          USER’S MANUAL 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ENDURE 500VA 
ENDURE 750VA 

ENDURE 1000VA 
ENDURE 2000VA

 

Summary of Contents for ENDURE 1000VA

Page 1: ...USER S MANUAL ENDURE 500VA ENDURE 750VA ENDURE 1000VA ENDURE 2000VA ...

Page 2: ...o different models The inner diameter of the copper ring terminal which is used to connect battery cables to DC terminals should be no less than 6mm 3 For battery installation and maintenance read the battery manufacturer s installation and maintenance instructions prior to operating PERSONAL PRECAUTIONS 1 Have plenty of fresh water and soap nearby in case battery acid contacts skin clothing or ey...

Page 3: ...Modem Phone line surge protection optional and overload protection Optional RS 232 and USB Communication Port WinPower free software available online for real time status monitoring and controlling Auto restart when AC utility is recovered Support Generator Input High Frequency Design with high DC AC Efficiency for higher than 85 Operation Installation Front Panel Controls and LED Indicators Shown...

Page 4: ... again to turn off UPS unit Mains Mode LED The green LED will light steadily when power mains are normal Note The green LED blinks every 2 seconds to indicate that battery is not fully charged when the unit switch on Inverter Mode LED The Yellow LED will light when power mains are abnormal and unit will work in inverter mode Fault LED Red LED will blink or light steadily when fault occurs Back Pan...

Page 5: ...nal Place the battery cable ring terminal over Endure s battery terminal Tighten the M5 nut Do not place anything between the flat part of battery terminal and the battery cable ring terminal since overheating may occur Battery Cable Connection to UPS Endure 500VA 750VA 1000VA 2000VA Caution DO NOT place anything between battery cable ring terminals and battery terminals The terminal stud is not d...

Page 6: ... match the DC voltage requirements of the UPS unit or it may damage both the UPS unit and or the batteries Parallel Connection Wiring batteries in parallel increases the total run times the batteries can operate the AC loads The more batteries connected in parallel the longer the loads can be powered from the UPS unit Series Parallel Connection Series parallel configuration increases both the batt...

Page 7: ...ical 4 8 ms typical 14 ms max INDICATOR AC Mode Green lighting Battery Mode Yellow lighting Battery Charging Mode When battery is not full enough in line mode green flashing every 2 seconds When battery full green lighting Overload Red flashing every 0 5 second Fault Red lighting AUDIBLE ALARM Battery Mode Sounding every 10 seconds Low Battery Sounding every 2 seconds Overload Sounding every 0 5 s...

Page 8: ... Overload 1 Verify that the load matches the capability specified in the specs Back up time is shortened Overload 1 Remove some non critical load Battery voltage is too low 2 Charge battery for 8 hours or more If any abnormal situations occur that are not listed above please call service personnel immediately Appendix A Models Input output cables gauge copper wire Battery cables gauge copper wire ...