background image

© Copyright Danfoss | Commercial Compressors | 2014.12

FRCC.PI.015.A4.02 - December 2014 - 

8510274P01A

H series 

compressors

Instructions

70
65
60

SH 11K

55
50
45
40
35
30
25
20

-30

-20

-15

-25

-10

-5

5

0

10

15

Condensing T

emp

er

atur

(°C

)

Evaporating Temperature (°C)

70
65
60

SH 5K

SH 11K

HCJ120 & HCJ121

        

55
50
45
40
35
30
25
20-30

-20

-15

-25

-10

-5

5

0

10

15

Condensing T

emp

er

atur

(°C

)

Evaporating Temperature (°C)

70
65
60

SH 11K

55
50
45
40
35
30
25
20

-30

-20

-15

-25

-10

-5

5

0

10

15

Condensing T

emp

er

atur

(°C

)

Evaporating Temperature (°C)

SH 5K

SH 10K

70
65
60
55
50
45
40
35
30
25
20

Condensing T

emp

er

atur

(°C

)

-30

-20

-15

-25

-10

-5

5

0

10

15

Evaporating Temperature (°C)

A

:  Model number

B

:  Technical number 

C

:  Serial Number

D

:  Manufacturing year

E

:  Internal protection

F

:  Supply voltage range

G

:  Run capacitor

H

:  Locked rotor current 

 

Maximum operating current

I

:  

Lubricant type and nominal charge

J

:  Approved Refrigerant

Hrm/HLm/HCm-HrP/HLP/HCP model variation T 

(r22/407C)

 

HrH/HLH/HLJ/HCJ

model variation T (r410A) 

Hrm/HLm/HCm - HrH/HLH/HLJ/HCJ

model variation U (r22 / r410A) 

HHP (r407C)

Installation and servicing of the compressor by qualified personnel only. Follow these 

instructions and sound refrigeration engineering practice relating to installation, 

commissioning, maintenance and service.

 The compressor must only be 

used for its designed purpose(s) 

and within its scope of application 

(refer to «operating limits»). Consult 

Application guidelines and datasheet 

available from cc.danfoss.com

 Never operate 

compressor without 

terminal box cover in 

place and secured. 

 Under all circumstances, the 

EN378 (or other applicable local 

safety regulation) requirements 

must be fulfilled. 

Wear protective goggles and 

work gloves.

The compressor is delivered under nitrogen gas pressure 

(between 0.3 and 0.4 bar / 4 and 6 psi). Do not disassemble 

bolts, plugs, fittings, etc... unless all pressure has been 

relieved from the compressor.

The compressor must be handled 

with caution in the vertical 

position (maximum offset from 

the vertical : 15°).

C

S

R

Line

Run 
Capacitor

Start 
Capacitor

Potential 
Relay

1

2

5

C

S

R

Line

Run 
Capacitor

Quick connect spade terminals

P terminal box type

push

push

push

A

B

C

D

E

F

G

H

I

J

PSC wiring

CSr wiring

Operating limits

Electrical connections

Single phase

C

T₁

Ring connect screw terminals

C terminal box type

S

T₂

R

T₃

Quick connect spade terminals 

P & T terminal box type

ring connect screw terminals

C & Q terminal box type

When HRM compressors are used with R417A, the 

factory charged oil must be replaced by PVE oil 320HV 

(120Z5034).

Brazed connection 

Rotolock connection

Models

Connec. 

size

Models

Connec. 

size

HRM032-042

HRP034-042

HRM/HRP045-047

HRH029-040

Suction 

3/4"

Disch. 1/2"

-

-

HRM/HRP048-060

HLM/HLP068-075

HRH041-056

HLH061-068

HLJ061-068

Suction 

7/8"

Disch.  1/2"

HRH044-

056

HLH061-

068

HLJ072-083

Suct. 1"1/4

Disch. 1"

HLM/HLP078-081

Suction 

7/8"

Disch. 3/4"

-

-

HCM/HCP094-120 

HCJ090-121

Suct. 1"1/8

Disch. 7/8"

-

-

1 – Introduction

These instructions pertain to the Danfoss scroll 

compressors used for HVAC systems. They provide 

necessary information regarding safety and proper 

usage of this product.

2 – Handling and storage

 •   Handle the compressor with care. Use the dedicated 

handles in the packaging. Use the compressor lifting 

lug and use appropriate and safe lifting equipment.

 •   Store and transport the compressor in an upright 

position.

 •  Store the compressor between -35°C and 70°C 

(31°F and 158°F).

 •  Don’t expose the compressor and the packaging 

to rain or corrosive atmosphere.

3 – Safety measures before assembly

 Never use the compressor in a flammable atmosphere.

 •  Mount the compressor on a horizontal flat surface 

with less than 7° slope.

Reviews: