background image

 

 
 
 
 

 

 

 

 

LE825G / CP685AVR-G / CP825AVR-G   

User

’s Manual 

K01-0000064-01 

 

IMPORTANT SAFETY WARNINGS 

(SAVE THESE INSTRUCTIONS) 

This manual contains important safety instructions. Please read and follow all instructions carefully during installation and operation of the unit. 

Read this manual thoroughly before attempting to unpack, install, or operate your UPS. 

CAUTION!   

To  prevent  the  risk  of  fire  or  electric  shock,  install  in  a  temperature  and  humidity  controlled  indoor  area  free  of  conductive 

contaminants.    (Please see specifications for acceptable temperature and humidity range). 

CAUTION!   

To reduce the risk of electric shock, do not remove the cover except to service the battery.    There are no user serviceable parts 

inside except for battery. 

CAUTION!   

Hazardous live parts inside can be energized by the battery even when the AC input power is disconnected. 

CAUTION!    The 

UPS must be connected to an AC power outlet with fuse or circuit breaker protection.    Do not plug into an outlet that is not 

grounded.    If you need to de-energize this equipment, turn off and unplug the unit. 

CAUTION!   

To avoid electric shock, turn off the unit and unplug it from the AC power source before servicing the battery or installing a computer 

component. 

CAUTION!

    To  reduce  the  risk  of  fire,  connect  only  to  a  circuit  provided  with  20  amperes  maximum  branch  circuit  over  current  protection in 

accordance with the National Electric Code, ANSI/NFPA 70. 

DO  NOT  USE  FOR  MEDICAL  OR  LIFE  SUPPORT  EQUIPMENT!   

CyberPower  Systems  does  not  sell  products  for  life  support  or  medical 

applications.   

DO  NOT

  use  in  any  circumstance  that  would  affect,  operation,    safety  of  any  life  support  equipment  or  with  any  medical 

applications or patient care. 

DO NOT USE WITH OR NEAR AQUARIUMS!   

To reduce the risk of fire or electric shock, do not use with or near an aquarium.

   

Condensation 

from the aquarium can cause the unit to short out. 

 
 

INSTALLING YOUR UPS SYSTEM   

 

 

UNPACKING 

Inspect the UPS upon receipt. The box should contain the following: 

(1) UPS unit; (2) 

User’s manual; (3) USB device cable; (4) PowerPanel

®

 Personal Edition software CD or Free download card

 

 

WHAT IS AVR?

 

The

 

LE825G/CP685AVR-G/CP825AVR-G provide complete power protection 

from 

utility 

power 

that 

is 

not 

always 

consistent. 

The 

LE825G/CP685AVR-G/CP825AVR-G  feature  1030  Joules/890  Joules/1030 

Joules  of  surge  protection,  and  provide  long  lasting  battery  backup  during 

power  outages.  The  LE825G/CP685AVR-G/CP825AVR-G  ensure  consistent 

power  to  your  computer  system  and  include  software  that  will  automatically 

save your open files and shutdown your  electronic equipment during a utility 

power loss. 

 

AUTOMATIC VOLTAGE REGULATOR

 

The

 

LE825G/CP685AVR-G/CP825AVR-G

 

stabilize utility power voltage levels 

that can be inconsistent.    The incoming utility power may be damaging to 

important data files and hardware, but with Automatic Voltage Regulation,

 

the 

computer will not experience damaging voltage levels.    An Automatic Voltage 

Regulator automatically increases low or decreases high voltage to a 

consistent, computer safe 110v/120v. 

The unit’s powerful battery will provide power only if the incoming voltage drops below 90v or increases 

above 140v. 

 

SYSTEM FUNCTIONAL BLOCK DIAGRAM 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT

 

1.

  Ensure that the equipment plugged into the UPS 

does not exceed the UPS unit’s rated capacity (685VA/390W for CP685AVR-G, 

825VA/450W for LE825G/CP825AVR-G). If the rated capacities of the unit are exceeded, an overload condition may occur and cause the 

UPS unit to shut down or the circuit breaker to trip.     

2.

  There are many factors that can affect the amount of power that your electronic equipment will require.    It is suggested that the load you will 

be placing on the outlet not exceed 80% of the unit’s capacity. 

 

HARDWARE INSTALLATION GUIDE 

1.  Your new UPS may be used immediately upon receipt.    However, 

recharging the 

battery for at least 8 hours

 is recommended to e

nsure that the battery’s maximum 

charge capacity is achieved.    A loss of charge may occur during shipping and 

storage.    To recharge the battery, simply leave the unit plugged into an AC outlet. 

2.  With the UPS unit off and unplugged, connect your computer, monitor, and any other 

peripherals requiring battery backup into the battery power supplied outlets.    Plug 

your other peripheral equipment (printer, scanner, speakers) into the full-time surge protection outlets.   

DO NOT plug a laser printer, paper 

shredder, copier, space heater, vacuum cleaner, sump pump or other large electrical device into battery and surge protected outlets.   

The power demands of these devices will overload and possibly damage the unit. 

3.  To protect a network connection from surges, connect a network cable into the IN jack of the UPS. Then connect 

a network cable from the OUT jack on the UPS to the network device. 

4.  Plug the UPS into a 2 pole, 3 wire grounding receptacle (wall outlet).    Make sure the wall branch outlet is 

protected by a fuse or circuit breaker and does not service equipment with large electrical demands (e.g. air 

conditioner, refriger

ator, copier, etc…).    The warranty prohibits the use of extension cords, outlet strips, and surge strips in conjunction with 

the UPS unit. 

5.  P

ress the power switch to turn the unit on.    The power on indicator light will illuminate and the unit will “beep”. 

6.  If an overload is detected, an audible alarm will sound and the unit will emit one long beep.    To correct this, turn the UPS off and unplug at 

least one piece of equipment from the battery power supplied outlets.    Make sure the circuit breaker is depressed and then turn the UPS on. 

7.  To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times. 

8.  To store your UPS for an extended period of time, cover it and store with the battery fully charged.    While in storage recharge the battery 

every three months to ensure battery life. 

 

 

BASIC OPERATION 

 

DESCRIPTION 

 

① 

Battery and Surge Protected Outlets 

The unit has four battery powered/surge suppression outlets for connected 

equipment to ensure temporary uninterrupted operation of your equipment 

during a power failure. (

 DO NOT plug a laser printer, paper shredder, 

copier, space heater, vacuum cleaner, sump pump or other large 

electrical device into battery and surge protected outlets. The power 

demands of these devices will overload and possibly damage the unit.)

 

② 

Full-Time Surge Protection Outlets 

The unit has four surge suppression outlets which are always ON. 

③ 

Power Switch 

Press the power button to turn the UPS ON or OFF. 

④ 

Power On Indicator 

This LED is illuminated when the utility power is normal and the UPS outlets are providing power, free of surges and spikes. 

⑤ 

Electrical Wiring Fault Indicator 

This LED indicator will illuminate to warn the user that a wiring problem exists, such as bad ground, missing ground or reversed wiring.    If 

this is illuminated, it is recommended to disconnect all electrical equipment from the outlet and have an electrician verify the outlet is 

properly wired. The unit will not provide surge protection without being plugged into a grounded and properly wired wall outlet. 

⑥ 

Communication Protection Ports 

Communication protection ports will protect any standard modem, fax, telephone line, network or Ethernet connection (RJ11/RJ45).

 

⑦ 

Circuit Breaker 

Located on the side of the UPS, the circuit breaker serves to provide overload and fault protection.   

⑧ 

USB Port and DB-9 Contact Closure Port to PC 

The ports allow connection and communication between the USB or DB-9 port on the computer and the UPS unit.    The UPS 

communicates its status to the PowerPanel

®

 Personal Edition software.   

 

Note: Only one of the ports, USB or DB-9, can be used to communicate with your computer at one time. 

⑨ 

Outlets Designed for AC Adapters 

The unit has four outlets spaced to allow AC power adapter blocks to be plugged into the UPS without overlapping or blocking adjacent 

outlets. 

⑩ 

Coax/Cable/DSS Surge Protection 

The Coax/Cable/DSS surge protection ports will protect any cable modem, CATV converter, or DSS receiver.

 

 

REPLACING THE BATTERY 

 

Replacement of batteries located in an 

OPERATOR ACCESS AREA

1. 

When replacing batteries, replace with the same number of the following battery: RB1280 for CP685AVR-G; RB1280A for 

LE825G/CP825AVR-G. 

2. 

CAUTION! Risk of Energy Hazard, 12V, maximum 8 (CP685AVR-G) or 9 (LE825G/CP825AVR-G) Ampere-hour battery. Before replacing 

batteries, remove conductive jewelry such as chains, wrist watches, and rings. 

3. 

CAUTION! 

  Do not dispose of batteries in a fire. The batteries may explode; 

4. 

CAUTION! 

  Do not open or mutilate batteries. Released material is harmful to the skin and eyes. It may be toxic. 

CAUTION - RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE. DISPOSE OF USED BATTERIES ACCORDING 

TO LOCAL REGULATIONS. 

 

TO REPLACE THE BATTERY 

1.  Turn off and unplug all connected equipment. 

2.  Unplug it from the AC power source. 

3.  Turn the UPS upside down. 

4.  Remove the 1 retaining screw. 

5.  Slide the battery compartment cover completely off of the unit. 

6.  Remove the battery from the compartment. 

7.  Disconnect the battery wires from the battery. 

8.  Install the replacement battery by connecting the red wire and black wire to the positive (+) and negative (-) terminal of the battery. 

9.  Put the battery back into the compartment. 

10.  Slide back the battery compartment cover and tighten the retaining screw. 

11.  Charge the unit for 4 

– 8 hours to fully charge the battery. 

REMINDER:   

Batteries are considered 

HAZARDOUS WASTE

 and must be disposed of properly.    Most retailers that sells lead-acid batteries 

collects used batteries for recycling, as required by local regulations. 

 

TROUBLE SHOOTING 

 
 

Problem

 

Possible Cause 

Solution

 

Full-time surge protection outlets 
stop providing power to 
equipment. Circuit breaker 
button is projecting from the side 
of the unit.

 

Circuit breaker has been tripped due 
to an overload. 

Turn the UPS off and unplug at least one piece of equipment.   
Wait 10 seconds, reset the circuit breaker by pressing the 
button, and then turn the UPS on.

 

The UPS does not perform 
expected runtime. 

Battery not fully charged. 

Recharge the battery by leaving the UPS plugged in. 

Battery is worn out. 

Contact CyberPower Systems about replacement batteries at 
tech@cpsww.com. 

The UPS will not turn on. 
 

The on/off switch is designed to 
prevent damage by rapidly turning it 
off and on. 

Turn the UPS off.    Wait 10 seconds and then turn the UPS on. 

The unit is not connected to an AC 
outlet. 

The unit must be connected to a 110/120v 60Hz outlet. 

The battery is worn out. 

Contact CyberPower Systems about replacement batteries at 
tech@cpsww.com. 

Mechanical problem. 

Contact CyberPower Systems at tech@cpsww.com. 

PowerPanel

®

 Personal Edition is 

inactive (all icons are gray). 

The USB / serial cable is not 
connected. 

Connect the USB / serial cable to the UPS unit and an open 
USB / serial port on the back of the computer.    You must use 
the cable that came with the unit. 

The USB / serial cable is connected 
to a bad USB port. 

Check for a different USB port and plug the cable in. 

The unit is not providing battery 
power. 

Shutdown your computer and turn the UPS off.    Wait 10 
seconds and turn the UPS back on.    This should reset the unit. 

The serial cable is not the cable that 
was included with the UPS unit. 

If you are using a serial cable you must use a CyberPower serial 
cable.    If you need this cable please contact technical support.   
tech@cpsww.com. 

Additional troubleshooting information can be found at 

“Support” at 

www.CPSww.com

 

EMI Filter 

Surge 

Suppressor

 

AVR 

Charger 

AC/DC 

Battery 

Inverter 

DC/A

Input 

Output 

Normal Mode 

Battery Mode 

Reviews: