background image

 

 

 
 

 

 

V0REV5ES1218

 

 

 

 

 

INSTALLATION AND USER MANUAL  

HTM EVI SERIES 

 

Summary of Contents for HTM EVI SERIES

Page 1: ...1 V0REV5ES1218 INSTALLATION AND USER MANUAL HTM EVI SERIES ...

Page 2: ...INSTALLATION AND USER MANUAL HTM 24E 2 V0REV5ES1218 ...

Page 3: ...t could lead to hazardous situations causing damage or injuries to the user third parties or even to the product itself or material goods The installer has the responsibility to install the minimum safety devices hydraulic and electrical set out in this Manual In case of failure the lack of any device may cause burns or other injuries The installer has the responsibility to inform the user about t...

Page 4: ...l Liquid distributors Anchoring elements Heating Module Silent Blocks User Manual 4 Indications about transport and unpacking the unit The HTM E is supplied packed into a wooden pallet properly secured to prevent damage during transport The material that CLIMER TECHNOLOGY uses to the packing are recyclables so dispose it in an appropriate container Use a forklift or hand pallet truck to transport ...

Page 5: ...essor thermostat Electric switchboard with overcurrent and short circuit protections Flow switch Temperature sensors placed at inlet and outlet water pipe Steel lacquered casing Below are indicated the technical data of the system HTM24E Heating capacity range 1 W 26210 18710 Input power range 1 W 4220 4260 Heating capacity range 2 W 26050 19610 Input power range 2 W 7600 7390 Heating capacity 3 W...

Page 6: ...r Copper Rods 40 Siver Insulating hose Drill Screwdriver Hydraulic installation components Electric installation components Once it has been checked that it is available all the necessary components and tools the installer should follow the next steps 1 Placing and anchoring panels 2 Installation of the liquid distributors 3 Installation of the gas manifold 4 Joining and welding the refrigerant pi...

Page 7: ...nels may also have other orientations but northerly orientation is the worst to receive solar radiation Inclination The minimum inclination of the panel is 15 º in order to ensure the correct evaporation of the coolant It is recommended to install the panel with an inclination between 45º and 90 º Orientation It is possible to install the panel both in vertical or horizontal position When the pane...

Page 8: ...ls Gap between panels A minimum distance of 50 cm between panels should be kept in order to have enough space to fit the pipes and collectors In the picture below is shown the dimensions of the panel 2 Anchoring panels Beside the panels is supplied a bag with anchoring elements that contain the following pieces per each panel 6 x Aluminium support L shape 6 x Screws M5 12 x Nuts M5 18 x Washer 5 1...

Page 9: ...according to the picture IMPORTANT To ensure the same flow of refrigerant in every panel and consequently take advantage of the evaporation surface entirely you should install the same tube length from the distributor to every panel If a pipe is too long for the length require it must be rolled up Panels are supplied with two nuts at the inlet and outlet connection The inlet to each panel is 1 4 i...

Page 10: ...y All the secondary collectors will be joined to the main suction line A Main suction line 4 Pipe connections Once the panel scheme is made proceed to join the liquid and suction line Refrigerant quality copper pipe is used to make the connection with a diameter specified in the following table Model Suction Line Liquid Line HTM 24E 1 1 8 3 4 ...

Page 11: ...d the connections disposition Models A mm B mm C mm W1 Water Outlet W2 Water inlet G L E Electric connection HTM 24E 690 658 734 1 1 1 8 3 4 4 wires The place where the module will be installed should allow an easy access to it in order to make maintenance work or inspection It is recommended to leave at least 400 mm of free space ...

Page 12: ... or resting places Try to place the heating module as near as possible of the panels installation and also near to the buffer tank Installer must install the supplied Silent blocks to avoid the transmission of vibration 7 CONNECTION BETWEEN HEATING MODULE AND PANELS CAUTION Heating Module is preload with a 20 kg of Nitrogen to ensure its tightness during the transport Liquid and suction connection...

Page 13: ...let and outlet refrigerant pipe in order to proceed with the welding Another option is to install a coupler between pipes e Welding Join the suction line that comes from the panels to the coolant inlet and the liquid line to the coolant outlet Then weld it by the oxyacetylene welding f Nitrogen load In order to check the tightness introduce nitrogen by using the pressure gauge already installed in...

Page 14: ...OFF and using the load port located at the high pressure line always in liquid state Once the initial load has been done make hydraulic and electric installation When the heating module has been connected to the grid switch on the grid voltage via the line circuit breaker DO NOT ACTIVE TH SYSTEM BY THE THERMOSTAT The heating module must be switch off at least 10 minutes while the crankcase heater ...

Page 15: ...on pump Ball valves Lined Filter Strainer Y Type Pressure reducing valve Expansion vessel Safety valve For the selection of the circulating pump it is needed to take into account the pressure loss in pipes and accessories pipe elbow filter valves In the following table is shown the water flow that must flow at least through the heat exchanger Standard models Water flow L h Pressure loss kPa HTM 24...

Page 16: ...l The minimum wire section and the characteristics of the circuit breaker that the installer has to install are shown in the following table These data are calculated based on a maximum distance of 15m In case of higher distances contact with technical department for a new dimensioning 2 Circulator pump Connect the circulator pump to the heating module The system will control automatically the ope...

Page 17: ...g an external switch to control the ON OFF of the system It is a zero voltage contact that must be connected to the terminals 7 7 If the installer does not use an external switch jumper connect the terminal blocks 7 7 In this case the module will be switch on through the thermostat see section 10 Comminisioning ...

Page 18: ...ess for 5 sec Access to USER parameter Navigation menu Once pressing Select item in programming and visualising environment value of USER parameters Confirmation Navigation menu Once pressing Select upper item in menus Mode modify Once pressing Increase parameter value Mode normal Press for 5 sec Swicht on off the system if the remote swicht is not installed Navigation menu Once pressing Select lo...

Page 19: ...USER MANUAL HTM 24E 19 V0REV5ES1218 3 Modifying parameters Below is shown in the picture the procedure to change the parameters r03 Change the hot water temperature set point r04 Change temperature differential 5 s menu ...

Page 20: ...ure Automatic 5 times in one hour Once exceeded manually reset TC1 Circuit thermal overload Manual E1 Probe B1 Automatic reset E2 Probe B2 Automatic reset FL Flow switch Automatic 5 times in one hour Once exceeded manually reset ELS Low supply voltage Automatic EHS High supply voltage Automatic CP1 Hours of compressor working Manual Reset The system does not stop ...

Page 21: ...INSTALLATION AND USER MANUAL HTM 24E 21 V0REV5ES1218 12 ANNEX HYDRAULIC SCHEME ...

Page 22: ...22 V0REV5ES1218 ELECTRICAL DIAGRAM THREE PHASE UNITS ...

Page 23: ...INSTALLATION AND USER MANUAL HTM 24E 23 V0REV5ES1218 A POWER CIRCUIT K1 K1 FS L1 L3 L2 L1 L1 N N IE 400V 3 50Hz N L2 L3 L2 L3 L1 N L2 L3 B mm Cu 2 IM K3 K3 L L1 N N IE 220V 1 50Hz N L N B mm Cu 2 IM ...

Page 24: ...INSTALLATION AND USER MANUAL HTM 24E 24 V0REV5ES1218 ELECTRONIC EXPANSION VALVE DIAGRAM ...

Page 25: ...sel 3 Lined Filter strainer Y type 4 Pump 5 Safety valve 6 By pass 7 Underfloor heating 8 HTM 9 Buffer tank B1 Temperature probe Electric Scheme LP Low pressure switch TC Compressor temperatura switch FL Flow switch HP High pressure switch RC Crankcase heater K1 Compressor K3 Pump FS Phase detector VS Solenoid valve ...

Page 26: ...INSTALLATION AND USER MANUAL HTM 24E 26 V0REV5ES1218 CLIMER TECHNOLOGY S L L V1REV2 This company reserves the right to modify the information contained herein without prior notice ...