1 Introduction

1.1 Purpose of the Installation Guide

This Installation Guide describes the replacement and the software update for the control card in VLT® Compressor Drive CDS 803.
VLT

®

 is a registered trademark for Danfoss A/S.

1.2 Safety Instructions

Only Danfoss authorized, qualified personnel are allowed to repair this equipment. The personnel must be familiar with the instruc-
tions and safety measures described in the VLT® HVAC Basic Drive FC 101 Service Manual.

W A R N I N G

DISCHARGE TIME

The drive contains DC-link capacitors, which can remain charged even when the drive is not powered. High voltage can be
present even when the warning indicator lights are off.
Failure to wait the specified time after power has been removed before performing service or repair work could result in death or
serious injury.

Stop the motor.
Disconnect AC mains, permanent magnet type motors, and remote DC-link supplies, including battery back-ups, UPS, and
DC-link connections to other drives.
Wait for the capacitors to discharge fully. The minimum waiting time is specified in the table 

Discharge time

 and is also visible

on the nameplate on the top of the drive.
Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the capacitors
are fully discharged.

Table 1: Discharge Time

Voltage [V]

Power range [kW (hp)]

Minimum waiting time (minutes)

3x200

6.0–10 (8.0–15)

15

3x400

6.0–7.5 (8.0–10)

4

3x400

10–30 (15–40)

15

1.3 Item Supplied

The following item is supplied:

Control card

Table 2: Code Numbers for Control Cards

Control card type

Code number

Control card, H3, H4, and H5

132B0700

Control card H6

132B1174

AN376926352883en-000101 / 130R1211 | 1

Danfoss A/S © 2021.05

Installation Guide

Control Card

VLT® Compressor Drive CDS 803