background image

Manufactured under license of 

Daewoo International Corporation

, Korea

www.daewoopowerproducts.com

USER’S MANUAL

DAGFS-

15AC

Silent diesel generator

Summary of Contents for DAGFS-15AC

Page 1: ...Manufactured under license of Daewoo International Corporation Korea www daewoopowerproducts com USER S MANUAL DAGFS 15AC Silent diesel generator...

Page 2: ...1 1 OPERATION 2 2 MAINTENANCE 9 3 TROUBLE SHOOTING AND REMEDY 11 4 INSTRUCTION FOR CONTROL PANEL FUNCTION AND OPERATION MANUAL 12 5 TECHNICAL DATA 14 6 WARRANTY 15 INDEX...

Page 3: ...f exhaust gas For avoiding exhaust gas sucked by the person the diesel generator will be not allowed to work under condition of worse ventilation because exhaust gas emitted from the engine includes h...

Page 4: ...harging REMARK It is not permitted to smoke or make the spark when filling in or at fuel storage During adding the fuel overflowing should be prevented After completion of filling oil should firmly re...

Page 5: ...antly So the generating set life will be shortened We recommend CC CD oil classified by API Choose the applicable viscosity oil according to the local ambient temperature Interval for changing lube oi...

Page 6: ...per to take out the cover of air cleaner for getting the element shown in Fig 2 5 Remark 1 It is forbidden to clean the element with detergent 2 When output power drops or exhaust gas is black should...

Page 7: ...d correctly to prevent the shock by electricity The fuel and lube oil have been removed prior to delivery When filling in the fuel should check whether there is the air in the piping before starting I...

Page 8: ...ause the motor to be blocked During the operation let the key be in ON position 6 If the control panel is intelligent type also please refer to its manual When it is difficult to start the engine in c...

Page 9: ...ncy and power will be lower than rated limit shown in 1 1Main technical specification and data C When voltage indicating on control panel reaches 10 of rated limit can add the load D Following table s...

Page 10: ...on of the generator is of better ventilation because engine exhaust includes harmful CO After stopping the generator clean it immediately to prevent the corrosion and to remove the sediment interva l...

Page 11: ...due to charging and discharging continuously Check the accumulator before starting The distillatory water can be added to stipulated limit if necessary If the accumulator is damaged exchange it in ti...

Page 12: ...Set control rod to RUN position Check lube oil lever The level between upper mark H and lower mark L Dirt on the nozzle Clean the nozzle No electricity in accumulator Charge or change the accumulator...

Page 13: ...starter key from OFF to ON position to power on the controller then change the starter key position to START to begin cranking after the engine fires release the starter key and voltage power and fre...

Page 14: ...ad to shut down AUTO PROTECTION In auto protection mode except for low oil pressure protection all the other protections volta ge frequency overload temperature are active 1 Voltage protection When th...

Page 15: ...is running If battery voltage value is lower than 8V or higher than 16 5V LED display or indicator starts flashing butshutdown protection is not initiated NOTE During Safety On delay protection is di...

Page 16: ...LTD are complying the rules of Machinery Directive EN 60204 1 2018 EN ISO 12100 2010 EN ISO 8528 13 2016EN 55012 2007 A1 2009 EN IC 61000 3 2 2019 EN 61000 3 3 2013 A1 2019 EN 55012 2007 A 1 2009 The...

Page 17: ...ngs Also the warranty does not cover failure of the automatic voltage regulator due to incorrect operation Failure caused by clogging of the fuel and cooling systems Wearing parts carbon brushes belts...

Page 18: ...www daewoopowerproducts com Manufactured under license of Daewoo International Corporation Korea...