background image

 Safety

-  

Installation should be performed only by a qualified electrician.

- 

Disconnect power at the source before installation, inspection or removal.

-  

Do not use the mini BLC 4DI if it is damaged.

-  

The electrical installation must be in conformance with the national legislation and relevant

 

standards.

-  

The mains connection of the mini BLC 4DI must be provided with a fuse or circuit breaker.

-   

The mini BLC 4DI has protection class IP20 and is suitable for use at indoor locations. 

Mount the mini BLC 4DI in an IP66 housing for use at outdoor locations.

Mini BLC-4DI

Mymesh Building Light Control

The Mymesh mini BLC 4DI is a product in the Mymesh Building Light Control product suite 
for wireless lighting control. The mini BLC 4DI is a wireless sensor for monitoring of up to four 
voltage free contacts.

 Application

-  

Refer to the mini BLC 4DI product sheet (see chess-wise.eu/downloads) for the product

 

specifications and the environmental conditions.

 Installation

Mount the mini BLC 4DI with 2x M3 screw/bolt (76 mm distance).

- 

Use maximal 1.5 mm2 wiring for all connections. Push the wires completely into the terminal

 

block. Use wire end sleeves when using flexible wires.

Solely use a plastic, polycarbonate or fiberglass housing without carbon additives should be  

 

used for installation of a mini BLC-DALI, or bring the white end part of the antenna outside the

 

housing.

- 

Install the antenna to the antenna connector. Do not mount the white end part of the antenna

 

close to metal surfaces to obtain optimal radio performance.

- 

Connect up to four of the contact inputs and the common GND to voltage free external  

 

contacts. (See wiring diagram on the next page)

Use shielded cables with AWG24 (or better), e.g. a CAT6 FTP cable.

- 

Do not use cables longer than 1000m.

- 

Connect the shield at one side only. 

by Chess

Installation instruction

Reviews: