background image

 
 

Installation and Startup Guide

This document covers the installation of CTP107-E Series HMI, for the detailed specifications 
and operation, please refer to Brochure and 

Crouzet Touch

 Soft User Manual. 

Handling and Storage: 

Environmental 
Considerations

 

(1)

Storage temperature -20°C/+60°C.

(2)

Do not let water penetrate into packaging boxes during their storage and

transportation.

(3)

Do not store the product in places of high temperature or under direct

sunlight.

(4)

Please also avoid the places of high humidity. Be sure not to expose the

product to condensation, rain or frozen condition.

Install Environment: 

NEMA Rating

 

CTP107-E Series HMI is NEMA 4 rated (Indoor Only). 

Electrical 
Environment

 

CTP107-E Series HMI has been tested to conform to European CE 
requirements. This means that the circuitry is designed to resist the effects of 
electrical noise. This does not guarantee noise immunity in severe cases. Proper 
wire routing and grounding will insure proper operation. 

Environmental 
Considerations

 

(1)

Make sure that the displays are installed correctly and that the operating
limits are followed. Avoid installing units in environments where severe
mechanical vibration or shocks are present.

(2)

Do not operate the unit in areas subject to explosion hazards due to
flammable gases, vapors or dusts.

(3)

Do not install the unit where acid gas, such as SO2 exists.

(4)

This device should be mounted in the vertical position and for use on the flat
surface enclosure.

(5)

Conform to UL508 (ISBN 0-7629-0404-6) machine safety for use in
Pollution Degree 2 Environment.

Unpacking the Unit

Installation Instructions 

Secure the operator panel in position, using all the fastening holes and the provided brackets   
and screws. Screw Torque: 0.29 ~ 0.44 N.m (For reaching waterproof effect and preventing the panel 
from being deformed.) 

Type 

A(mm) 

B(mm) 

CTP107-E 

192 

138 

USB Stick Clamp Usage 

Combining the USB Stick with the clamp and the tying strap can prevent USB stick from disconnecting 
with HMI when strong vibration is present. 
1. Insert the USB connector to the clamp and tie them together with the tying strap.
2. Press the spring and insert the USB stick into HMI.

Power Connections 

 

 

 

System Settings 

When HMI is powered up and displays image, 
click the system setting button. 
(Default System Password: 111111) 
It is necessary to connect the HMI to   
your network through a RJ-45 cable. 

CTP107-E series    88 970 564

 

Installation Instruction 

Unpack and check the delivery. If damage 
is found, notify the supplier. 

NOTE:   

Place the operator panel on a stable 
surface during installation. Dropping it or 
letting it fall may cause damage. 

Go to the Network tab, you may choose 
to auto get DHCP IP, or designate your 
own IP.

 

NOTE: 

1. Conne

ct positive DC line to the ‘+’ terminal and the DC

ground to 

the ‘-’ terminal.

2. When using a USB cable to download project file, please
do not connect HMI with PLC and PC simultaneously to
prevent potential difference from destroying USB ports of
HMI and PC.

(A) 

(B)

Cutout

(1) 

(2) 

(3) 

(5)

(4)

(6) 

(1) Installation Instruction, 2-sided A4 *1

(2) Human Machine Interface *1

(3) Power Connector *1

(4) Brackets & Screws *1 pack

(5) USB Stick Clamp & Tying Strap *1

(6) Fuse 1.25A/250V 5*20mm *1

Reviews: