Important Safety Warnings 

 

 

This manual contains instructions and warnings that should be followed during the 

installation, operating and storage of the UPS system. Please keep this manual for 

further reference. 

 
CAUTION! 

To prevent the risk of fire or electric shock, install in a temperature and humidity 

controlled indoor area free of conductive contaminants. (See the specifications for the 
acceptable temperature and humidity range) 

CAUTION! 

To reduce the risk of overheating the UPS, do not cover the UPS' cooling vents and 

avoid exposing the unit to direct sunlight or installing the unit near heat emitting appliances 
such as radiators. 

CAUTION! 

Do not plug the UPS input into its own output. 

CAUTION!

 Do not allow liquids or any foreign object to enter the UPS. Do not place beverages 

or any other liquid-containing vessels on or near the unit.   

CAUTION!

 In the event of an emergency, press the OFF button and disconnect the power 

cord from the AC power supply to completely disable the UPS. 

CAUTION! 

The UPS installation must be correctly grounded in order to reduce leakage current 

below 3.5mA. 

Attention

 The UPS output is supplied by two sources. When the UPS is disconnected from 

mains power, hazardous voltages may still be present from the internal battery. The battery 
should be disconnected when maintenance or service work inside the UPS is necessary. 

CAUTION! 

Servicing of batteries should be undertaken or supervised by qualified personnel 

only. 

CAUTION! 

When replacing the batteries, use the same number and type of batteries. 

CAUTION! 

Dispose of batteries in the correct manner and in line with local laws and 

regulations. Never dispose of batteries in a fire. Do not attempt to open the battery. Released 
electrolyte is harmful to the skin and eyes. 

CAUTION!

 Unplug the UPS prior to cleaning and do not use liquid or spray detergent. 

CAUTION! 

A battery can present a risk of electric shock and short circuit.   

CAUTION! 

This is a category C2 UPS product. In a residential environment, this product may 

cause radio interference, in which case the user many be required to take additional measures. 
 
 

Designed and Engineered by: 

 

CertaUPS 

www.certaups.com

   

 

 

 

 

Specifications 

MODEL 

C200-1000 

C200-1500 

C200-2000 

CAPACITY 

1000VA/700W 

1500VA/1050W 

2000VA/1400W 

INPUT

 

Input Voltage 

110/120VAC or 220/230/240VAC 

Voltage Range 

81-145VAC / 162-290VAC 

OUTPUT

 

Voltage Regulation 

+/-10% 

Transfer Time 

Typical 2-6ms, 10ms max. 

Waveform 

Pure Sinewave 

BATTERY

 

Type & Number 

12V/7Ah x 2 

12V/9Ah x 2 

12V/10Ah x 2 

Charging Time 

4-6 hours recover to 90% capacity 

PHYSICAL

 

Dimension (DxWxH) mm 

350 x 146 x 160 

397 x 146 x 205 

Net Weight (kgs) 

8.96 

12.18 

13.7 

 
 

 

 

C200 Uninterruptible Power Supply 