Description
The tall pedestal kit contains all parts required to install the
tall pedestal for E1h and E2h drives. The tall pedestal is
400 mm (15.7 in) and replaces the standard pedestal that
ships with the drive.
Kit Ordering Numbers
Kit number
Kit description
176F6764
Tall pedestal kit for E1h
176F6763
Tall pedestal kit for E2h
Table 1.1 Ordering Numbers for the Tall Pedestal Kit
Items Supplied
The tall pedestal kit contains the following items. Refer to
Illustration 1.1
.
Item
Quantity
Pedestal
1
Front panel
1
Front top bracket
1
Front bottom bracket
1
Locking brackets
2
M10x22 screw
6
M8 hex nut
4
M5x14 countersunk screw
6
M10 nylon-insert lock nut
2
Table 1.2 Items Supplied in Tall Pedestal Kit
Safety Information
Only qualified, Danfoss authorized personnel are allowed to
install the parts described in these installation instructions.
Handling of the drive and its parts must be done in
accordance with the corresponding
operating guide
.
WARNING
ELECTRICAL SHOCK HAZARD
VLT
®
FC series drives contain dangerous voltages when
connected to mains voltage. Improper installation, and
installing or servicing with power connected, can cause
death, serious injury, or equipment failure.
To avoid death, serious injury, or equipment failure:
•
Only use qualified electricians for the installation.
•
Disconnect the drive from all power sources before
installation or service.
•
Treat the drive as live whenever the mains voltage
is connected.
•
Follow the guidelines in these instructions and local
electrical safety codes.
WARNING
DISCHARGE TIME
The drive contains DC-link capacitors, which can remain
charged even when the drive is not powered. High voltage
can be present even when the warning LED indicator lights
are off. Failure to wait 40 minutes after power has been
removed before performing service or repair work can result
in death or serious injury.
•
Stop the motor.
•
Disconnect AC mains and remote DC-link power
supplies, including battery back-ups, UPS, and DC-
link connections to other drives.
•
Disconnect or lock PM motor.
•
Wait 40 minutes for capacitors to discharge fully.
•
Before performing any service or repair work, use
an appropriate voltage measuring device to make
sure that the capacitors are fully discharged.
Installation Instructions
Tall Pedestal Kit for E1h/E2h Drives
VLT
®
FC Series FC 102, FC 103, FC 202, and FC 302
Danfoss A/S © 03/2018 All rights reserved.
MI35V102