Instruction for use

Safety system protects human life and material assets!

Once a year functional testing by a specialist company authorized by the manufacturer.

Connection, mounting and functional testing by a

specialist company authorized by the manufacturer.

Green control diodes in the buttons must constantly be on,

otherwise see "Information for Starting".

Repair power failure at once. Emergency power supply for 72 hours.

Smoke vent button control panel RZN 4503-T

There are

guarantee for all D+H products from date of verified handing over of the system

up to maximal 3 years after date of delivery, when mounting and starting has been carried out by a
D+H authorized

D+H guarantee is expired in case of connection of D+H components with external systems or
with mixing of D+H products with parts of other manufacturers.

2 years

distributor.

Guarantee

Summary of Contents for RZN 4503-T

Page 1: ...nnection mounting and functional testing by a specialist company authorized by the manufacturer Green control diodes in the buttons must constantly be on otherwise see Information for Starting Repair...

Page 2: ...After the maintenance time is expired ca 14 to 16 months the ventilation function OPEN can be interrupted depending on the presetting of the service timer Reset can be carried out by a specialist comp...

Page 3: ...ensation for damage Therefore regular maintenance and checking of functional readiness is imperative and must be ensured These standard requirements are demanded in accordance with regulations of the...

Page 4: ...t function CLOSE Fault Charging voltage controller Battery LED system O K DIP switch factory set see p 9 and 11 LED mains LED alarm LED group fault LED battery fault LED earthfault Reset line LED line...

Page 5: ...BZUG RAUCHABZUG RZN RT 4 click 1 2 4 RAUCHABZUG RAUCHABZUG 3 RZN RT RZN 4503 T Operation Release in case of alarm Manual opening by smoke vent button Automatic opening by fire detector o r a n d Autom...

Page 6: ...With manual release Opening the housing RZN RT with supplied key Automatic opening by external control see DIP switch S1 page 8 hold for OFF shortly tap for ON 3 s o r o r function is deactivatable b...

Page 7: ...rtner com Service 12 month 12 month RAUCHABZUG www dh partner com Service 12 month 12 month In case of power failure Emergency closing In case of non resettable alarm hold for OFF 3 s see DIP switch S...

Page 8: ...and the smoke vent opens e g at an interrupted button line or missing terminal resistor In case of a group fault the control panel will be switched to alarm and the smoke vent opens e g in case of an...

Page 9: ...tor fault line fault group fault power failure earth fault passing on of central CLOSE ResetAlarm as pulse group closed longer x s Charge temperature guided Monitoring presence final discharging volta...

Page 10: ...y stage of fire Protected wiring is required with protection against mechanical damages according to DIN 18232 section 2 5 5 paragraph 4 Cable from the smoke vent control panel to connection of drive...

Page 11: ...ives smoke vent buttons if necessary fire detectors and vent buttons See wiring and connection plans Mounting and Installation Set DIP switch S1 on motherboard as follows Resistor must be cramped in e...

Page 12: ...detector individual by D H smoke detector tester as an alternative by cigarette smoke response delay circa 20 s Red display diode must be on Smoke vent must open For closing wait until there is no mo...

Page 13: ...meldezentrale Contact external control e g fire alarm system JY St Y 4x2x0 6 JY St Y 4x2x0 6 JY St Y 2x2x0 6 Zentrale RZN Aufputz 230VAC 24VDC in der N he der RWA Klappe Control panel RZN surface type...

Page 14: ...cht eingesetzt werden The resistor must not be used when line connections with 2 detector dependency are employed N N A K S Unterbrechertaster Interrupter button Haftmagnet Magnetic clamp Haftmagnete...