16X8A Relay Module
(CL-DR-RL16X8A)
Rail Mounting
16X8A Relay Module is designed to be installed on a standard
35 mm wide DIN rail (EN 50022, BS 5584).
Hook the module from the top, pull down the rail moun ng
clips, push the module to the rail and release the rail
moun ng clips.
Screw Mounting
Screw the module to any surface through 4 corner screw
holes.
3
4
1
2
INSTALLATION GUIDE
version 1.0.1
Input Voltage
18V-24V DC (24V DC is recommended)
Input Current
320mA (for 24V DC)
I/O Connec ons
C-Bus
2 X RJ45
Output
16 X relay channel -8A per Channel
(rising-cage 5mm screw terminals)
Pr
oduct Specific
aon
1. Screw holes
2. Output connectors
3.Rail moun ng clips
4. Channel LEDs
5. Status LEDs
6. Control bu ons (1-16)
7. RS-485 jack
1
2
3
1
1
4
1
5
7
6
3
7
16x8A Relay Module
CL-DR-RL16X8A
Ch9
Ch10
Ch11
Ch12
Ch13
Ch14
Ch15
Ch16
1
2
C-Bus
C-Bus
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Com
1-4
Com
5-8
Com
9-12
Com
13-16
Power In: 24V DC, 320mA max, from data bus
4
Compatible with Control4
16x8A Relay Module
CL-DR-RL16X8A
Ch9
Ch10
Ch11
Ch12
Ch13
Ch14
Ch15
Ch16
1
2
C-Bus
C-Bus
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Com
1-4
Com
5-8
Com
9-12
Com
13-16
Power In: 24V DC, 320mA max, from data bus
#2
#3
#4
#5
#8
#1
#6
#7
C-Bus
C-Bus
#2
#3
#4
#5
#8
#1
#6
#7
1
2
3
Change Module Address
In order to change the module address follow steps below consecu vely and uninterruptedly:
1. Disconnect the main power. Hold bu on #1 & #2 simultaneously (bu on’s and LED’s number
sequence is considered from right to le as shown in following picture)
.
2. Reconnect the main power. Release bu on #2 a er LEDs #1 to #4 flashed. Then release bu on #1
a er LEDs #1 and #2 flashed. Power LED will start flashing quickly.
3. Press bu on #1, 4 mes. Then the module address will be displayed by LEDs in binary.
4. Press bu on #1 to increase the module address and bu on #2 to decrease it.
5. Press bu on #3 to save the module address and bu on #4 to cancel. A er saving the new module
address or canceling the process, the module will reset.
The devices which are connected from a common interface cannot have same module
address.