background image

 

 
 
 

Intelligent Touch Manager 

BACnet® Server Gateway 

DCM014A51 

 

QUICK USER GUIDE 

 

 

 

UGUS_DCM014A51_03-17 

Summary of Contents for intelligent Touch Manager BACnet DCM014A51

Page 1: ...Intelligent Touch Manager BACnet Server Gateway DCM014A51 QUICK USER GUIDE UGUS_DCM014A51_03 17...

Page 2: ...Points List 6 5 1 iTM System Points List 6 5 2 Indoor Unit Points List 6 6 Programming Notes 9 6 1 iTM Control Logic and The Related BACnet Points 9 6 2 Setpoints 9 6 3 Auto changeover 9 6 4 Setpoints...

Page 3: ...l of the VRV system except for individual indoor unit and controls configurations 2 Types of Daikin VRV Systems The VRV system can consist of Heat Recovery systems Heat Pump systems or a system that i...

Page 4: ...5 2 00 to 2 15 3 00 to 3 15 and 4 00 to 4 15 A remote control group consists of 1 to 16 indoor units daisy chained together via P1P2 connections The unit is used to identify the indoor unit within a g...

Page 5: ...ored through the iTM BACnet Server Gateway 3 Up to 7 additional DIII Net communication systems can be added with the optional iTM Plus Adaptors 4 The iTM BACnet Server Gateway support change of value...

Page 6: ...wing are indoor unit control and monitoring points Each indoor unit group shall have one set of these points Refer to iTM BACnet Server Design Guide Part 2 for point description Instance No Object_Nam...

Page 7: ...us BI Off On 26 Communication Status BI Normal Alarm 27 Thermo on Status BI Off On 28 Compressor Status MI Off On Defrost Hot Start 29 Aux Heater Status BI Off On 30 Forced Thermo off BV Disable Enabl...

Page 8: ...bled therefore a value set on the indoor unit management point remains unchanged even if Present_Value is changed 4 The Out_Of_Service property of Max Cooling Setpoint and Min Cooling Setpoint indicat...

Page 9: ...he BMS are also updated in the iTM and setpoints set at the iTM are updated to the BMS The Unoccupied setpoint can be set via the schedule iTM or BMS or manually from the iTM or BMS The setback should...

Page 10: ...oor unit When the timed override function is enabled for an indoor unit group the units will be turned off automatically after the preset timer has expired if the unit is turned on during the unoccupi...

Page 11: ...ver The iTM BACnet Server updates the PV and reset the 10 min timer 4 If the value in Management Point is not changed which means the indoor unit did not accept the new value and failed to update the...

Page 12: ...No change 3 When 10 min timer expires PV back to 70 F EXAMPLE 3 Operation mode to Changeover slave unit Step BMS BACnet Server in ITM Management Point in ITM Indoor Unit Pre condition Operation mode...

Page 13: ...management points in the iTM are monitored and controlled by the BMS without additional hardware devices The iTM Auto Changeover Setpoint Range Limit Setback Dual Setpoint logic and Schedule control...

Page 14: ...ions and with the instructions in this installation manual Improper installation may cause electric shock or fire Only use specified accessories and parts for installation Failure to use specified par...

Reviews: