OPERATION MANUAL

3 Phase Power Analyser / 

Data Logger

Model LDW-6095K

Your purchase of this 3 PHASE

POWER ANALYZER marks a step

forward for you into the field

of precision measurement.

Although this POWER ANALYZER

is a complex and delicate

instrument, its durable structure

will allow many years of use if

proper operating techniques are

developed.

Please read the following

instructions carefully and always

keep this manual within easy

reach.

Summary of Contents for LDW-6095K

Page 1: ... a step forward for you into the field of precision measurement Although this POWER ANALYZER is a complex and delicate instrument its durable structure will allow many years of use if proper operating techniques are developed Please read the following instructions carefully and always keep this manual within easy reach ...

Page 2: ... not apply the overload voltage current to the input terminal Remove test leads before open the battery cover Cleaning Only use the dry cloth to clean the plastic case Environment Conditions Installation Categories III 600V Pollution Degree 2 Altitude up to 2000 meters Indoor use Relative humidity 80 max ...

Page 3: ...scription before measuring 17 5 MEASURING PROCEDURES 46 5 1 1Φ 2W one phase by two wires measurement 46 5 2 1Φ 3W one phase by three wires measurement 47 5 3 3Φ 3W three phase by three wires measurement 49 5 4 3Φ 4W three phase by four wires measurement 50 5 5 The CT and PT measurement 52 5 6 ZERO adjustment for Watt Hour 53 5 7 Harmonic Function Measurement 54 5 8 Graphic Phasor Diagram 56 5 9 Vo...

Page 4: ...BAT screen 67 5 16 Appendix 1 68 6 MAINTENANCE 69 6 1 Cleaning 69 6 2 Replacement of batteries 69 7 RS232 PC SERIAL INTERFACE 70 8 Download the saving data from the SD card to the computer EXCEL software 72 9 PATENT 76 10 THE ADDRESS OF AFTER SERVICE CENTER 77 ...

Page 5: ...DC 9V adapter 2 G SD memory card and Carrying bag Measurement V phase to phase V phase to ground A phase to ground KW KVA KVAR PF phase KW KVA KVAR PF system KWH KVAH KVARH PFH system Phase angle Harmonics display 1 50th order Simultaneous display of Harmonics and Wave form Display of Waveform with Peak Values Analysis of Total Harmonic Distortion THD Graphic Phase diagram with 3 Phase system para...

Page 6: ...selves Powered by AA UM 3 DC 1 5 V X 8 batteries Alkaline type or DC 9V adapter Computer data output can cooperate with optional USB Cable LUSB 01 RS232 cable LUPCB 02 and Data Acquisition software Optional current probes LCP 1201 LCP 2000 LCP 200 LCP 3000 detail specification User can order the meter only without the current probes with the special request as intend to cooperate their own current...

Page 7: ...mV 500mV 1V 2V 3V and range Current probe input current range ACA 20 A 200A 2000A 1200 A 30A 300A 3000A Meter can cooperate the universal current probe Safety IEC1010 CAT III 600 V standard ACV input 10 Mega ohms impedance Range select ACV Auto range ACA Manual range Clamp 40 Hz to 1 KHz frequency response Spec tested 45 to 65 Hz frequency Over load ACV 720 ACV rms protection ACA 1300 ACA with cla...

Page 8: ... second down load to the Excel Integration time for data logger 2 seconds to 7200 seconds the during of setting step are 2 seconds Data Output RS232 computer serial interface USB RS232 Connect the optional USB cable Computer LUSB 01 will get the USB plug interface Connect the optional RS232 cable LUPCB 02 will get the RS232 plug Operating 0 to 50 32 to 122 Temperature Operating Less than 80 R H Hu...

Page 9: ...Set 4 PCs Alligator clips TL88 4AC 1 Set 4 PCs Clamp Probe LCP 1201 3 PCs AC to DC 9V adapter 1 PC SD card 2 G 1 PC Carrying bag 1 PC Optional 2000 Amp current probe LCP 2000 Accessories 200 Amp current probe LCP 200 Flexible 3000 Amp current probe LCP 3000 USB Cable LUSB 01 RS232 cable LUPCB 02 Data Acquisition software 2 2 Electrical Specifications ACV Range Resolution Accuracy 10 0V to 600 0V 0...

Page 10: ...1A 1000 A 0 5 5A 1A 1000 A Power factor Range Resolution Accuracy 0 00 to 1 00 0 01 0 04 Remark PFH Long term power factor PFΣ For 3Φ 4W 3Φ 3W PFΣ PF1 PF2 PF3 3 For 1Φ 3W PFΣ PF1 PF2 2 Φ Phase angle Range Resolution Accuracy 180 to 180 0 1 1 ACOS PF Frequency Range Resolution Accuracy 45 to 65 Hz 0 1 Hz 0 1 Hz 6 ...

Page 11: ... KVA 1 0 8KVA 1 000 to 9 999 MVA 0 001 MVA 1 0 008MVA The resolution is changed according the different ACA range Reactive Power Range Resolution Accuracy 0 000 to 9 999 KVAR 0 001 0 01 0 1KVAR 1 0 008 KVAR 10 00 to 99 99 KVAR 0 01 0 1 KVAR 1 0 08 KVAR 100 0 to 999 9 KVAR 0 1 KVAR 1 0 8 KVAR 1 000 to 9 999 MVAR 0 001 MVAR 1 0 008 MVAR The resolution is changed according the different ACA range Wat...

Page 12: ...ARH 100 0 to 999 9 KVARH 0 1 KVARH 2 0 8 KVARH 1 000 to 9 999 MVARH 0 001 MVARH 2 0 008 MVARH Harmonics of AC voltage in Magnitude Fundamental frequency 50 Hz 60 Hz Range Resolution Accuracy 1 to 20th 2 0 5 V 21 to 30th 0 1 V 4 0 5 V 31 to 50th reference Harmonics of AC voltage in Percentage Fundamental frequency 50 Hz 60 Hz Range Resolution Accuracy 1 to 20th 2 10 d 21 to 30th 0 1 4 20 d 31 to 50...

Page 13: ... d 21 to 30th 0 1 4 20 d 31 to 50th reference Peak value of ACV or ACA Range Sample Time Accuracy 50 Hz 19 us 5 30 d 60 Hz 16 us us micro seconds Crest Factor of ACV or ACA Range Resolution Accuracy 1 000 9 999 0 001 5 0 3 Total Harmonic Distortion Range Resolution Accuracy 0 to 20 0 1 2 5 d 20 1 to 100 6 10 d 9 ...

Page 14: ...3 FRONT PANEL DESCRIPTION 1 Fig 1 10 ...

Page 15: ... key button 3 11 Shift key button 3 12 Setup key button 3 13 Voltage input terminals 3 14A Current probe signal input sockets 3 14B Current probe power sockets 3 15 SD card socket 3 16 RS232 socket 3 17 Reset button 3 18 DC 9V power adapter socket 3 19 Battery Cover Battery compartment 3 20 Stand 3 21 Current Sense Jaw 3 22 Trigger 3 23A Current probe signal plugs 3 23B Current probe power plug 11...

Page 16: ...3 26 Harmonic Analysis Right Key 3 27 Harmonic Analysis V1 V2 V3 A1 A2 A3 Select Key 3 28 Harmonic Function Voltage or Current Input Range 3 29 Power Measurement Key 3 30 Phase Diagram Key 3 31 Waveform of Voltage and Current Key 3 32 Transient Key 12 ...

Page 17: ...ht display of screen 1 will show as SD Check along with blinking while inserting SD CARD then disappears after several seconds that indicates the data from SD CARD has been read completed 2 The bottom right display of screen 2 will show as NO DISK along with blinking when SD CARD is not inserted 13 ...

Page 18: ...3 0 0 WH 0 000 KWH SH 0 000KVAH QH 0 000 KVARH FREQ 0 0 Hz CP1201 SD 20A 3Φ4W SEC 2 CT 1 PT 1 Check screen 2 4 2 V12 0 0 V V1 0 0 V A1 0 00 A V23 0 0 V V2 0 0 V A2 0 00 A V31 0 0 V V3 0 0 V A3 0 00 A P1 0 000 KW S1 0 000KVA Q1 0 000 KVAR P2 0 000 KW S2 0 000KVA Q2 0 000 KVAR P3 0 000 KW S3 0 000KVA Q3 0 000 KVAR PΣ 0 000 KW SΣ 0 000KVA QΣ 0 000 KVAR PF1 0 00 PF 2 0 00 PF 3 0 00 PFΣ 0 00 PF H 0 00 ...

Page 19: ...o setup the function before measuring 8 EXIT KEY 3 8 Fig 1 Press the key to exit setting screen 9 SHIFT KEY 3 11 Fig 1 Press the key to set the different functions in setting screen 10 UP KEY 3 3 Fig 1 Press the key to move the cursor up in setting screen 11 DOWN KEY 3 4 Fig 1 Press the key to move the cursor down in setting screen 12 Harmonic Analysis Left Key 3 24 Fig 1 13 Harmonic Key 3 25 Fig ...

Page 20: ...f 220 0 V Delet File 0 SDVP 10 SD Format 0 Decimal Basic Use Size 388 KB Clamp Type CP1201 Free Size 1946 MB A Range 200A screen 1 4 4 Total Size 1946 MB V Range 200mV RS232 Out Sel PT 1 1 V1 I1 P1 CT 1 1 S1 Q1 PF1 Beep ON Φ1 FREQ Year Month Date Hour Minute Second 2010 11 13 14 37 25 Folder Name WTA01 SETUP File Name 3P401001 XLS SHIFT 2 REC Date 2008 11 28 00 03 17 Sampling Time 2 Trans Ref 220 ...

Page 21: ...at to Format SD CARD fast PT Set the potential transformer from 1 to 1000 CT Set the current transformer from 1 to 600 Beep Set to ON OFF for buzzer Clamp Type Select the Clamp Type to CP 1201 CP 200 CP 2000 CP 3000 or Other Type RS232 out Sel Set RS232 output function maximum up to nine items can be selected to output screen 1 screen 2 Year Set the year Month Set the month Date Set the date Hour ...

Page 22: ...RS232 Out Sel PT 1 1 V1 I1 P1 CT 1 1 S1 Q1 PF1 Beep ON Φ1 FREQ Year Month Date Hour Minute Second 2010 12 05 11 14 49 screen 2 4 5 1 Folder Name WTA01 SETUP File Name 3P401001 XLS SHIFT 1 REC Date 2008 11 28 00 03 17 Sampling Time 2 Trans Ref 220 0 V Delet File 0 SDVP 10 SD Format 0 Decimal Basic Use Size 388 KB Clamp Type CP1201 Free Size 1946 MB A Range 200A Total Size 1946 MB V Range 200mV RS23...

Page 23: ...he screen will show NO File indicator in REC Date option when the selected file is new as screen 1 B The screen will show recording date and time in REC Date option when the selected file has been recorded as screen 2 screen 1 4 5 2 Folder Name WTA03 SETUP File Name 3P401001 XLS REC Date NO File Sampling Time 2 Trans Ref 220 0 V Delet File 0 SDVP 10 SD Format 0 Decimal Basic Use Size 388 KB Clamp ...

Page 24: ...t expect file number from 001 to 050 Remark When press or 2 sec the setting no will change fast 1P201001 1P2 means one phase by two wires 1P301001 1P3 means one phase by three wires 3P301001 3P3 means three phases by three wires 3P401001 3P4 means three phases by four wires HAR01001 HAR means harmonic measurement PHA01001 PHA means phasor measurement TRA01001 TRA means transient measurement Remark...

Page 25: ...ic 4 5 2 Use Size 388 KB Clamp Type CP1201 Free Size 1946 MB A Range 200A Total Size 1946 MB V Range 200mV RS232 Out Sel PT 1 1 V1 I1 P1 CT 1 1 S1 Q1 PF1 Beep ON Φ1 FREQ Year Month Date Hour Minute Second 2010 11 13 14 37 25 Folder Name WTA01 SETUP File Name 3P401001 XLS SHIFT 2 REC Date 2008 11 28 00 03 17 Sampling Time 2 Trans Ref 220 0 V screen 4 Delet File 0 SDVP 10 4 5 2 SD Format 0 Decimal B...

Page 26: ...SHIFT 1 REC Date 2008 11 28 00 03 17 Sampling Time 2 Trans Ref 220 0 V Delet File 0 SDVP 10 SD Format 0 Decimal Basic Use Size 388 KB Clamp Type CP1201 Free Size 1946 MB A Range 200A Total Size 1946 MB V Range 200mV RS232 Out Sel PT 1 1 V1 I1 P1 CT 1 1 S1 Q1 PF1 Beep ON Φ1 FREQ Year Month Date Hour Minute Second 2010 11 13 14 37 25 screen 2 4 5 3 Folder Name WTA01 SETUP File Name 3P401001 XLS REC ...

Page 27: ...n 1 or else press SETUP KEY in Y or N option to return to screen 1 B Press in screen 1 to enter next setting function Delete File SD Format screen 1 4 5 4 Folder Name WTA01 SETUP File Name 3P401001 XLS SHIFT 1 REC Date 2008 11 28 00 03 17 Sampling Time 2 Trans Ref 220 0 V Delete File 0 SDVP 10 SD Format 0 Decimal Basic Use Size 388 KB Clamp Type CP1201 Free Size 1946 MB A Range 200A Total Size 194...

Page 28: ...1 S1 Q1 PF1 Beep ON Φ1 FREQ Year Month Date Hour Minute Second 2010 11 13 14 37 25 4 5 5 SD Format Formatting function for SD CARD A The indicator Y or N will appear on right side display of the option while pressing SHIFT KEY continuously at least two seconds and press the display will show Y in highlight as screen 2 press SETUP KEY again to confirm to format SD CARD then return to screen 1 or el...

Page 29: ...V1 I1 P1 CT 1 1 S1 Q1 PF1 Beep ON Φ1 FREQ Year Month Date Hour Minute Second 2010 11 13 14 37 25 screen 2 4 5 5 Folder Name WTA01 SETUP File Name 3P401001 XLS SHIFT 1 REC Date 2008 11 28 00 03 17 Sampling Time 2 Trans Ref 220 0 V Delete File 0 SDVP 10 SD Format Y OR N Decimal Basic Use Size 388 KB Clamp Type CP1201 Free Size 1946 MB A Range 200A Total Size 1946 MB V Range 200mV RS232 Out Sel PT 1 ...

Page 30: ... once again will return to screen 1 then press to enter next setting function PT CT screen 1 4 5 6 Folder Name WTA01 SETUP File Name 3P401001 XLS SHIFT 1 REC Date 2008 11 28 00 03 17 Sampling Time 2 Trans Ref 220 0 V Delete File 0 SDVP 10 SD Format 0 Decimal Basic Use Size 388 KB Clamp Type CP1201 Free Size 1946 MB A Range 200A Total Size 1946 MB V Range 200mV RS232 Out Sel PT 1 1 V1 I1 P1 CT 1 1 ...

Page 31: ... Beep ON Φ1 FREQ Year Month Date Hour Minute Second 2010 11 13 14 37 25 4 5 7 CT Set the Current Transformer A When press SHIFT KEY once the symbol SHIFT1 will disappear as screen 2 at this time press or can adjust to expect CT values the adjusting numbers are from 1 to 600 Remark When press or 2 sec the setting no will change fast B Press SHIFT KEY once again will return to screen 1 then press to...

Page 32: ...PT 1 1 V1 I1 P1 CT 1 1 S1 Q1 PF1 Beep ON Φ1 FREQ Year Month Date Hour Minute Second 2010 11 13 14 37 25 screen 2 4 5 7 Folder Name WTA01 SETUP File Name 3P401001 XLS REC Date 2008 11 28 00 03 17 Sampling Time 2 Trans Ref 220 0 V Delete File 0 SDVP 10 SD Format 0 Decimal Basic Use Size 388 KB Clamp Type CP1201 Free Size 1946 MB A Range 200A Total Size 1946 MB V Range 200mV RS232 Out Sel PT 1 1 V1 I...

Page 33: ...next setting function BEEP Trans Ref type screen 1 4 5 8 Folder Name WTA01 SETUP File Name 3P401001 XLS SHIFT 1 REC Date 2008 11 28 00 03 17 Sampling Time 2 Trans Ref 220 0 V Delete File 0 SDVP 10 SD Format 0 Decimal Basic Use Size 388 KB Clamp Type CP1201 Free Size 1946 MB A Range 200A Total Size 1946 MB V Range 200mV RS232 Out Sel PT 1 1 V1 I1 P1 CT 1 1 S1 Q1 PF1 Beep ON Φ1 FREQ Year Month Date ...

Page 34: ...ze 1946 MB V Range 200mV RS232 Out Sel PT 1 1 V1 I1 P1 CT 1 1 S1 Q1 PF1 Beep ON Φ1 FREQ Year Month Date Hour Minute Second 2010 11 13 14 37 25 4 5 9 Trans Ref Nominal voltage for transient detection reference A When press SHIFT KEY once will disappear as screen 2 at this time press or to adjsut the voltage level to 50 0 V to 850 0 V B Press SHIFT KEY once again will return to screen 1 then press t...

Page 35: ...PT 1 1 V1 I1 P1 CT 1 1 S1 Q1 PF1 Beep ON Φ1 FREQ Year Month Date Hour Minute Second 2010 12 14 09 22 41 screen 2 4 5 9 Folder Name WTA01 SETUP File Name 3P401001 XLS REC Date NO File Sampling Time 2 Trans Ref 220 0 V Delete File 0 SDVP 10 SD Format 0 Decimal Basic Use Size 23 MB Clamp Type CP1201 Free Size 1904 MB A Range 200A Total Size 1927 MB V Range 200mV RS232 Out Sel PT 1 1 V1 I1 P1 CT 1 1 S...

Page 36: ...then press to enter next setting function SDVP Decimal screen 1 4 5 10 Folder Name WTA01 SETUP File Name 3P401026 XLS SHIFT 1 REC Date NO File Sampling Time 2 Trans Ref 220 0 V Delete File 0 SDVP 10 SD Format 0 Decimal Basic Use Size 23 MB Clamp Type CP1201 Free Size 1904 MB A Range 200A Total Size 1927 MB V Range 200mV RS232 Out Sel PT 1 1 V1 I1 P1 CT 1 1 S1 Q1 PF1 Beep ON Φ1 FREQ Year Month Date...

Page 37: ...FREQ Year Month Date Hour Minute Second 2010 12 14 09 22 41 4 5 11 Decimal Type set the Decimal type to Basic or Euro The numerical data structure of SD card is default used the as the decimal for example 20 6 1000 53 But in certain countries Europe is used the as the decimal point for example 20 6 1000 53 Under such situation it should change the Decimal character at first A When press SHIFT KEY ...

Page 38: ...en 1 then press to enter next setting function Decimal type Clamp type screen 1 4 5 11 Folder Name WTA01 SETUP File Name 3P401001 XLS SHIFT 1 REC Date 2008 11 28 00 03 17 Sampling Time 2 Trans Ref 220 0 V Delete File 0 SDVP 10 SD Format 0 Decimal Basic Use Size 388 KB Clamp Type CP1201 Free Size 1946 MB A Range 200A Total Size 1946 MB V Range 200mV RS232 Out Sel PT 1 1 V1 I1 P1 CT 1 1 S1 Q1 PF1 Be...

Page 39: ...ar Month Date Hour Minute Second 2010 11 13 14 37 25 4 5 12 Clamp Type set the clamp type to CyberVisuell Clamp or other Clamp A When press SHIFT KEY once the symbol SHIFT1 will be disappeared and show as screen 2 at this time press or to select the standard clamp or other Clamp LCP 200 LCP 1201 LCP 2000 LCP 3000 Other B When select the different Clamp type the V range and the A range will show th...

Page 40: ...PT 1 1 V1 I1 P1 CT 1 1 S1 Q1 PF1 Beep ON Φ1 FREQ Year Month Date Hour Minute Second 2010 11 13 14 37 25 screen 2 4 5 12 Folder Name WTA01 SETUP File Name 3P401001 XLS REC Date 2008 11 28 00 03 17 Sampling Time 2 Trans Ref 220 0 V Delete File 0 SDVP 10 SD Format 0 Decimal Basic Use Size 388 KB Clamp Type CP1201 Free Size 1946 MB A Range 200A Total Size 1946 MB V Range 200mV RS232 Out Sel PT 1 1 V1 ...

Page 41: ...0A 2000A 30A 300A 3000A Attention The meter s A range Current range value should same as the Clamp s current selecting range value B Press SHIFT KEY once again will return to screen 1 then press to enter next setting function A Range V range screen 1 4 5 13 Folder Name WTA01 SETUP File Name 3P401001 XLS SHIFT 1 REC Date 2008 11 28 00 03 17 Sampling Time 2 Trans Ref 220 0 V Delete File 0 SDVP 10 SD...

Page 42: ...REQ Year Month Date Hour Minute Second 2010 11 13 14 37 25 4 5 14 V range Setting Voltage range Setting A When press SHIFT KEY once the symbol SHIFT1 will be disappeared and show as screen 2 at this time press or to select V range to 200mV 300mV 500mV 1V 2V 3V The setting function only available for the Other clamp The V range value of CP 200 CP 1201 CP 2000 CP 3000 will dfault to 200mV it can not...

Page 43: ...PT 1 1 V1 I1 P1 CT 1 1 S1 Q1 PF1 Beep ON Φ1 FREQ Year Month Date Hour Minute Second 2010 11 13 14 37 25 screen 2 4 5 14 Folder Name WTA01 SETUP File Name 3P401001 XLS REC Date 2008 11 28 00 03 17 Sampling Time 2 Trans Ref 220 0 V Delete File 0 SDVP 10 SD Format 0 Decimal Basic Use Size 388 KB Clamp Type CP1201 Free Size 1946 MB A Range 200A Total Size 1946 MB V Range 200mV RS232 Out Sel PT 1 1 V1 ...

Page 44: ...or full as screen 6 D After the selecting is completed press SHIFT KEY continuously at least two seconds again will return to screen 1 and show all the selected items at the same time E Press in screen 1 to enter next setting function RS232 Out Sel Year screen 1 4 5 15 Folder Name WTA01 SETUP File Name 3P401001 XLS SHIFT 1 REC Date 2008 11 28 00 03 17 Sampling Time 2 Trans Ref 220 0 V Delete File ...

Page 45: ...8 Q1 29 Φ 3 8 I2 19 Q2 30 WH 9 I3 20 Q3 31 SH 10 P1 21 QΣ 32 QH 11 P2 22 PF1 33 FREQ screen 3 4 5 15 RS232 OUTPUT SELECT 34 H01 45 H12 56 H23 35 H02 46 H13 57 H24 36 H03 47 H14 58 H25 37 H04 48 H15 59 H26 38 H05 49 H16 60 H27 39 H06 50 H17 61 H28 40 H07 51 H18 62 H29 41 H08 52 H19 63 H30 42 H09 53 H20 64 H31 43 H11 54 H21 65 H32 44 H01 55 H22 66 H33 41 ...

Page 46: ...1 Φ V31 70 H37 81 H48 92 Φ V1 71 H38 82 H49 93 Φ V2 72 H39 83 H50 94 Φ V3 73 H40 84 THD 95 Φ A1 74 H41 85 Vpp 96 Φ A2 75 H42 86 CFV 97 Φ A3 76 H43 87 App 98 AveV 77 H44 88 CFA 99 AveA screen 5 4 5 15 RS232 OUTPUT SELECT 100 Vn 101 An 102 dV 103 VUR 104 Vd0 105 Vd2 106 dA 107 AUR 108 Ad0 109 Ad2 42 ...

Page 47: ...1 33 FREQ FULL 4 5 16 Year Month Date Hour Minute Second setting A When press SHIFT KEY once the symbol SHIFT1 will disappear as screen 2 at this time press or to adjust expect numbers and press or continuously at least two seconds can skip the numbers faster B Press in screen 1 to enter next setting function Year Month C The settings about Month Date Date Hour Hour Minute Minute Second are same a...

Page 48: ...ss setup key that will save setting value and also start counting function of second Folder Name WTA01 SETUP File Name 3P401001 XLS SHIFT 1 REC Date 2008 11 28 00 03 17 Sampling Time 2 Trans Ref 220 0 V screen 1 Delete File 0 SDVP 10 4 5 16 SD Format 0 Decimal Basic Use Size 388 KB Clamp Type CP1201 Free Size 1946 MB A Range 200A Total Size 1946 MB V Range 200mV RS232 Out Sel PT 1 1 V1 I1 P1 CT 1 ...

Page 49: ...REQ Year Month Date Hour Minute Second 2010 11 13 14 37 25 4 5 17 When all settings are completed press EXIT KEY to return measuring screen 4 5 18 The descriptions about SD CARD memory space A Use Size To show the space data numbers that have been used B Free Size To show the data numbers of balance space C Total Size To show the data numbers of total space D Typical SD CARD and SDHC both can be u...

Page 50: ...cted name of system will be appeared on bottom left display of screen 2 B 2 Connect the line voltage L1 Vn Neutral to V1 and N terminals of the instrument B 3 Place the conductor of CP 1201 A1 to A1 as screen 1 B 4 Connect the output of clamp meter CP 1200 A1 to A1 terminal of the instrument B 5 The related measuring factors will be appeared on display about the instruction of factor please refer ...

Page 51: ... A P 1 0 000KW P F 1 0 00 S 1 0 000KVA P F H 0 00 Q 1 0 000KVAR Φ 1 0 0 W H 0 000KWH S H 0 000KVAH Q H 0 000KVARH F R E Q 50 1 Hz CP1201 20A 1Φ2W SEC 2 CT 1 PT 1 5 2 1Φ3W one phase by three wires measurement A Diagram screen1 5 2 47 ...

Page 52: ...nd A2 as screen 1 B 4 Connect the outputs of clamp meter CP 1201 A1 CP 1201 A2 to A1 and A2 terminals of the instrument B 5 The related measuring factors will be appeared on display about the instruction of factor please refer appendix 1 5 16 page 68 screen 2 5 2 V 1 0 0 V P 1 0 000KW V 2 0 0 V P 2 0 000KW A 1 0 00 A S 1 0 000KVA A 2 0 00 A S 2 0 000KVA Q 1 0 000KVAR Q 2 0 000KVAR PΣ 0 000 KW SΣ 0...

Page 53: ...ttom left display of screen 2 B 2 Connect the line voltage L1 L2 and L3 to V1 V2 and V3 terminals of the instrument B 3 Place the conductor of CP 1201 A1 CP 1201 A2 CP 1201 A3 hook to A1 A2 A3 as screen 1 B 4 Connect the outputs of clamp meter CP 1201 A1 CP 1201 A2 CP 1201 A3 to A1 A2 A3 terminals of the instrument B 5 The related measuring factors will be appeared on display about the instruction...

Page 54: ... 0 00 A V 3 1 0 0 V A 3 0 00 A P Σ 0 000 KW S Σ 0 000 KVA Q Σ 0 000 KVAR PFΣ 0 00 P F H 0 00 WH 0 000 KWH SH 0 000 KVAH QH 0 000 KVARH FREQ 50 0 Hz CP1201 20A 3Φ3W SEC 2 CT 1 PT 1 5 4 3Φ4W three phases by four wires measurement A Diagram screen 1 5 4 50 ...

Page 55: ... meter CP 1201 A1 CP 1201 A2 CP 1201 A3 to A1 A2 A3 terminals of the instrument B 5 The related measuring factors will be appeared on display about the instruction of factor please refer appendix 1 5 16 page 68 screen 2 5 4 V12 0 0 V V1 0 0 V A1 0 00 A V23 0 0 V V2 0 0 V A2 0 00 A V31 0 0 V V3 0 0 V A3 0 00 A P1 0 000 KW S1 0 000 KVA Q1 0 000 KVAR P2 0 000 KW S2 0 000 KVA Q2 0 000 KVAR P3 0 000 KW...

Page 56: ...splay of screen 2 B 2 Connect the line voltage L1 L2 L3 and Vn to V1 V2 V3 and N terminals of the instrument B 3 Place the conductor of CP 1201 A1 CP 1201 A2 CP 1201 A3 hook to A1 A2 A3 as screen 1 B 4 Connect the outputs of clamp meter CP 1201 A1 CP 1201 A2 CP 1201 A3 to A1 A2 A3 terminals of the instrument B 5 The related measuring factors will be appeared on display about the instruction of fac...

Page 57: ...00 KW S3 0 000 KVA Q3 0 000 KVAR PΣ 0 000 KW SΣ 0 000 KVA QΣ 0 000 KVAR PF1 0 00 PF2 0 00 PF3 0 00 PFΣ 0 00 PFH 0 00 Φ1 0 0 Φ2 0 0 Φ3 0 0 WH 0 000 KWH SH 0 000 KVAH QH 0 000 KVARH FREQ 0 0 Hz CP1201 20A 3Φ4W SEC 2 CT 1 PT 1 5 6 ZERO adjustment for Watt Hour If reset the Exit key button 3 8 Fig 1 continuously and 6 seconds the measurement value of WH SH QH will reset to Zero value 53 ...

Page 58: ... the distortion Press V A range Key 3 28 Fig 1 switch to VH or AH to let the wave form not existing distortion as Screen 3 Screen 4 4 Press Left Key 3 24 Fig 1 or Right Key 3 26 Fig 1 will show the voltage or current Nth harmonic value Screen 1 5 7 Pk Pk 623 1 V CFV 1 414 V1 220 3 V L THD 1 5 HD1 100 0 220 3V 60Hz 2 8 CP1201 FREQ 59 9Hz 200A 3Φ4W SEC 2 CT 1 PT 2 54 ...

Page 59: ...A 1 414 A1 70 47 A L THD 5 5 HD1 100 0 70 47A 60Hz 1 8 CP1201 FREQ 59 9Hz 200A 3Φ4W SEC 2 CT 1 PT 2 Screen 3 5 7 Pk Pk 623 1 V CFV 1 414 V1 220 3 V H THD 1 7 HD1 100 0 220 5V 60Hz 1 9 CP1201 FREQ 59 9Hz 200A 3Φ4W SEC 2 CT 1 PT 2 55 ...

Page 60: ...the Screen 1 2 Description of phasor diagram a V1 V2 V3 Phase voltages in phasor format with respect to V1 A1 A2 A3 Line currents in phasor format with respect to A1 b AVE Average of the line voltages V12 V23 and V31 an the line current A1 A2 and A3 c AVn Calculated voltage and current of neutral with respect to ground d dV Historical maximum value of Max V1 V2 V3 Min V1 V2 V3 Min V1 V2 V3 100 e V...

Page 61: ...balance Ratio in d0 of voltage or current d2 The second number is the Negative Sequence Unbalance Ratio in d2 of voltage or current g dA Historical maximum value of Max A1 A2 A3 Min A1 A2 A3 Min A1 A2 A3 100 h AUR Current unbalance ratio Screen 1 5 8 57 ...

Page 62: ... to V2 V3 2 Press Waveform Key 3 31 Fig 1 once again will enter to Current Waveform screen as Screen 2 then 1Φ 3Φ Key 3 2 Fig 1 once in sequence will switch the Current waveform from A1 to A2 A3 3 Press Waveform Key 3 31 Fig 1 once again will enter to Voltage Current Waveform screen as Screen 3 then press 1Φ 3Φ Key 3 2 Fig 1 once in sequence will switch the Voltage Current waveform from V1 A1 to V...

Page 63: ...Screen 1 5 9 Screen 2 5 9 59 ...

Page 64: ... level at first the setting procedures please refere to chapter 4 5 9 and chapter 4 5 10 2 Press Transient Key 3 32 Fig 1 will enter to Transient Capture screen insert the SD memory card then press the REC Button 3 9 Fig 1 will make the measuremnt refer as the Screen 1 3 Definition a SWELL Vrms Vref Vref SDVP b DIP Vrms Vref Vref SDVP c OUTAGE Vrms 30 V to 40 V 60 ...

Page 65: ...ction as Screen 3 5 One screen can show 13 transient events One file can record 99 transient events When the transient even more than 13 no then press the Button Button can show more transient events If the transient events less than 13 no Button Button are disable Screen 1 5 10 Remark When press 1Φ 3Φ Button 3 2 Fig 1 once in insequence it can switch to the the transient measurement of different ...

Page 66: ...Screen 2 5 10 Screen 3 5 10 62 ...

Page 67: ... 0 000 KW S3 0 000 KVA Q3 0 000 KVAR PΣ 0 000 KW SΣ 0 000 KVA QΣ 0 000 KVAR PF1 0 00 PF2 0 00 PF3 0 00 PFΣ 0 00 PFH 0 00 Φ1 0 0 Φ2 0 0 Φ3 0 0 WH 0 000 KWH SH 0 000 KVAH QH 0 000 KVARH FREQ 0 0 Hz CP1201 Change 20A 3Φ4W SEC 2 CT 1 PT 1 Card B The bottom right display will show the recorded data points B 1 Each file can record up to 30 000 data points as screen 1 when the record points exceed 30 000...

Page 68: ...0 0 Φ3 0 0 WH 0 000 KWH SH 0 000 KVAH QH 0 000 KVARH FREQ 0 0 Hz CP1201 REC 20A 3Φ4W SEC 2 CT 1 PT 1 9 screen 2 5 11 B V12 0 0 V V1 0 0 V A1 0 00 A V23 0 0 V V2 0 0 V A2 0 00 A V31 0 0 V V3 0 0 V A3 0 00 A P1 0 000 KW S1 0 000 KVA Q1 0 000 KVAR P2 0 000 KW S2 0 000 KVA Q2 0 000 KVAR P3 0 000 KW S3 0 000 KVA Q3 0 000 KVAR PΣ 0 000 KW SΣ 0 000 KVA QΣ 0 000 KVAR PF1 0 00 PF2 0 00 PF3 0 00 PFΣ 0 00 PF...

Page 69: ...S3 0 000 KVA Q3 0 000 KVAR PΣ 0 000 KW SΣ 0 000 KVA QΣ 0 000 KVAR PF1 0 00 PF2 0 00 PF3 0 00 PFΣ 0 00 PFH 0 00 Φ1 0 0 Φ2 0 0 Φ3 0 0 WH 0 000 KWH SH 0 000 KVAH QH 0 000 KVARH FREQ 0 0 Hz CP1201 20A 3Φ4W SEC 2 CT 1 PT 1 HOLD screen 2 5 12 V12 0 0 V V1 0 0 V A1 0 00 A V23 0 0 V V2 0 0 V A2 0 00 A V31 0 0 V V3 0 0 V A3 0 00 A P1 0 000 KW S1 0 000 KVA Q1 0 000 KVAR P2 0 000 KW S2 0 000 KVA Q2 0 000 KVA...

Page 70: ...on 4 5 13 A range Setting Current range Setting page 37 Remark The function of the A Range Current Range key is available for the Clamp Type A Range V Range setting only screen 1 5 14 same as screen 2 4 5 13 Folder Name WTA01 SETUP File Name 3P401001 XLS REC Date 2008 11 28 00 03 17 Sampling Time 2 Trans Ref 220 0 V Delete File 0 SDVP 0 SD Format 0 Decimal Basic Use Size 388 KB Clamp Type CP1201 F...

Page 71: ...0 0 V V3 0 0 V A3 0 00 A P1 0 000 KW S1 0 000 KVA Q1 0 000 KVAR P2 0 000 KW S2 0 000 KVA Q2 0 000 KVAR P3 0 000 KW S3 0 000 KVA Q3 0 000 KVAR PΣ 0 000 KW SΣ 0 000 KVA QΣ 0 000 KVAR PF1 0 00 PF2 0 00 PF3 0 00 PFΣ 0 00 PFH 0 00 Φ1 0 0 Φ2 0 0 Φ3 0 0 WH 0 000 KWH SH 0 000 KVAH QH 0 000 KVARH FREQ 0 0 Hz CP1201 LOWBAT 20A 3Φ4W SEC 2 CT 1 PT 1 67 ...

Page 72: ...wer VA QΣ Total Reactive Power VAR PF1 PF2 PF3 Power Factor of each phase PFΣ Total Power Factor PFH Long Term Average Power Factor WH SH Φ 1 Φ 2 Φ 3 Phase Angle of each phase WH Watt Hour SH Apparent Power Hour QH Reactive Power Hour 1Φ 2W One phase by two wires 1Φ 3W One phase by three wires 3Φ 3W Three phases by three wires 3Φ 4W Three phases by four wires SEC The sampling time of data logger C...

Page 73: ... 1 When Display show the LOWBAT indicator ref 5 15 page 67 it should change the batteries 2 open the Battery Cover 3 19 Fig 1 away from the instrument and remove the battery 3 Replace with batteries DC 1 5V AA UM 3 battery X 8 PCs and reinstate the cover When install the batteries should make attention the battery polarity 4 Make sure the battery cover is secured after changing the batteries 69 ...

Page 74: ...can be utilized to the user s specific application A RS232 lead with the following connection will be required to link the instrument with the PC serial input Meter PC 3 5 mm jack plug 9W D Connector Center Pin Pin 4 Ground shield Pin 2 2 2 K resister Pin 5 The 16 digits data stream will be displayed in the following format D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0 70 ...

Page 75: ...TVA D6 TVA Hr 65 KW HR C6 KVAR D7 KVAR Hr B6 KACV C7 MVAR D8 MVAR Hr B7 MACV C8 GVAR D9 GVAR Hr B8 KACA C9 TVAR E0 TVAR Hr D10 Polarity 0 Positive 1 Negative D9 Decimal Point DP position from right to the left 0 No DP 1 1 DP 2 2 DP 3 3 DP D8 to D1 Display reading D1 LSD D8 MSD For example If the display reading is 1234 then D8 to D1 is 00001234 D0 End Word RS232 setting Baud rate 9600 Parity No pa...

Page 76: ...d into the SD card adapter then connect the SD card adapter into the computer 3 Power ON the computer and run the EXCEL software Down load the saving data file for example the file name 3P401001 XLS 1P201001 XLS 1P301001 XLS 3P301001 XLS from the SD card to the computer The saving data will present into the EXCEL software screen for example as following EXCEL data screens then user can use those E...

Page 77: ...EXCEL data screen 2 for example EXCEL data screen 3 for example EXCEL data screen 4 for example 73 ...

Page 78: ...EXCEL data screen 5 for example EXCEL data screen 6 for example EXCEL graphic screen 1 for example 74 ...

Page 79: ...EXCEL graphic screen 2 for example EXCEL graphic screen 3 for example 75 ...

Page 80: ...EXCEL graphic screen 4 for example EXCEL graphic screen 5 for example 9 PATENT The meter SD card structure already get patent or patent pending in following countries 76 USA China Germany Japan Taiwan ...

Page 81: ... power consumption can be monitored This usually means the currents should be drawn from a single power source the transformer Question If it can do this what settings should be used ie 3P4W or 1P3W etc Answer 3P4W R N A1 S N A2 T N A3 Question Also I don t understand what the 1P3W setting is for the user manual only seems to show it monitoring 2 circuits can you please explain how this is to be u...

Page 82: ...970 M 359043 CHINA ZL 2008 2 0189918 5 ZL 2008 2 0189917 0 USA Patent pending 10 THE ADDRESS OF AFTER SERVICE CENTER 77 1106 LDW6095 1012 LDW6095 www esis com au Ph 02 9481 7420 Fax 02 9481 7267 esis enq esis com au Distributed and supported in Australia by ...