INSTALLATION INSTRUCTIONS

INSTRUCTIONS D’INSTALLATION

TO INSTALL:

DIRECT MOUNT - CANOPY APPLICATIONS

NOTE: 

For use with XA-BXCCJBOX accessory or customer 

supplied junction box and stem.

STEP 1:

Remove bushing from threaded hub.

STEP 2:

Cut a 2.0” hole for stem into canopy. For installation using 
alignment template instructions refer to “Alignment 
Template (Optional)” section.

NOTE: 

Luminaire can be mounted to an existing hole in 

canopy up to 4” diameter. 

STEP 3:

To mount luminaire to canopy, insert and tighten (4) 
supplied Phillips hex head self-drilling sheet metal 
screws as shown in 

Figure 1.

STEP 4: 

From above canopy feed leads from luminaire through 
customer supplied 3/4” NPT Stem. Screw customer 
supplied NPT Stem into luminaire hub. See 

Figure 2.

STEP 5: 

Attach customer supplied junction box to the other end of 
the customer supplied 3/4” NPT Stem and make wiring 
connections into customer supplied junction box per 

Electrical Connections

” section.

STEP 6:

Apply sealant around stem, hub and alignment screw for a 
complete seal. 

ALIGNMENT TEMPLATE (OPTIONAL)

STEP 1:

Reference 

Figure 3 

for alignment. Insert supplied #8 

screw into alignment hole on luminaire. See 

Figure 4 

(on 

back page).

STEP 2:

Cut a 2.0” hole into the desired location of the canopy to 
mount the threaded hub of the luminaire. See 

Figure 3.

STEP 3:

4” away from the Stem Hole, drill a 0.325” hole, Alignment 
Hole, using a 11/32” drill bit for the alignment screw. See 

Figure 3.

1

Insert 

Mounting 

Screws

2

3/4” NPT Stem
(Provided by customer)

Canopy

Luminaire Hub

  2.00” 

  0.325” 

 4.00” 

3

Stem Hole

Alignment Hole

IMPORTANT SAFEGUARDS

When using electrical equipment, basic safety precautions should always be followed including the 
following:

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

1.  DANGER

- Risk of shock- Disconnect power before installation.

DANGER

 – Risque de choc – Couper l’alimentation avant l’installation.

2.  This luminaire must be installed in accordance with the NEC or your local electrical code. If you 

are not familiar with these codes and requirements, consult a qualified electrician. 

Ce produit doit être installé conformément à NEC ou votre code électrique local. Si vous n’êtes 

pas familier avec ces codes et ces exigences, veuillez contacter un électricien qualifié.

3.  DO NOT lift luminaire by the power leads or cord.

SAVE THESE INSTRUCTIONS FOR FUTURE 

REFERENCE

NOTE:

No user maintenance is required. Do not 
remove the enclosure cover after installation.