Phone: (855) 770-5678 | http://www.daikinac.com 

4008862 

WIRED THERMOSTAT 

 

Color graphic interface with capacitive screen for controlling zones in DZK systems. 
Powered by Main Control Board. Finished in steel and glass. 
 
Functionalities: 

 

Available languages:  English, French and Spanish. 

 

Control of set point temperature. Displayed in 1ºF/0.5ºC increments. 

 

Configurable set point range for Cooling and Heating. 

 

Auto changeover mode can automatically change to cool/heat mode at set 
point ±1ºF/0.5ºC (can be configured from 0 to 7ºF using field settings) with a 
guard timer of 15, 30, 60 or 90 minutes. 

 

Room temperature and relative humidity measurement of the zone. 

 

Operation mode, user mode and airflow control 

(Only Main Wired Thermostat)

 

Timer function. 

 

Time schedules programming. 

 

Remote access to other zones of the system. 

 

Configurable as Main or Zone thermostat. 

 

 

DZK-MTS-3

 

 
 

 

 

 

 
 

 

 

Rev. 1.00 

10-2016 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 

TECHNICAL SPECS 

 

Power supply and consumption 

Type of power supply 

Vdc 

V max 

12 V supplied from the Main Control Board 

I max 

145 mA 

Stand-by consumption 

0.876 W 

Connection and communications 

Shielded twisted pair   AWG 20 – 4 wired 

Maximum wiring length 

(Control board to thermostat) 

130 ft (40 m) 

Operating temperatures 

Storage

 

-4 to 158ºF (-20 to 70 ºC) 

Operation 

32 to 122ºF (0 to 50ºC) 

Operating humidity range   5 to 90% (non-condensing) 

Set-point temperature range 

59 to 86ºF (15 to 30ºC) 

Reading accuracy 

±1ºF (±0.5 ºC) 

Display accuracy 

±1ºF (±0.5 ºC) 

Relative humidity 

±4 % 

Mechanical aspects 

Assembly   Surface through support 

Protection class 

IP 20 

Type of probe 

Airzone_NTC_10K 

Weight (Mass) 

0.44 lb (198 g) 

Dimensions (WxHxD) 

3.62x3.62x0.62 inch (92x 92x15.85 mm) 

 
 

D

 

H

 

W

 

Reviews: