Installation guide
Contactors CI 6 - CI 30
Thermal overload relays TI 16C - TI 25C - TI 30C
03
7C
06
15
03
7C
06
15
© Danfoss | DCS (az) | 2017.10
IC.PI.C10.C2.00 | 520B7001 | 1
TI 16C / TI 25C / TI 30C
Conditional Short Circuit Rating - Suitable for use on
circuits capable of delivering not more than 100 000 rms
symmetrical amperes, 600 V maximum when protected
by Class J fuses
Before installing the contactor, make sure that the control voltage supply corresponds with the specified voltage.
Wrong control voltage across the terminals (A1 and A2) can cause contactor chattering or coil overheating and damage.
Control voltage must be applied within tolerances given below:
- Standard coil: from -15% to 10%
- Double frequency coil: ±10%