background image

FLEX Series with Cree SmartCast

®

 Technology

Commercial Specification Troffers with Emergency Driver

Includes: FLX14™, FLX22™ and FLX24™

INSTALLATION INSTRUCTIONS

1 of 4

LPN00611X0001A1_C

FLX14™

FLX22™

FLX24™

•  The FLEX Series of specification troffers is for non-insulated 

ceiling applications using T-Bar ceiling grid, drywall grid adaptors, 
and suspended mount. 

•  Designed for use in 120-277V 50-60 Hz or 347V 60Hz protected 

circuit (fuse box, circuit breaker). Supply wire sized as per NEC or 
governing code(s), 90C rated.  

•  Make sure to cap off all unused leads.
•  Lens and removable end cap may shift during installation. To seat 

lens press end caps and squeeze lens to engage with back panel.

IMPORTANT SAFEGUARDS

When using electrical equipment, basic safety precautions should 

always be followed including the following:

READ AND FOLLOW ALL SAFETY 

INSTRUCTIONS

1.  DANGER

- Risk of shock- Disconnect power before installation.

DANGER

 - RISQUE DE CHOC - COUPER L’ALIMENTATION 

AVANT L’INSTALLATION

2.  CAUTION 

– Installation and servicing should be performed by 

qualified personnel only. De-energize before opening.

ATTENTION 

– L’installation et l’entretien doivent être effectués 

par du personnel qualifié seulement. Mettre hors tension avant 

l’ouverture

3.  To reduce the risk of electric shock, disconnect both standard 

and emergency power supplies and converter connector of the 

emergency driver before servicing.

Pour réduire le risque de décharge électrique, vous devez 

déconnecter à la fois le disjoncteur divisionnaire ou les fusibles et 

les alimentations d’urgence avant l’entretien.

4.  Do not use outdoors.

Ne pas utiliser à l’extérieur.

5.  Do not let power supply cords touch hot surfaces.

Ne laissez pas les cordons d’alimentation toucher les surfaces 

chaudes.

6.  Do not mount near gas or electric heaters.

Ne montez PAS près des appareils de chauffage de gaz ou 

électriques.

7.  DO NOT use this equipment for other than its intended use.

NE PAS utiliser cet équipement à d’autres fins que celle qui est 

prévue.

8. 

Equipment should be mounted in locations and heights where it will not readily be subjected to tampering by unauthorized 

personnel.

L’équipement doit être monté dans des endroits et à des hauteurs où il ne sera pas soumis à des altérations par des personnes 

non autorisées.

9.  The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.

L’utilisation d’accessoires non recommandés par le fabricant peut causer une situation dangereuse. 

10.  Suitable for suspended ceilings.

11.  Max. mounting height: 15 ft.

Hauteur de montage max.: 15 pieds.

12.  Access above ceiling required. Do not install insulation within 3” (76mm) of any part of the luminaire. 

Accès requis au-dessus du plafond. Ne pas mettre l’isolant à moins de 3 po (76 mm) de toute partie du luminaire

13.  Suitable for suspended ceilings.

Convient aux plafonds suspendus.

SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE

Summary of Contents for FLEX Series

Page 1: ...tor of the emergency driver before servicing Pour réduire le risque de décharge électrique vous devez déconnecter à la fois le disjoncteur divisionnaire ou les fusibles et les alimentations d urgence avant l entretien 4 Do not use outdoors Ne pas utiliser à l extérieur 5 Do not let power supply cords touch hot surfaces Ne laissez pas les cordons d alimentation toucher les surfaces chaudes 6 Do not...

Page 2: ... bend the luminaire hooks against the T Bar to secure the luminaire See Figure 1 SUSPENDED MOUNTING STEP 1 Attach customer supplied cables to the 2 cable slots on each side of the housing See Figure 2 STEP 2 Attach customer supplied cables to mounting surface using customer supplied hardware Ensuring that mounting surface can support the luminaire STEP 3 Attach the RF Module to the luminaire by cl...

Page 3: ...witch assembly by screwing the small trim ring removed in Step 5 back onto the test switch assembly Tighten the larger trim ring above the ceiling until it is snugged tight against the ceiling See Figure 5 CLEANING LENS STEP 1 Remove lens and end cap assembly by pulling straight downward gently See Figure 6 STEP 3 After cleaning is complete insert lens and end cap assembly back into the luminaire ...

Page 4: ...e checked periodically to ensure that it is working The following schedule is recommended Visually inspect the charging indicator light monthly It should be illuminated Test the emergency operation of the fixture at 30 day intervals for a minimum of 30 seconds When the test switch is depressed the LED array should operate Conduct a 90 minute discharge test once a year The LED array should operate ...