Service Instructions

RSD6621010

July 2021

Copyright © 2021 

Only personnel that have been trained to install, adjust, 

service or repair(hereinafter, “service”) the equipment 

specified in this manual should service the equipment.  The 

manufacturer will not be responsible for any injury or 

property damage arising from improper service or service 

procedures.  If you service this unit, you assume responsi

-

bility for any injury or property damage which may re

-

sult.  In addition, in jurisdictions that require one or more 

licenses to service the equipment specified in this manual, 

only licensed personnel should service the equipment.  

Improper installation, adjustment, servicing or repair of 

the equipment specified in this manual, or attempting to 

install, adjust, service or repair the equipment specified in 

this manual without proper training may result in product 

damage, property damage, personal injury or death.

WARNING

Daikin 80% Single Stage Gas Furnaces 

DM80SN, DC80SN 

& Accessories

This manual is to be used by qualified, professionally trained 

HVAC technicians only. 

Daikin does not assume any responsibility for property dam

-

age or personal injury due to improper service procedures or 

services performed by an unqualified person. 

The material in this manual does not supersede manufactur

-

ers installation and operation instructions.  

Summary of Contents for DM80SN

Page 1: ...anual only licensed personnel should service the equipment Improper installation adjustment servicing or repair of the equipment specified in this manual or attempting to install adjust service or rep...

Page 2: ...EVIEW ALL SERVICE INFORMATION IN THE APPROPRIATE SERVICE MANUAL BEFORE BEGINNING REPAIRS IMPORTANT NOTICES RECOGNIZE SAFETY SYMBOLS WORDS AND LABELS WARNING This unit should not be connected to or use...

Page 3: ...Installation and service must be performed by a qualified installer service agency or the gas supplier IMPORTANT INFORMATION WARNING Should overheating occur or the gas supply fail to shut off turn of...

Page 4: ...rcular a trav s del aparato cuando se opera en cualquier modo B10259 216 CO can cause serious illness including permanent brain damage or death B10259 216 RISQUE D EMPOISONNEMENT AU MONOXYDE DE CARBON...

Page 5: ...itial Release B 1st Revision Configuration M Upflow Horizontal Major Revision C Downflow Horizontal A Initial Release B 1st Revision Nox AFUE 80 80 AFUE 92 92 AFUE 96 96 AFUE 97 97 AFUE Cabinet Width...

Page 6: ...cause death or serious illness and which are known to the state of California to cause cancer birth defects or other reproductive harm This product contains fiberglass insulation Fiberglass insulatio...

Page 7: ...grounded object Product Application This product is designed for use as a residential home gas furnace It is not designed or certified for use in mobile home trailer or recreational vehicle applicatio...

Page 8: ...ating Inlet gas supply pressures must be maintained within the ranges specified below The supply pressure must be con stant and available with all other household gas fired appli ances operating The m...

Page 9: ...ted beside the low voltage thermostat connection strip Twinning allows simultaneous operation of two furnaces and forces the indoor blower motors of each furnace to oper ate synchronously into a commo...

Page 10: ...is is a 24 volt circuit only the common con nection must be on C terminal of the low voltage terminal strip where thermostat wires are con nected Wiring for this circuit must NOT be con nected to the...

Page 11: ...s the available speeds for Low High heat mode 3 When the center switch is pressed the current displayed speed shall be selected and control shall apply the newly selected speed in next heating call NO...

Page 12: ...rtment door and move the furnace gas valve manual control to the OFF position 3 Close the manual gas shutoff valve external to the furnace 4 Replace the burner compartment door Filters Filters must be...

Page 13: ...e then should be wired to the furnace accordingly CHECKING FOR PHASING PRIMARY TO SECONDARY OF UNMARKED TRANSFORMERS VOLT OHM METER G ND PRIMARY SECONDARY TRANSFORMER R C METER READS 24 VOLTS LINE VOL...

Page 14: ...ormance Filters should be cleaned permanent or replaced disposable every two months or as required It is the owner s responsibility to keep air filters clean When replacing a filter it must be replace...

Page 15: ...the unit adjust the gas valve pressure regulator or resize orifices CAUTION Always connect a manometer to the outlet tap at the gas valve before adjusting the pressure regulator In no case should the...

Page 16: ...79 947 45 20 40 80 160 400 20 45 90 180 360 900 46 78 157 391 21 43 86 171 343 857 47 19 38 76 153 383 22 41 82 164 327 818 48 75 150 375 23 39 78 157 313 783 49 147 367 24 37 75 150 300 750 50 18 36...

Page 17: ...CHECKING AUXILIARY LIMIT CONTROL 22 S 302 CHECKING FLAME ROLLOUT CONTROL 22 S 303 INDUCED DRAFT BLOWER MOTOR 23 S 304 CHECKING GAS VALVE REDUNDANT 23 S 305 CHECKING MAIN BURNERS 24 S 306 CHECKING ORI...

Page 18: ...ced replace with AWM 105 C 2 64 thick insulation of the same gauge or its equivalent CHECKING THERMOSTAT WIRING AND ANTICIPATOR S 3A THERMOSTAT AND WIRING WARNING Disconnect ALL power before servicing...

Page 19: ...r completing check and or replacement of trans former and check and or repair of control circuit reinstall blower compartment door 8 Turn on electrical power and verify proper unit operation S 16 CHEC...

Page 20: ...es for the quantity of air If the total external static pressure exceeds the minimum or maximum allowable statics check for closed dampers reg isters undersized and or oversized poorly laid out duct w...

Page 21: ...0 CHECKING PRIMARY LIMIT CONTROL All use a nonadjustable automatic reset bi metal type limit control Refer to the following drawing for the location of the primary limit Location of Primary Limit Prim...

Page 22: ...sonal injury or death VOLT OHM METER RED RESET BUTTON COLOR IDENTIFYING TAB Testing Auxiliary Limit Control WARNING To avoid possible fire only reset the auxiliary limit control once If it should open...

Page 23: ...regulation and 100 percent safety shut off WARNING Disconnect ALL power before servicing Single stage gas valves should be tested on the furnace with 24 VAC connected to the gas valve and manometers r...

Page 24: ...er to prevent distortion In no instance should an orifice be peened over and redrilled This will change the angle or deflection of the vacuum effect or entraining of primary air which will make it dif...

Page 25: ...er before servicing or in stalling this unit Multiple power sources may be present Failure to do so may cause proper ty damage personal injury or death 5 Disconnect manometer after turning off gas at...

Page 26: ...ve the outlet pressure boss plug Install an 1 8 NPT hose barb fitting into the outlet pressure tap b Attach a hose and manometer to the outlet pres sure barb fitting c Turn ON the gas supply d Turn on...

Page 27: ...rature the igniter ohm reading should be from 37 68 ohms S 309 CHECKING FOR FLASHBACK Flashback will also cause burning in the burner venturi but is caused by the burning speed being greater than the...

Page 28: ...SI Z223 1 and information provided by the gas supplier to determine the proper orifice size S 312 CHECKING FOR DELAYED IGNITION Delayed ignition is a delay in lighting a combustible mixture of gas and...

Page 29: ...out The following drawings illustrate from a bottom view the ap proximate distances for the ignitor and flame sensor to the gas in shot burner You will note they are in the main burner stream not in t...

Page 30: ...80SN0803B 0 70 0 06 0 85 0130F00505 DM80SN0804B 0 70 0 06 0 85 0130F00505 DM80SN0805C 0 75 0 07 0 90 0130F00506 DM80SN1005C 0 70 0 06 0 85 0130F00505 DM80SN1205D 0 80 0 05 0 95 0130F00507 DC80SN0403A...

Page 31: ...67 315 N A F02 1141 1089 1045 1001 958 914 869 823 F03 1311 1267 1226 1189 1150 1114 1072 1034 F04 1395 1347 1309 1270 1233 1199 1164 1125 F05 1490 1447 1407 1373 1336 1303 1269 1237 F06 1553 1510 146...

Page 32: ...22 439 367 315 N A F02 1141 1089 1045 1001 958 914 869 823 F03 1311 1267 1226 1189 1150 1114 1072 1034 F04 1395 1347 1309 1270 1233 1199 1164 1125 F05 1490 1447 1407 1373 1336 1303 1269 1237 F06 1553...

Page 33: ...F01 841 657 595 522 439 367 315 N A F02 1141 1089 1045 1001 958 914 869 823 F03 1311 1267 1226 1189 1150 1114 1072 1034 F04 1395 1347 1309 1270 1233 1199 1164 1125 F05 1490 1447 1407 1373 1336 1303 12...

Page 34: ...2 1141 52 1089 54 1045 57 1001 59 958 62 914 869 823 F03 1311 45 1267 47 1226 48 1189 50 1150 52 1114 1072 1034 F04 1395 42 1347 44 1309 45 1270 47 1233 48 1199 1164 1125 F01 837 N A 752 N A 671 N A 5...

Page 35: ...62 1233 1207 F01 760 697 636 569 481 402 349 300 F02 1286 1238 1196 1157 1117 1077 1036 998 F03 1393 1348 1308 1270 1230 1196 1158 1123 F04 1459 1414 1371 1336 1297 1264 1229 1193 F05 1753 1713 1677 1...

Page 36: ...1262 1233 1207 F01 760 697 636 569 481 402 349 300 F02 1286 1238 1196 1157 1117 1077 1036 998 F03 1393 1348 1308 1270 1230 1196 1158 1123 F04 1459 1414 1371 1336 1297 1264 1229 1193 F05 1753 1713 167...

Page 37: ...1348 1318 1289 1262 1233 1207 F01 760 697 636 569 481 402 349 300 F02 1286 1238 1196 1157 1117 1077 1036 998 F03 1393 1348 1308 1270 1230 1196 1158 1123 F04 1459 1414 1371 1336 1297 1264 1229 1193 F0...

Page 38: ...A 697 N A 636 N A 569 N A 481 N A 402 349 300 F02 1286 46 1238 48 1196 50 1157 51 1117 53 1077 1036 998 F03 1393 43 1348 44 1308 45 1270 47 1230 48 1196 1158 1123 F04 1459 41 1414 42 1371 43 1336 44 1...

Page 39: ...set at 7 Secs Adjustments can be made in 7 Secs increments from0 to 35 Secs Cool Off Delay Delay Seconds Default set at 65 Secs Adjustments can be made in 5 Secs increments from 0 to 120 Secs Blower...

Page 40: ...1 STAGE STATUS CODES 40 Idle Continous Fan F Compressor Cooling Low Stage Compressor Cooling High Stage Gas heat Single Stage Control OEM test Mode Mode Main Menu STATUS MENU...

Page 41: ...ulator blower motor Correct speed or replace blower motor if necessary Loose or improperly connected wiring in high limit circuit Tighten or correct wiring connection Flame sensed with no call for hea...

Page 42: ...ontrol module Blown fuse or tripped circuit breaker Correct condition which caused fuse to open replace fuse Integrated control module is non functional Replace non functional integrated control modul...

Page 43: ...PERATURE RATING OF AT LEAST 105v C USE COPPER CONDUCTORS ONLY 4 UNIT MUST BE PERMANENTLY GROUNDED AND CONFORM TO N E C AND LOCAL CODES 5 TO RECALL THE LAST 6 FAULTS MOST RECENT TO LEAST RECENT DEPRESS...

Page 44: ...is very interested in all product comments Please fill out the feedback form on the following link https daikincomfort com contact us You can also scan the QR code on the right to be directed to the f...