ACTIVE DRIVER 

 
 

 

 
 
 
 

 
 
 
 
 
 
 
 

 

INTRODUCTION 

 

The DAB ACTIVE DRIVER is an innovative integrated pump control system that utilizes a 
variable frequency drive controller (VFD) to provide CONSTANT PRESSUE regardless of the 
demand flow requirements. 
 

>Applications 

 

The DAB ACTIVE DRIVER will fit to most DAB domestic pump, specifically Jet, JINOX, JECOM, 
EURO, EUROINOX, EUROCOM, K Series and KVCX Vertical Multistage. 
 
The unit is available if the following configurations, 
 

ACTIVE DRIVER M/M 1.1  

Suits single phase 230v power supply, and will couple to single phase pump units up to 
1.1kW, and is programmable to a maximum pressure of 6 Bar (600kPa), not exceed a 
flow of 300lpm. 
 

ACTIVE DRIVER M/T 1.0  

Suits single phase 230v power supply, and will couple to three phase pump units up to 
1.0kW, and is programmable to a maximum pressure of 9 Bar (900kPa), not exceed a 
flow of 300lpm. 
 

ACTIVE DRIVER M/T 2.2  

Suits single phase 230v power supply, and will couple to three phase pump units up to 
2.2kW, and is programmable to a maximum pressure of 9 Bar (600kPa), not exceed a 
flow of 300lpm. 

 

 
 
 

 

 

I

NVERTER 

CONTROLLED

 

Summary of Contents for ACTIVE DRIVER M/M 1.1

Page 1: ...configurations ACTIVE DRIVER M M 1 1 Suits single phase 230v power supply and will couple to single phase pump units up to 1 1kW and is programmable to a maximum pressure of 6 Bar 600kPa not exceed a...

Page 2: ...ting a set point of 350kPa will mean that the pump will normally run at lower frequency speed and less likely to cavitate Installing the ACTIVE DRIVER The ACTIVE DRIVER would normally be installed in...

Page 3: ...stem is required to run at This is inputted in Bar The rated current of the pump can be located on the compliance plate attached to the pump or is listed in the DAB Factory catalogue in the ELECTRICAL...

Page 4: ...the back of this guide Displays of the Main Values It is also possible to access operational information of the system by pressing the mode key these indications are Fr Displays the current frequency...

Page 5: ...e desired operating pressure of the system To access this setting press mode and set simultaneously for two seconds the display should indicate SP and then flash to 3 0 which is the pre set of 3 0 Bar...

Page 6: ...e system Go or Sb od OPERATING MODE this refers to the presence of a pressure cell To access this setting press mode set and simultaneously for five seconds press mode until the display indicates od a...

Page 7: ...or Sb Eb ENABLING THE BOOSTER turn the alternating function on in a multiple pumps system Not applicable to the AD M M 1 1 To access this setting press mode set and simultaneously for five seconds pre...

Page 8: ...8 Programming Resetting Factory Settings It is possible to restore the default settings by pressing set an for two seconds whilst restoring the power supply switching on...

Page 9: ...9 Programming Quick Set Up The following is a quick set up procedure for basic operation for all settable parameters refer to the complete input list on the last page...