background image

MANUAL

HUMIDISTAT

24 VAC
SOLENOID VALVE
LEADS

HUMIDIFIER

24 VAC TERMINALS

ON FURNACE

NOTE: 

CONNECT SOLENOID

VALVE TO HOT WATER IF 
HUMIDIFIER WILL BE 
OPERATED INDEPENDENT 
OF HEATING CALLS.

HUMIDIFIER

TRANSFORMER

(FIELD SUPPLIED)

120 VAC

24 VAC

24 VAC
SOLENOID VALVE
LEADS

MANUAL

HUMIDISTAT

120 VAC “EAC”

TERMINALS

ON FURNACE

(R) 24 VAC

HOT TERMINAL

NOTE:

FOR APPLICATIONS WITH 

THERMIDISTAT™ REFER TO
THERMIDISTAT™ INSTALLATION
INSTRUCTIONS.

WARNING: DO NOT CONNECT FURNACE HUM TERMINAL

DIRECTLY TO THERMIDISTAT™ HUM TERMINAL

INDOOR

EQUIPMENT

(HUM) TERMINAL

HUMIDIFIER

THERMIDISTAT™

CONTROL

24 VAC
SOLENOID VALVE
LEADS

EQUIPMENT

CONTROLLER

HUMIDIFIER

INDOOR

UNIT

24 VAC
SOLENOID
VALVE
LEADS

HUMIDIFIER

INDOOR

UNIT

24 VAC
SOLENOID
VALVE
LEADS

READ COMPLETE SAFETY INSTRUCTIONS AND INSTALLATION TEMPLATE BEFORE STARTING

This product must be installed by a qualified heating and air conditioning contractor. Failure to do so could result in serious injury from electrical shock.

This product must be installed in compliance with all local, state and federal codes.

ATTENTION INSTALLER:

SBP SMALL BYPASS HUMIDIFIER

The humidifier can be installed on

either the supply or return plenum of

a forced air handling system and is

easily reversible for installation with

right hand or left hand bypass duct

connections. The humidifier

dimensions and serviceability must be

considered when selecting the best

location for the humidifier.

RETURN

SUPPLY

S

RETURN

R

SUPPLY

S

Horizontal

Upflow

90-1115

90-1116

90-1117

90-1118

90-1119

90-1079

WARNING

1.

ELECTRICAL SHOCK HAZARD.

Disconnect electrical power to the
furnace and install lock-out tag
before starting installation. Failure to
do so could result in serious injury
from electrical shock.

2.

SHARP EDGES HAZARD.

Sharp

edges may cause serious injury from
cuts. Use care when making plenum
openings and handling ductwork.

3.

RISK OF SCALDING.

Water

temperature over 125°F can cause
severe burns and scald instantly.
Shut off the hot water supply before
disconnecting or tapping into any
hot water supply line.

SPECIFICATIONS

HUMIDIFIER DIMENSIONS

Width

(including solenoid valve):

15

5

8

Height

(including drain spud):

13”

Depth

:

10

1

4

BYPASS DUCT OPENING

6” diameter

PLENUM OPENING

9

1

2

”W x 9

1

2

”H

WATER FEED RATE

3 gph

ELECTRICAL DATA

24 VAC-60 Hz, 0.5 AMP

CAUTION

1. Do not install humidifier where freezing temperatures

could occur. The water line could freeze and crack
causing water damage to the home.

2. Do not install humidifier or bypass connection on the

furnace cabinet.

3. Do not install humidifier or bypass connection on a

plenum face where the blanked off ends of the cooling
coil will restrict air movement through the humidifier.

4. Do not set humidity level above recommended or to

recommended level if condensation exists on inside
windows of any unheated space, as condensation
damage may result. Excess humidity can cause
moisture accumulation which can allow the possibility
for mold growth in the home.

5. Do not connect humidifier transformer to

blower motor wiring. Premature component
failure may result.

6. When installing Humidifier Control on

downflow furnace, ensure blower continues to
run after a heat call is satisfied to eliminate
high temperatures from damaging the Control.

7. Do not install humidifier where water pressure

exceeds 125 psi, since damage to the
humidifier may result. Follow codes in effect
concerning pressure reduction.

8. Do not install humidifier on systems with

greater than 0.4 in. wg pressure differential
between supply and return plenums.

RISK OF PROPERTY AND EQUIPMENT DAMAGE.

INSTALLATION OPTIONS

WIRING DIAGRAMS

HumidiTrac

Automatic Humidifier Control

For detailed Automatic Humidifier Control

installation and wiring instructions,

see Form IM-AHC-02 included with Control.

DIAGRAM A

FOR OPERATION DURING “HEAT CALL” ONLY

DIAGRAM B

FOR OPERATION WHEN BLOWER IS ENERGIZED

DIAGRAM D

ZONING HOOK-UP

WITH EQUIPMENT CONTROLLER

DIAGRAM E

NEW COMMUNICATING CONTROL HOOK-UP

WITH ALL INDOOR EQUIPMENT

DIAGRAM C

FOR HUMIDIFIER OPERATION WITH THERMIDISTAT™ CONTROL

©2010 CAC/BDP