Thank you for purchasing our smoke 
alarm. Please take a few minutes to 
read the user’s manual thoroughly 
and familiarize yourself and your 
family with its operation. And save it 
for future reference.

SPECIFICATIONS

P

ower: 

built-in DC 3V(CR123A) Lithium battery

            (battery not replaceable)

Alarm Volume: 

>85dB (A) at 3 meters

Alarm Sensitivity: 

0.10-0.16dB /m

SILENCE TIME:

 approx. 8 minutes

Comply With: 

EN14604:2005/AC: 2008

Sound Pattern: 

ISO8201 (BI 0.5s - pause 0.5s - BI 0.5s - pause 0.5s - BI 

0.5s - pause 1.5s, with the RED LED flash, repeated this alarm 
pattern)

DESCRIPTION

The unit is a photoelectric smoke alarm device. It is particularly 
sensitive for detecting visible micro-particles (associated with 
smoldering fires) and reacts faster than ionization alarms. An 
example of such smoldering fires is a cigarette burning in a 
couch or bedding, a common cause of devastating blazes. Please 
note this device does not detect flames, heat, carbon monoxide or 
other hazardous gases. It has many advanced features and an 
extended operational life with the included battery.

RECOMMENDED LOCATIONS FOR ALARMS

1. The locations must comply with the applicable building 
regulations. BS 5839-6

:

2013 gives guidance on the number, types 

and positioning of alarms. In general, smoke alarms should be 
installed in every circulation space such as Hallways, Landings, 
Bedrooms and principal living spaces (living room). Larger 
spaces may require the use of more than one unit.

2. Installed on each and every storey.
3. Hot smoke rises and spreads out, so a central ceiling position is 
the preferred location. The air is “dead” and does not move into 
corners, therefore smoke must be mounted away from corners. 
Position the unit at least 30 cm away from walls and corners and 
30 cm away from any light fitting or decorative object witch may 
obstruct smoke entering the Alarm. (see the diagram 1).

4. When the ceiling is slanting, the alarm needs to be installed 
minimum 50cm away from the highest ceiling point in the room 
(see the diagram 2).

CAUTION: 

Our smoke alarm is also suitable for use in leisure 

accommodation vehicles (LAVs).

1

2

o

40 C. (due to nuisance/false alarm activation).

5. In extremely dusty, dirty, or insect infested areas where particles 
may interfere/obstruct with Alarm operation.

6. Away from air conditioning or ventilation grilles/ 
louvres.

 

ACTIVATION

Press test button and hold it for above 3 seconds until LED lights, 
and release it within 2 seconds, the unit will generate a “beep” 
indicates that it is activated and goes into work status.

INSTALLATION

WARNING:

 To prevent injury, this unit must be securely attached to 

the ceiling in accordance with the installation instructions.

Model: TSS380A-H

LOCATIONS TO AVOID

1. Don't place Alarms in bathrooms, Kitchens, Garages or other 
rooms where the Alarm may be triggered by steam, condensation 
and normal smoke/heat from appliances.

2. In areas with high humidity, like bathrooms or areas near 
dishwashers or washing machines, install at least 6 metres away 
from these areas.

3. Near air returns or heating and cooling supply vents, install at 
least 1m away from these areas. The air could blow smoke away 
from the detector, interrupting its alarm.

o

4. In rooms where temperature may fall below 0 C or rise above

OPERATION AND TESTING

Testing

Test by pushing the test button on the cover. This will sound the 
alarm if the electronic circuitry, alarm, and battery are working. If 
no alarm sounds, the unit has defective batteries or other failures.

DO NOT

  use an open flame to test your alarm, you could damage 

the alarm or ignite combustible materials and start a structure 
fire.

NOTE:

 Weekly Testing Is Required

Normal Condition

The red LED should flash every 48 seconds to show that the alarm 
is active.

Alarm Condition

When the Alarm senses products of combustion and sounds the 
audible alarm, the red LED will flash one flash/second. The 
flashing LED and pulsating alarm will continue until the air is 
cleared.

Low Power Pack Condition

IMPORTANT: 

Your smoke alarm requires the power pack to have 

sufficient capacity of power to operate correctly.

Should your smoke alarm enter a low power pack condition the 
unit will emit an audible chirp once every 48 seconds with light 
flash once. When this occurs you must replace the alarm 
immediately. Your smoke alarm will continue to warn of this low 
power pack condition for at least 30 days, however, failure to 
change the alarm after this time would mean your smoke alarm 
may have insufficient power to alert you in a real fire situation.

Installation Sketch Map

 

Diagram 3

 

Diagram 1

Ceiling

Best here

Never here

30 cm

 

Diagram 2

50

 cm

No

t in

 th

is a

rea

An

y w

he

re 

in 

thi

s a

rea

20

0 c

m

Never here

RD-380A-18-001     Rev A     2020.04.03

21

1116

DoP: RD-380A-H-24-001