CSW / SL Surge Protection Module

 for Non-OmniControl Commercial Gate Operators

This Surge Protection Module will provide protection for the following input commands.

Please read this entire manual before installation

Chamberlain Professional Products 

strongly

 recommends the installation 

of this Surge Protection Module to protect the gate operator from harmful 
surges caused by lightning strike phenomenon.

It is important to recognize that the surge protection module may not 
prevent damage to the gate operator in the event of a direct lightning 
strike.

The success of the surge protection will be based in the proper installation 
of the Surge Protection Module and the proper grounding of both the 
surge protector module and the gate operator itself.

Name of Lines Protected

External Safety Loop “Command” input
External Exit Loop “Command” input
Fire Department or Key switch “Open” command
Strike Open or Push Button to open command
Radio receiver “Command” input
Ground reference and +24 VDC supply

1
1
1
1
1
2

Number of Lines Protected

Earth Ground Rod Installation

The earth ground rod must be located within 3 feet from the gate 
operator. Use the proper type earth ground rod for your area.

The ground wire 

must

 be a single, whole piece of wire. 

Never

 

splice two wires for the ground wire. If you should cut the 
ground wire too short, break it, or destroy its integrity, replace it 
with a single wire length. 

12 gauge wire

Proper grounding gives an electrical charge, such as from an 
electrical static discharge or a near lightning strike, a path from 
which to dissipate its energy safely into the earth.

Without this path, the intense energy generated by lightning could be 
directed towards the gate operator. Although nothing can absorb the 
tremendous power of a direct lightning strike, proper grounding can 
protect the gate operator in most cases.

8 ft

Chamberlain Professional Products, Inc. is not responsible 
for improper installation or failure to comply with all 
necessary local building codes.

Part # Q411

Before digging more than 18" deep, contact local underground utility locating companies.

Avoid damaging gas, power, or other underground utility lines.

P/N Q411  –  PATENT PENDING

P/N Q411  –  PATENT PENDING

®

STRIKE OPEN

PUSH BUTTON

STRIKE OPEN

PUSH BUTTON

FIRE DEPT

KEY SWITCH

FIRE DEPT

KEY SWITCH

CLASS 2

SUPPLY

CLASS 2

SUPPLY

SAFTEY

LOOP

SAFTEY

LOOP

RADIO

RECEIVER

RADIO

RECEIVER

EXIT

LOOP

EXIT

LOOP

+

+

CSW / SL 
SURGE 
SUPPRESSOR

®

CSW / SL Surge Protection Module

 Step-by-Step instructions (con't)

STEP 13

Test all the accessories in combination with the gate operator to corroborate proper installation and functionality.

For additional protection against surges, ensure that the cables or wires going to your accessories comply 
with the following rules:

All wires going the accessories 

must

 be shielded wires.

 The 

shield 

must

 be connected as follows:

 

 

A) At the gate operator: To the chassis of the gate operator

 

 

B) At the accessories: To their chassis (Earth grounding at the accessories will be even more beneficial)

Ensure that the connections to the chassis are made secure to create good contact.

For Technical Support:

 1-800-528-2806

845 Larch Avenue  Elmhurst, Illinois 60126

www.chamberlain.com

© 2005 The Chamberlain Group, Inc.

All Rights Reserved

01-50739

®

Summary of Contents for Elite CSW/SL

Page 1: ...s from an electrical static discharge or a near lightning strike a path from which to dissipate its energy safely into the earth Without this path the intense energy generated by lightning could be directed towards the gate operator Although nothing can absorb the tremendous power of a direct lightning strike proper grounding can protect the gate operator in most cases 8 ft Chamberlain Professiona...

Page 2: ...1 Rm Main Dept Manu 2 Rm Air 1 Conditioner Air 2 Conditioner Conference Room 1 Conference Rm 2 3 Refer Bus 1 2 3 Conference Room 2 Comp Serve 2 Comp Serve 1 Turn the gate operator off by turning off the building facility breaker for the 120 Vac supply to the gate operator P N Q411 PATENT PENDING P N Q411 PATENT PENDING STRIKE OPEN PUSH BUTTON STRIKE OPEN PUSH BUTTON FIRE DEPT KEY SWITCH FIRE DEPT ...

Page 3: ...1 Rm Main Dept Manu 2 Rm Air 1 Conditioner Air 2 Conditioner Conference Room 1 Conference Rm 2 3 Refer Bus 1 2 3 Conference Room 2 Comp Serve 2 Comp Serve 1 Turn the gate operator off by turning off the building facility breaker for the 120 Vac supply to the gate operator P N Q411 PATENT PENDING P N Q411 PATENT PENDING STRIKE OPEN PUSH BUTTON STRIKE OPEN PUSH BUTTON FIRE DEPT KEY SWITCH FIRE DEPT ...

Page 4: ...s from an electrical static discharge or a near lightning strike a path from which to dissipate its energy safely into the earth Without this path the intense energy generated by lightning could be directed towards the gate operator Although nothing can absorb the tremendous power of a direct lightning strike proper grounding can protect the gate operator in most cases 8 ft Chamberlain Professiona...

Reviews: