Code

Type

Sensivity (A)

Tripping delay (s)

Communications

P24652

RGU - 10C MT

0,03-0,1-0,3-0,5-1-3
by direct adjustment

5-10-30 by

SETUP

INS-SEL-0,02-0,1-0,2-0,3-0,4-0,5-0,75-1

by direct adjustment

3-5-10 by

SETUP

Available

RS-485

P 2 X X X X 0 0 X

Código

Code

Código interno

Internal code

Tensión de
alimentación

Power supply

230 V a.c.

110 V a.c.

0

1

RGU-10C MT Electronic earth leakage protection relay with self-reclosing system

For instance, RGU-10C MT supplied by 110 V a.c.

GENERAL DESCRIPTION

DESCRIPTION LED AND BUTTONS.

- Device with programmable differential relay with self-reclosing system. Symbol

in LCD.

- It has 2 independents outputs by relays. Trip and locked by reclosing.
- It has 1 input for external Trip/Reclose. This input is not opto - coupled.
- Mounting in Rail DIN 46277 (EN 50022) or panel 72x72 by mean accessory (M5ZZF1)
- Associated to a

/

Series external , toroidal current transformer.

- It must be asociated to a MCB motorized with or without a trip coil.
- It verifies connection with differential transformer

by means inductive test.

- Leakage detection and measurement is via calculating its true efective value (TRMS).
- Display settings values and instant residual current to its accociated units.

- Shows equipment status via a display and 2 LED.
- 5 button equipment setup and setting.
- 2 button equipment TEST and RESET.

WG WGS

WG/WGS

-

INDICATION BY LED AND DISPLAY.

RECLOSING THE EQUIPMENT.

RELAY PARAMETERS SETTING

-

-

LED and display signals a change

of status by changing from green to red.l
Display event type messages or values.

The yellow LED is blinking. Red Display shows the
tripp cause fluctuating with partial reclosures No

.

The yellow LED is fixed. The equipment arrives al
maximun number of reclosures established by the
self-reclosing sequence. Red display shows the cause.

-

By short press on

the display shows the number of reclosures by

earth leakage, short ciruit-overload faults and total number. The partial number are floating pages
In these pages it can configure the self-reclosing sequence by press

button.

- BY

/

1. Automathic (earth leakage, short ciruit-overload faults or manual).

Enabled.

2. Manual reclose by pushing button
3. External reclose sytem by remote or communications signal. When it forces a trip by remote
signal, only it can reclose by another remote signal.
4. Manual reclose circuit breaker associated.

In the case 2 and 3 the all partial counters of reclosures returns to a zero.

, .

t

.

SAVE.

.

. .

. Select the default position of the relay contacts

7-8-9 that indicates the situation of locked by reclosures of the device . In (Std) 8-7 NA / 8-9 NC
and (+) 8-7 NC / 8-9 NA and appears the

symbol in display.

. In reclosure partial numbers by press

button we

configure the self-reclosing sequence referred at the page which it’s showing us. By default is
configured nº10 by earth leakage protection and nº5 by short-circuit/overload protection.

TRIP RELAY.

BETWEN RECLOSURES.

LOCKED BY RECLOSURES

No OF RECLOSURES.

PROG

REC

TRIP LOCKED BY RECLOSURES

RESET

-

-

,

- SIGNALLING CONTACTS RELAY STATE, std/+

- SELF-RECLOSING SYSTEM, REC

REC

( ,

y std/+ )

t I

d

d

t

I

I

d

d

d

d

SETTING TRIP DELAY

SENSITIVITY SETTING

The

message and two values appear on the screen after

pressing the

button. The lowest value indicates the current set value and the highest is the

values to be configured which are displayed by pressing

The selected value to be saved is

displayed by showing the message

The same operation as above setting is carried out by pressing

Tripping cause

Message display

Test
Remote signal trip/reclose
Earth leakage fault
Short circuit / Overload fault
Communications

TESt
EXT
DIF / valor
MAG
REM

PROG

+

Others MESSAGES by display

SAVE
EXIT
OVR
ERRt

Enter setting values
Exits setting mode
Value reading off scale
Poor toroidal conection

M98205901-03-09B

P24652001

PARAMETERS BY

DIRECT ADJUSTMENT

-DELAY SETTING
-

ROTATION

SETUP

-SENSIVITY SETTING

-CONTACTS SETTING NO/NC

-ENABLE/DISABLE

SELF-RECLOSING SYSTEM

REC

SREC

No RECLOSURES

TIME SEQUENCES

RESET TIME

RECLOSE SEQUENCES BY EARTH LEAKAGE CURRENT FAULT

SREC No RECLOSURES

TIME SEQUENCE

RESET TIME

RECLOSE SEQUENCE BY SHORTCIRCUIT/OVERLOAD FAULT

TECHNICAL FEATURES

Relay type: Electronic class A. High frequency current filtering.

- Reclosing type: Authomatic, RESET button or by cutting power supply.
- Rated power supply voltage

Operating temperature
Connections

Permissible cable section:
Recommended tightening torque: 0.5-0.6 Nm
Length of cable to strip:

7 mm

Switch Output contact features

Rated current/Maximum instant current
Rated voltage/Maximum switching voltage
Rated load in

- Tipo

: 230 o 110 Va.c. (+/- 20%) 50/60 Hz, 6 VA

-

: -10ºC / 50ºC

-

:

0,127 - 2,082 mm

-

13-14-15, 7-8-9 and 5-6

: 6/10 A a.c.

: 250/230 V a.c.

AC: 2,500 V·A

Contacts protected by varistor

- Varistor Features

Maximun Voltage: 275 Va.c.

-Characteristics input remote Trip/Reclose 1-2

Input not using optocoupler

2

REC

REC

MT

REC

MT

REC

WARNING: The reclosing sequences marked by

is recommended for motorized circuit breakers with or

without trip coil. I >63 A.

N

Maximun DC Load Breaking
Capacity:
Maximun opening current

Electrical useful life for AC
loads: No of cycles

MAG

¡ IMPORTANT

!

The relay only self-recloses before a trip by earth leakage, short-circuit/overload current fault. The Test (red button) only

verifies the relay trips the protection. It recloses only by manual pressing RESET button.

0

DISABLED

1

2

1 minute

30 minutes

2

2

1 minute

60 minutes

3

2

90 s

30 minutes

4

2

90 s

60 minutes

2

3 minutes

30 minutes

6

...

...

...

7

...

...

...

8

...

...

...

5

0

DISABLED

1

6

8, 16, 30, 59, 115 and 224 s

15 minutes

2

30

20, 40 s and 5 min. to the end

15 minutes

3

8

30 s, 1, 2, 3, 4, 5, 6 and 7 min

15 minutes

4

6

10, 20, 30, 60, 130 and 600 s

15 minutes

5

6

2, 4 and 8 min. to the end

15 minutes

6

7

30 s, 1, 2, 3, 4, 8 and 16 min.

30 minutes

7

10

1 min.

30 minutes

8

10

90 s

30 minutes

9

8

2, 4 and 6 minutes to the rest

15 minutes

10

3 minutes

30 minutes

11

7

2, 4, 8, 16, 32, 32 and 32 minutes

15 minutes

10

12

31

2, 4 and 6

15 minutes

13

6

8 s

15 minutes

14

...

...

...

minutes to the rest

MAG

MAG

MAG

MAG

MAG

MAG

MAG

REC

REC

GREEN LED: ON
RED LED: TRIPPED BY FAULT

SCREENS /

SETUP

R

RESET button: It reinitiates the operation of the equipment by any event

that tripps it.evento. It indicates the equipment version.

YELLOW LED: Locked by reclosures (fix)

Betwen reclosures (blinking)

Button

FREQ

LIM

SEC.T

TRIP

Button

60 Hz

10 s, 30 A

RST.C

Mb

Pulsador

PROG

PERIPHERICS

BAUDS

PARITY

COM

PsI

1 ..

.. 99

2.4
4.8
9.6

19.2
38.4
57.6

115.0
0
EN
OD

50 Hz

1 s, 3 A

St

MA

-

, PER( ) / BD(

) / PAR( ), communications.

-

, (

) frecuency (Hz)

-

,(

), range of values (Id / td)

-

, (

),contacts 5-6 [

-

, (

), initiates the partials counters.

COM
FREQ
LIM
SEC. T

RST.C

NA/NC]

-

(without trip coil)

TRIP, (

), breaking element

1

9.6

0

50

1s, 3A

NO

NO

MA

Default values in

SETUP

TEST button: It makes a forced firing to verify the protection.

YES

NO

SETUP

SETTINGS

A long press in

activates the

settings. In this operating

mode by pressing buttons

and

it shows the submenus and the

setting values to modify . With

these

SETUP

PROG

PROG

PROG

new setting values are

validated, the message

is shown by display and exits setting

mode. In case of keypad inactive, it exits setting mode and the message

is shown by display wihtout changes.

In

(Circuit Breaker), The value

is used when the CB don

t need a

trip coil. The value

is used when CB needs one.

In

it defines the working mode of outputs contacts relay 5-6. By

default 5-6 is normally open (St )

SAVE

EXIT

TRIP

SEC.T

(LOCKED SIGNAL)

(See graph)

(See graph)