Description

The top-entry sub D9 connector kit is designed for enclosure

sizes D1h–D8h, E1–E2, and E1h–E4h with VLT

®

 PROFIBUS DP

MCA 101 option. It fits the following drives:

VLT

®

 HVAC Drive FC 102

VLT

®

 Refrigeration Drive FC 103

VLT

®

 AQUA Drive FC 202

VLT

®

 AutomationDrive FC 302

This kit provides a top-entry sub D9 PROFIBUS connection that
maintains the IP protection rating of the drive up to IP54.

Part number

Kit description

176F1742

Top-entry sub D9 connector kit for enclosure sizes

D and E with PROFIBUS option

Table 1.1 Part Numbers for the Top-entry Sub D9 Connector Kit

The kit contains the following parts:

Item

Quantity

Connector plate

1

Gasket, connector plate

1

Sub D9 connector with wire assembly

1

Ground strap

1

Strain relief

1

Rubber cover

1

Jack screw

2

M4 screw, thread cutting

2

Table 1.2 Items Supplied in Top-entry Sub D9 Connector Kit

Safety Instructions

Only qualified, Danfoss authorized personnel are allowed to
install the parts described in these installation instructions.
Handling of the drive and its parts must be done in
accordance with the corresponding 

operating guide

.

WARNING

ELECTRICAL SHOCK HAZARD

VLT

®

 FC series drives contain dangerous voltages when

connected to mains voltage. Improper installation, and
installing or servicing with power connected, can cause
death, serious injury, or equipment failure.

To avoid death, serious injury, or equipment failure:

Only use qualified electricians for the installation.

Disconnect the drive from all power sources before
installation or service.

Treat the drive as live whenever the mains voltage
is connected.

Follow the guidelines in these instructions and local
electrical safety codes.

WARNING

DISCHARGE TIME

The drive contains DC-link capacitors, which can remain
charged even when the drive is not powered. High voltage
can be present even when the warning LED indicator lights
are off. Failure to wait 40 minutes after power has been
removed before performing service or repair work can result
in death or serious injury.

Stop the motor.

Disconnect AC mains and remote DC-link power
supplies, including battery back-ups, UPS, and DC-
link connections to other drives.

Disconnect or lock PM motor.

Wait 40 minutes for capacitors to discharge fully.

Before performing any service or repair work, use
an appropriate voltage measuring device to make
sure that the capacitors are fully discharged.

Installation Instructions

Top-entry Sub D9 Connector Kit for
Enclosure Sizes D and E with PROFIBUS Option
VLT

®

 FC Series FC 102, FC 103, FC 202, and FC 302

Danfoss A/S © 10/2017 All rights reserved.

MI38Q302

Summary of Contents for 176F1742

Page 1: ... when connected to mains voltage Improper installation and installing or servicing with power connected can cause death serious injury or equipment failure To avoid death serious injury or equipment failure Only use qualified electricians for the installation Disconnect the drive from all power sources before installation or service Treat the drive as live whenever the mains voltage is connected F...

Page 2: ... 7 1 Remove the front cover from the drive 2 Remove the local control panel LCP 3 Remove the LCP cradle by pulling the cradle outward See Illustration 1 1 4 Unfasten 2 M5 nuts 8 mm from the underside of the left cover plate and remove the plate from the drive enclosure Retain the 2 M5 nuts 1 Drive enclosure 3 LCP cradle 2 Left cover plate 4 LCP Illustration 1 1 Removal of LCP LCP Cradle and Left C...

Page 3: ...sub D9 connector are seated firmly on the metal surface of the plate and not on the gasket 5d Place the assembled connector plate into the opening at the top of the drive enclosure See Illustration 1 3 1 Gasket 2 Connector plate 3 Opening for connector 4 Screw post Illustration 1 2 Gasket Installed on Connector Plate Installation Instructions Top entry Sub D9 Connector Kit for Enclosure Sizes D an...

Page 4: ...ive enclosure Illustration 1 3 Connector Plate Installation Installation Instructions Top entry Sub D9 Connector Kit for Enclosure Sizes D and E with PROFIBUS Option VLT FC Series FC 102 FC 103 FC 202 and FC 302 4 Danfoss A S 10 2017 All rights reserved MI38Q302 ...

Page 5: ...r easier connector installation remove the PROFIBUS module before attaching the Phoenix connector Then reinstall the PROFIBUS module 7 Plug the Phoenix connector into the PROFIBUS module See Illustration 1 5 1 Phoenix connector 2 PROFIBUS module Illustration 1 5 Phoenix Connector Installation 8 When the sub D9 connector is not in use 8a Place the rubber cover over the connector See Illustration 1 ...

Page 6: ...e PROFIBUS module See Illustration 1 8 6 Fasten 1 M4 thread cutting screw T10 securing the strain relief in place 1 Bottom of left cover plate 2 M5 nut 3 Top of drive enclosure Illustration 1 7 Bottom View of Left Cover Plate from Inside Enclosure 1 M4 thread cutting screw 2 Strain relief Illustration 1 8 Strain Relief Installation Danfoss can accept no responsibility for possible errors in catalo...