background image

   

 

Overview 

The EBDSPIR-AD PIR (passive infrared) presence detector 
provides automatic control of lighting loads with optional 
manual control. 
Output Channel 1 comprises a mains voltage relay capable 
of simple on/off switching, while Output Channel 2 provides 
dimmable control of 1-10V ballasts. 
Functioning as a presence detector, the unit can turn lights 
on when a room is occupied and off when the room is 
empty. Optional settings allow lights to be turned off in 
response to ambient daylight, or to implement a maintained 
illuminance (daylight harvesting) system. 

All functionality is fully programmable using an IR handset. 

Features 

Back features 

Ceiling PIR presence detector – 1-10V dimming 

EBDSPIR-AD, EBDSPIR-AD-IP 

Product Guide 

Retaining Spring 

Retaining Spring 

Power Input 
& Switched 
Output Connector 

(Channel 1) 

Dimmable 

Control Output 

Connector 

(Channel 2) 

Switch Input 

Connector 

PIR Sensor 

Detects movement within the unit’s detection range, 
allowing load control in response to changes in occupancy. 

IR Receiver 

Receives control and programming commands from an  
IR (infrared) handset. 

Light Level Sensor 

Measures the overall light level in the detection area  

Status LEDs 

The LED flashes 

R

ed to indicate the following: 

Power Input & Switched Output Connector 

(Channel 1)

 

Used to connect mains power to the unit and to connect a 
switched load. 

Dimmable Control Output Connector 

(Channel 2)

 

Used to connect 1-10V controllable ballasts and 
transformers for dimmable loads. 

Switch Input Connector 

Two input terminals can be used to manually override the 
dimming levels and override the lights on or off. 

Walk Test LED active 

        

when movement is detected

 

Valid setting received 

 

Front features 

Sensor Lens 

which covers... 

 

PIR Sensor 

IR Receiver 

Light Level Sensor 

Status LEDs 

Mounting Bezel 

EBDSPIR-AD-IP-LT30 

A special order version that can be used down to -30ºC 

Summary of Contents for EBDSPIR-AD

Page 1: ...ontrol Output Connector Channel 2 Switch Input Connector PIR Sensor Detects movement within the unit s detection range allowing load control in response to changes in occupancy IR Receiver Receives control and programming commands from an IR infrared handset Light Level Sensor Measures the overall light level in the detection area Status LEDs The LED flashes Red to indicate the following Power Inp...

Page 2: ...2 Detection diagram Area of lower sensitivity Area of high sensitivity ...

Page 3: ... Walk Test LED which will flash red when movement is detected Switch Level On Off Occupancy detection can be made dependant on the ambient light level using the Lux On Level and Lux Off Level parameters Maintained Illuminance daylight harvesting The detector measures the overall light level in the detection area and calculates the correct output for the luminaires to achieve a preset lux level mai...

Page 4: ...than 1 second The handset will click every time a parameter is received The device will show multiple flashes of its LED All of the values will be shown against the parameters in the menu The individual parameters may be edited and then saved as a Macro Notes If a parameter s has been missed because of a communication error the missing value s is replaced by dashes When reading back the Channel 1 ...

Page 5: ...L OUT L N SW1 UP SW2 DOWN DIMMING BALLAST DIMMING LUMINAIRE 1 10V CIRCUIT PROTECTION IF REQUIRED LIVE NEUTRAL CENTRE BIASED RETRACTIVE SWITCH 240V SWITCHING Optional for presence mandatory for absence detection L OUT L N SW1 UP SW2 DOWN CIRCUIT PROTECTION IF REQUIRED LIVE NEUTRAL CENTRE BIASED RETRACTIVE SWITCH 240V SWITCHING Optional for presence mandatory for absence detection LUMINAIRE NON DIMM...

Page 6: ...f Turns off after occupancy Channel mode Set to Switch only Switch mode Set to 2 position switch together Note a single position switch can be used instead to toggle the output set to 1 position switch separate L OUT L N SW1 UP SW2 DOWN DIMMING BALLAST DIMMING LUMINAIRE 1 10V CIRCUIT PROTECTION IF REQUIRED LIVE NEUTRAL CENTRE BIASED RETRACTIVE SWITCH 240V SWITCHING Optional for presence mandatory ...

Page 7: ...ircuit is good Check that the load is functioning by bypassing the sensor e g link terminals L and L Out on Channel1 If the detection range is smaller than expected check the diagram on page 2 Rotating the sensor slightly may improve the detection range HINT The Walk Test LED function can be used to check that the unit is detecting movement in the required area What if the load does not turn OFF E...

Page 8: ...ux On Level value Sensitivity 9 1 5 9 3 6 8 Sensitivity level for detecting movement 1 low sensitivity 9 high sensitivity Defaults D Returns the unit to the default settings Burn in 0 0 50 100 Determines how long the output will be at 100 so that lamps burn in The burn in time is not affected by power supply interruptions Presence Absence Presence Presence Absence Presence mode allows the output t...

Page 9: ...ght they will turn off again after the Lux Time Note that whenever the an external switch is pressed whether in absence or presence mode if the lights were out because of the lux level they will be immediately turned on again for at least the Lux Time Power Up State On On or Off Select No for a 30 second delay on start up If Yes is selected there will be no delay on start up and the detector will ...

Page 10: ...Maximum dimming output level Min Value 0 0 to 100 Minimum dimming output level Memorise N Yes or No If this is set to Yes the last manual lux level set will be memorised and used as the new switch on level On value 99 0 to 99 Dimming output level when switched on 0 99 Off value 0 0 to 99 Dimming output level when switched off 0 99 If a non zero off value is set then the output will toggle between ...

Page 11: ...11 This page intentionally left blank ...

Page 12: ...35ºC Humidity 5 to 95 non condensing Material casing Flame retardant ABS and PC ABS Type Class 2 IP rating EBDSPIR AD IP40 EBDSPIR AD IP IP55 EBDSPIR AD IP LT30 IP55 Compliance EMC 2004 108 EC LVD 2006 95 EC Technical data Part numbers C P Electronics Ltd Brent Crescent London NW10 7XR United Kingdom Tel 44 0 333 900 0671 Fax 44 0 333 900 0674 www cpelectronics co uk enquiry cpelectronics co uk Re...