background image

 

-1- 

 

 

ES-10 

Field Installation Manual 

 

INDEX 

Important Instructions…………………………………………………………………………….  2 

Product Specifications…………………………………………………………….................. 3 

Unpacking & Mounting ………………………………………………………….……………. 

Connection Type 1 ………………………………………………………………….............. 

5  

Connection Diagram ………………………………………………..………………………… 

6                                

Connection Type 2 ……………………………... ……………………………………………. 

Connection Type 3 ……………………………………………………………………………… 

Electrical Data Sheet ………………………………………..…………………………………. 

Recommended Part List…………………………………………………..…………………….  10 

 

 

 
 

Summary of Contents for ES-10

Page 1: ...llation Manual INDEX Important Instructions 2 Product Specifications 3 Unpacking Mounting 4 Connection Type 1 5 Connection Diagram 6 Connection Type 2 7 Connection Type 3 8 Electrical Data Sheet 9 Recommended Part List 10 ...

Page 2: ...llation must be UL listed UL approved and as per NEC code WARNING Celec manufacture components parts that can be used in a wide variety of industrial commercial applications The selection and application of Celec products remains the responsibility of the equipment designer or end user Celec accepts no responsibility for how its products may be incorporated into final design Under no circumstances...

Page 3: ...urrent 21 6 Amp per phase Maximum kVar 7 8 Maximum Ambient Temperature 400 C Enclosure Type 1 Connection Terminal Connection Type Size Wire Type Temperature Torque N m Lb in T1 Power Circuit 10 AWG Str 1050 C 1 2 14 T2 T3 T4 CT Circuit 22 18 AWG Str Sol 1050 C 0 5 7 Earthing Terminals Bonding Circuit 10 AWG Str Sol 1050 C 8 5 75 ...

Page 4: ...Do not use ES 10 in case of any Breakage or loose connections or Oil Spill inside MOUNTING CAUTION Indoor Use Only Type 1 Enclosure 1 Choose the dry and Clean Wall to Install the ES 10 taking care conduit connections from Bottom side Enclosure Size is 400 x 300 x 120 mm and weight 10kg 22 Pounds 2 Premark the Mounting holes on wall or structure 3 Make a Drill for the wall plugs 4 Fix the Enclosure...

Page 5: ...cuit Breaker in the Main Breaker Panel a Connect the wire L1 to Phase 1 of 30 Amp circuit breaker b Connect the wire L2 to Phase 2 of 30 Amp circuit breaker C Connect the wire L1 to Phase 3 of 30 Amp circuit breaker d Connect the Neutral from Neutral Bar 1 14 Qualified Representative must inspect size of cable 10 AWG 1 15 Connect power cables to T1 Terminal Block of ES 10 1 2 Current Sensor Connec...

Page 6: ... 6 ...

Page 7: ...ain Breaker Panel Three Phase 120 208V AC WYE Connection up to 200 Ampere ES 10 units should be mounted with four appropriate sized fasteners before connect to Main Breaker Panel 1 Remove Main Panel covers exposing internal wiring and breakers 2 Remove existing 3 Pole breaker blanks and install new 3 Pole 20 Amp circuit Breakers 3 For rest of connection follow the Connection type 1 on page 5 ...

Page 8: ...ES 10 to Customer Main Breaker Panel 1 Install new 30 Amp Blade Fused disconnect or External Circuit Breaker switch to wall or existing backboard Qualified Representative should note if codes allow for direct connection to bus bars in main breaker panel or requires installation of an additional sub panel 2 Wire in rigid conduit between customer main breaker panel external disconnect switch Connect...

Page 9: ...it Breaker Fuse Equipment Protection Internal design has adequate clearance and creepage distance against line transients MOVs not required Circuit breaker Required 30 Amp 3 pole Low Losses 0 5 Watt each step Human Protection All High voltage shielded from contact Operating temperature range 40o C Ambient Dimensions L X H X D 16 X 12 X 5 400 x 300 x 120 mm Metal Enclosure Type 1 Operating Life Swi...

Page 10: ...Any 4 Screw 50 mm Size M8 Any 4 1 2 Conduit Connector Any 4 1 2 Tube Conduit Any As required 3 4 Conduit Connector Any 4 3 4 Tube Conduit Any As required All the Parts used in installation must be UL recognized or UL listed NOTE Installation of material and workmanship at the customer s Main Breaker Panel shall be the responsibility of the qualified Electrician in accordance with NEC Any and all c...