Phone: (855) 770-5678 | http://www.daikinac.com
4008862
WIRED THERMOSTAT
Color graphic interface with capacitive screen for controlling zones in DZK systems.
Powered by Main Control Board. Finished in steel and glass.
Functionalities:
•
Available languages: English, French and Spanish.
•
Control of set point temperature. Displayed in 1ºF/0.5ºC increments.
•
Configurable set point range for Cooling and Heating.
•
Auto changeover mode can automatically change to cool/heat mode at set
point ±1ºF/0.5ºC (can be configured from 0 to 7ºF using field settings) with a
guard timer of 15, 30, 60 or 90 minutes.
•
Room temperature and relative humidity measurement of the zone.
•
Operation mode, user mode and airflow control
(Only Main Wired Thermostat)
.
•
Timer function.
•
Time schedules programming.
•
Remote access to other zones of the system.
•
Configurable as Main or Zone thermostat.
DZK-MTS-3
Rev. 1.00
10-2016
TECHNICAL SPECS
Power supply and consumption
Type of power supply
Vdc
V max
12 V supplied from the Main Control Board
I max
145 mA
Stand-by consumption
0.876 W
Connection and communications
Shielded twisted pair AWG 20 – 4 wired
Maximum wiring length
(Control board to thermostat)
130 ft (40 m)
Operating temperatures
Storage
-4 to 158ºF (-20 to 70 ºC)
Operation
32 to 122ºF (0 to 50ºC)
Operating humidity range 5 to 90% (non-condensing)
Set-point temperature range
59 to 86ºF (15 to 30ºC)
Reading accuracy
±1ºF (±0.5 ºC)
Display accuracy
±1ºF (±0.5 ºC)
Relative humidity
±4 %
Mechanical aspects
Assembly Surface through support
Protection class
IP 20
Type of probe
Airzone_NTC_10K
Weight (Mass)
0.44 lb (198 g)
Dimensions (WxHxD)
3.62x3.62x0.62 inch (92x 92x15.85 mm)
D
H
W