drafts 10 Re attach thermostat cover to back plate by aligning the top two prongs of the back plate i...

Page 3: ...ser to reset the Service Filter counter to zero and remove the SERVICE FILTER icon if displayed on the thermostat screen Press the OVERRIDE button while in Setup Step 3 and the counter is reset to zero Press the arrow buttons to ad just the number of hours the blower will run before the SER VICE FILTER icon is displayed The range is 0 to 1950 hours Set the variable to 0 to disable this function Th...

Page 4: ...arity for the heat pump The vari able can be set to either B or O Set the reversing valve polarity to the correct value depending on the application The default is O Program Thermostat Schedules Before pro gramming the thermostat plan the thermostat daily schedule The schedule is divided into 7 days Monday through Sunday Each day has from 2 to 4 time periods Occupied 1 Occupied 2 Occupied 3 Unoccu...

Page 5: ... been entered press the Program button to exit Programming mode NOTE The thermostat will continue to follow the schedule until a new one is entered If only one occupied schedule is selected the Occupied 2 and 3 schedules are skipped If the start time is set later in the day than the stop time the program will run from midnight of that day to the stop time and then from the start time to mid night ...

Page 6: ...the deadband plus 2 degrees Clock Backup In the event of a power loss the ther mostat will keep time for a minimum of 48 hours without external power or batteries Fan Operation If Fan On is selected the fan will run continuously during occupied schedule except when Mode is switched to OFF The fan will be off during unoccupied schedule except during heating or cooling operation If Fan On is not sel...

Page 7: ...ower operation timer to 0 hours Cooling Will Not Energize Select COOL mode Decrease cooling set point to 10 degrees below room temperature Check for 24 vac at Y1 terminal If present ther mostat is operating correctly and problem is with wiring or equipment If 24 vac is not present replace the thermostat Check for Compres sor Cycle per Hour Limit Cooling may be locked out Heating Will Not Energize ...

Page 8: ...ntinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53500037 01 Printed in U S A Form 50QE 7SI Pg 8 7 07 Replaces 50QE 2SI Book 1 4 Tab 5a 5a Copyright 2007 Carrier Corporation ...